Product data
Duct Free Systems - Electrical Data - 40 Series Under Ceiling Units
Model Voltage Voltage Fan Heater Power Minimum
V-Ph-60Hz Min Max FLA kW FLA MCA MOCP FLA Wire Size
40QAB018-3~ 208/230-1 187 253 0.50 -- -- 0.63 15.0 0.50 14
40QAB024-3 208/230-1 187 253 0.50 -- -- 0.63 15.0 0.50 14
40QAB036-3 208/230-1 187 253 1.30 -- -- 1.60 15.0 1.30 14
40QAB048-3 208/230-1 187 253 1.60 * -- -- 2.00 15.0 1.60 14
40QAB060-3 208/230-1 187 253 2.60 ** -- -- 3.30 15.0 2.60 14
40QAE018-3~ 208/230-1 187 253 0.50 2.00 8.66 9.29 15.0 11.29 14
40QAE024-3 208/230-1 187 253 0.50 2.00 8.66 9.29 15.0 11.29 14
40QAE036-3 208/230-1 187 253 1.30 3.00 13.00 17.70 20.0 14.30 14
40QAE048-3 208/230-1 187 253 1.60 * 4.00 17.40 23.80 25.0 19.00 12
40QAE060-3 208/230-1 187 253 2.60 ** 5.00 21.70 28.70 30.0 24.30 10