Product data

COOLINGCAPACITIES
TABLE NO. 55 - 42WKN004
Entering
Water
Temp (F)
Water
Temp
Rise (F)
Entering Air (F) dry bulb
72 80
Entering Air (F) wet bulb
63 67 71 63 67 71
TH SH TH SH TH SH TH SH TH SH TH SH
40
10 6,807 5,160 9,525 4,848 12,370 4,379 7,520 7,452 9,514 7,164 12,364 6,788
15 4,091 3,882 6,306 3,613 9,348 3,319 6,099 6,099 6,532 5,938 9,336 5,667
20 2,585 2,285 2,850 2,337 5,729 2,080 4,703 4,703 4,697 4,688 5,712 4,408
45
10 4,381 4,092 6,882 3,826 9,728 3,453 6,273 6,273 6,889 6,133 9,712 5,800
15 2,754 2,754 3,318 2,552 6,384 2,298 4,905 4,905 4,918 4,884 6,368 4,623
20 1,726 1,726 1,753 1,646 2,469 1,035 3,498 3,498 3,504 3,504 3,623 3,427
55
10 1,659 1,659 1,657 1,649 3,633 1,399 3,810 3,810 3,818 3,818 4,062 3,733
15 731 731 732 732 813 508 2,416 2,416 2,421 2,421 2,426 2,426
20 1,398 1,398 1,400 1,400 1,401 1,401
42WKN004 (cont)
Entering
Water
Temp (F)
Water
Temp
Rise (F)
Entering Air (F) dry bulb
88
Entering Air (F) wet bulb
63 67 71
TH SH TH SH TH SH
40
10 9,514 9,514 9,777 9,445 12,356 9,119
15 8,196 8,196 8,212 8,212 9,324 7,981
20 6,838 6,338 6,851 6,851 7,009 6,778
45
10 8,328 8,328 8,344 8,344 9,704 8,113
15 7,014 7,014 7,028 7,028 7,224 6,949
20 5,665 5,665 5,676 5,676 5,688 5,688
55
10 5,908 5,908 5,920 5,920 5,933 5,933
15 4,588 4,588 4,597 4,597 4,607 4,607
20 3,211 3,211 3,217 3,217 3,224 3,224
LEGEND Click here to view Systems Index Table.
SH Sensible Heat
TH Total Heat
TABLE NO. 56 - 42WKN008
Entering
Water
Temp (F)
Water
Temp
Rise (F)
Entering Air (F) dry bulb
72 80
Entering Air (F) wet bulb
63 67 71 63 67 71
TH SH TH SH TH SH TH SH TH SH TH SH
40
10 13,097 8,854 17,553 8,583 22,397 8,153 13,524 12,266 17,525 11,935 22,373 11,656
15 8,931 7,064 13,436 6,893 18,497 6,640 11,071 10,706 13,544 10,280 18,472 10,086
20 5,756 5,336 8,286 4,938 13,658 4,862 9,049 9,004 9,840 8,610 13,632 8,261
45
10 8,837 7,043 13,266 6,819 18,065 6,467 10,760 10,588 13,282 10,174 18,024 9,905
15 5,721 5,372 8,445 4,991 13,696 4,876 8,915 8,915 9,682 8,588 13,672 8,272
20 3,493 3,483 3,802 3,114 8,011 2,932 7,041 7,041 7,191 6,925 8,636 6,451
55
10 3,359 3,359 3,688 3,153 8,107 2,951 6,734 6,734 6,768 6,741 8,348 6,370
15 1,495 1,495 1,499 1,486 1,848 965 4,789 4,879 4,894 4,894 5,075 4,740
20 ——————2,825 2,285 2,831 2,831 2,837 2,837
42WKN008 (cont)
Entering
Water
Temp (F)
Water
Temp
Rise (F)
Entering Air (F) dry bulb
88
Entering Air (F) wet bulb
63 67 71
TH SH TH SH TH SH
40
10 15,714 15,698 17,708 15,300 22,344 15,015
15 14,099 14,099 14,820 13,842 18,467 13,443
20 12,366 12,366 12,588 12,261 14,352 11,783
45
10 13,808 13,808 14,350 13,661 18,011 13,256
15 12,193 12,193 12,327 12,154 14,183 11,729
20 7,041 7,041 10,473 10,463 11,025 10,165
55
10 9,980 9,980 10,011 10,011 10,300 9,919
15 8,289 8,289 8,314 8,314 8,362 8,320
20 6,434 6,434 6,453 6,453 6,474 6,474
LEGEND Click here to view Systems Index Table.
SH Sensible Heat
TH Total Heat