Product data
Duct Free Systems - Electrical Data - 40 Series Console Units
Model Voltage Voltage Fan Heater Power Minimum
V-Ph-60Hz Min Max FLA kW FLA MCA MOCP FLA Wire Size
40CG-018---301RM 208/230-1 187 253 0.6 -- -- 0.8 15 0.6 14
40CG-024---301RM 208/230-1 187 253 0.6 -- -- 0.8 15 0.6 14
40CG-030---301RM 208/230-1 187 253 0.6 -- -- 0.8 15 0.6 14
40CS-018---301RM 208/230-1 187 253 0.6 2.0 9.0 11.5 25 8.9 14
40CS-024---301RM 208/230-1 187 253 0.6 3.0 13.6 17.0 35 13.1 10
40CS-030---301RM 208/230-1 187 253 0.6 3.0 13.6 17.0 40 13.1 10
Legend:
* One fan is 1.1 Amps, the second fan is 0.5 Amps
** Two fans each operating at 1.3 Amps
~ The QAB/QAE018 is a QAB/QAE024 using a different motor speed fan tap plug.
FLA - Full Load Amps
LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps
Rev "A"
MOCP - Maximum Overcurrent Protection Amps. (Fuse or Heating, Air Conditioning, and Refrigeration Circuit Breaker
01/09/02