Product data
COOLINGCAPACITIES(cont)
TABLE NO. 59 - 42WKN016
Entering
Water
Temp (F)
Water
Temp
Rise (F)
Entering Air (F) — dry bulb
72 80
Entering Air (F) — wet bulb
63 67 71 63 67 71
TH SH TH SH TH SH TH SH TH SH TH SH
40
10 26,652 17,990 35,692 17,453 25,524 16,571 27,498 24,913 35,634 24,231 45,476 30,474
15 18,250 14,381 27,410 14,061 37,654 13,518 22,536 21,770 27,620 20,908 37,604 27,378
20 11,790 10,894 17,016 10,090 27,920 9,940 18,442 18,331 20,094 17,522 27,872 23,966
45
10 18,014 14,321 26,990 13,873 36,734 13,151 21,878 21,528 27,018 20,669 36,686 26,919
15 11,684 10,948 17,920 10,184 27,942 9,947 18,146 18,146 19,724 17,456 27,892 23,849
20 7,120 7,099 7,798 6,363 16,468 6,011 14,366 14,366 14,682 14,124 17,698 20,685
55
10 6,852 6,852 7,544 6,420 16,556 6,026 13,698 13,698 13,770 13,715 17,028 20,061
15 3,032 3,032 3,042 3,015 3,750 1,958 9,952 9,952 9,982 9,982 10,366 16,935
20 ——————5,742 5,742 5,754 5,754 5,766 13,204
42WKN016 (cont)
Entering
Water
Temp (F)
Water
Temp
Rise (F)
Entering Air (F) — dry bulb
88
Entering Air (F) — wet bulb
63 67 71
TH SH TH SH TH SH
40
10 31,916 31,884 36,000 31,104 45,416 30,474
15 28,664 28,664 30,166 28,115 37,590 27,378
20 25,166 25,166 24,932 24,932 23,966 23,966
45
10 28,046 28,046 29,160 27,731 36,624 26,919
15 24,792 24,792 25,076 24,725 28,908 23,849
20 21,260 21,260 21,326 21,305 22,484 20,685
55
10 20,278 20,278 20,340 20,340 20,936 20,061
15 16,868 16,868 16,920 16,920 17,020 16,935
20 13,122 13,122 13,162 13,162 13,204 13,204
LEGEND Click here to view Systems Index Table.
SH — Sensible Heat
TH — Total Heat
TABLE NO. 60 - 42WKN020—2-TUBE
Entering
Water
Temp (F)
Water
Temp
Rise (F)
Entering Air (F) — dry bulb
72 80
Entering Air (F) — wet bulb
63 67 71 63 67 71
TH SH TH SH TH SH TH SH TH SH TH SH
40
10 27,298 17,744 36,590 17,673 46,402 17,354 28,158 24,216 36,540 23,897 46,346 23,729
15 18,986 14,145 28,240 14,148 38,744 14,142 22,896 21,362 28,602 20,508 38,696 20,509
20 12,208 10,767 17,680 10,025 28,920 10,382 18,646 18,254 20,816 17,194 28,958 16,709
45
10 18,676 14,007 27,896 13,976 37,834 13,772 21,966 20,999 28,016 20,256 37,776 20,097
15 12,062 10,795 18,010 10,140 28,914 10,351 18,190 18,063 20,424 17,074 28,886 16,667
20 7,876 7,695 8,680 6,501 17,104 6,192 14,506 14,506 15,056 13,987 18,614 12,899
55
10 6,942 6,942 7,872 6,313 17,262 6,214 13,664 13,664 13,840 13,577 17,836 12,646
15 3,460 3,460 3,480 3,355 4,512 2,130 10,082 10,082 10,116 10,116 10,772 9,544
20 ——————6,444 6,444 6,458 6,458 6,496 6,347
42WK020 — 2-TUBE (cont)
Entering
Water
Temp (F)
Water
Temp
Rise (F)
Entering Air (F) — dry bulb
88
Entering Air (F) — wet bulb
63 67 71
TH SH TH SH TH SH
40
10 31,530 31,089 36,916 30,234 46,282 29,944
15 28,348 28,291 30,874 27,385 38,798 26,771
20 25,114 25,114 26,032 24,522 30,538 23,423
45
10 27,552 27,552 29,754 26,927 37,744 26,308
15 24,588 24,588 25,254 24,244 30,004 23,221
20 21,306 21,306 21,446 21,253 23,318 20,263
55
10 20,020 20,020 20,094 20,094 21,342 19,613
15 16,894 16,894 16,956 16,956 17,190 16,812
20 13,286 13,286 13,332 13,332 13,380 13,380
LEGEND Click here to view Systems Index Table.
SH — Sensible Heat
TH — Total Heat