Product data

Duct Free Systems - Piston/Charge Combinations
Cooling Only High Wall Heat Pump High Wall
Indoor Outdoor AccuRater Charge Indoor Outdoor AccuRater AccuRater Charge
Unit Unit Piston Lbs Unit Unit Piston Piston Lbs
No
Note #1
Indoor Outdoor
Note #1
40QNB009 38AN-009-1 Cap Tube 1.5 40QNE009 38BK-009-1 32 * 30 * 1.5
40QNB012-1 38AN-012-1 Cap Tube 1.8 40QNH012 38BK-012-3 42 * 42 * 2.0
40QNB012-3 38AN-012-3 Cap Tube 1.8 40QNH018 38BK-018-3 51 47 4.95
40QNB018 38HDC018 49 4.6 40QNH024 38BK-024-3 59 52 5.1
38HDL018 49 3.8
40QNB024 38HDL018 49 3.8
38HDC024 57 6.0 Heat Pump Under Ceiling
38HDL024 57 4.4
Indoor Outdoor AccuRater AccuRater Charge
Cooling Only Under Ceiling
Unit Unit Piston Piston Lbs
Indoor Outdoor
Note #1
Indoor Outdoor AccuRater Charge
40QAE024 38QR-018C-3 55 49 4.3
Unit Unit Piston Lbs
38QR-024C-3 55 49 6.3
No
Note #1 40QAE036 38QR-030C-3 63 55 6.4
40QAB024 ^ 38HDC018-3 53 3.7 38QR-036C-3 63 61 7.5
38HDL018-3 53 4.3 38QR-036C-5 63 61 8.7
40QAB024 38HDC024-3 57 6.3 38QR-036C-6 63 61 8.7
38HDL024-3 57 4.9 ** 40QAE048 38QR-048C-3 84 78 10.0
40QAB036 38HDC030-3 65 7.1 38QR-048C-5 84 78 10.0
38HDL030-3 65 5.2 38QR-048C-6 84 78 10.0
40QAB036 38HDC036-3 70 5.4 40QAE060 38QR-060C-3 96 82 11.9
38HDC036-5 70 5.4 38QR-060C-5 96 82 11.9
38HDC036-6 70 5.4 38QR-060C-6 96 82 11.9
38HDL036-3 70 5.0
40QAB048 38HDC048-3 84 7.4 Heat Pump Cassette
38HDC048-5 84 7.4
38HDC048-6 84 7.4
Indoor Outdoor AccuRater AccuRater Charge
38HDL048-3 84 7.1
Unit Unit Piston Piston Lbs
40QAB060 38HDC060-3 93 13.6
Indoor Outdoor
Note #1
38HDC060-5 93 13.6 40QKE024 38QR-018C-3 51 49 5.5
38HDC060-6 93 13.6 40QKE036 38QR-024C-3 61 49 5.9
38HDL060-3 93 13.6 38QR-030C-3 63 55 5.9
40QKE048 38QR-036C-3 67 59 5.9
Cooling Only Cassette 38QR-036C-5 67 59 8.0
38QR-036C-6 67 59 8.0
Indoor Outdoor AccuRater Charge
Unit Unit Piston Lbs
Heat Cool Under Ceiling
No
Note #1
COOLING WITH ELECTRIC HEAT
40QKB024 ^ 38HDC018-3 52 4.8 **
Indoor Outdoor AccuRater Charge
38HDL018-3 52 3.9
Unit Unit Piston Lbs
40QKB036 38HDC024-3 62 5.4
No
Note #1
38HDL024-3 62 4.6 40QAE024 38HDC018-3 52 3.6
38HDC030-3 63 5.2 38HDC024-3 53 6.2 **
38HDL030-3 63 5.6 38HDL018-3 52 4.3
38HDC036-3 65 6.0 ** 38HDL024-3 53 4.9 **
38HDC036-5 65 6.0 ** 40QAE036 38HDC030-3 63 5.6
38HDC036-6 65 6.0 ** 38HDC036-3,5,6 65 5.6
38HDL036-3 65 6.0 ** 38HDL030-3 63 5.2
38HDL036-3 65 5.0
Satellite 40QAE048 38HDC048-3,5,6 84 7.4
38HDL048-3 84 7.1
Indoor Outdoor AccuRater Charge
40QAE060 38HDC060-3,5,6 93 13.6
Unit Unit Piston Lbs
38HDL060-3 93 8.7
No
Note #1
40HD-024 38HDC024-3 57 5.5 Heat Cool Cassette
38HDL024-3 57 4.4
COOLING WITH ELECTRIC HEAT
40HD-036
38HDC036-3,5,6
73 6.3
Indoor Outdoor AccuRater Charge
38HDL036 73 5.8
Unit Unit Piston Lbs
40HD048
38HDC048-3,5,6
90 7.8
No
Note #1
38HDL048 90 7.9 40QKE024 38HDC018-3 52 5.8 **
38HDL018-3 52 3.9
Legend:
40QKE036 38HDC024-3 62 4.8
* Non-serviceable Aeroquip piston
38HDL024-3 62 4.6
** Combination may require additional charge
38HDC030-3 63 5.2
^ The 024 size unit shown is configured as an 018 size unit changing
38HDL030-3 63 5.6
the motor speed fan tap plug.
40QKE048 38HDC036-3,5,6 67 5.8
38HDL036-3 67 6.0
Note:
1) Charge is based on 25' of interconnecting tubing. Charge may
need to be added for longer runs.
2) Cooling units shipped with a full charge. Heat Pumps are
Rev "A"
shipped with a holding charge
02/15/02