Product data

Duct Free Systems - Electrical Data - 40 Series High Wall Units
Model Voltage Voltage Fan Heater Power Minimum
V-Ph-60Hz Min Max FLA kW FLA MCA MOCP FLA Wire Size
40QNB009-1 115-1 104 127 0.41 -- -- Note #1 Note #1 0.41 14
40QNB012-1 115-1 104 127 0.55 -- -- Note #1 Note #1 0.55 14
40QNB012-3 208/230-1 187 253 0.23 -- -- Note #1 Note #1 0.23 14
40QNB018-3 208/230-1 187 253 0.53 -- -- 0.66 15.0 0.53 14
40QNB024-3 208/230-1 187 253 0.53 -- -- 0.66 15.0 0.53 14
40QNE009-1 115-1 104 127 0.41 -- -- Note #1 Note #1 0.41 14
40QNH012-3 208/230-1 187 253 0.23 0.75 3.30 Note #1 Note #1 0.23 14
40QNH018-3 208/230-1 187 253 0.53 1.80 7.80 10.90 15.0 0.53 14
40QNH024-3 208/230-1 187 253 0.53 1.80 7.80 10.90 15.0 0.53 14
Notes:
1)
I
n
d
oor un
it
mus
t
b
e connec
t
e
d
t
o ou
td
oor un
it
.
S
ee ou
td
oor un
it
f
or
d
a
t
a.
Legend:
FLA - Full Load Amps
LRA
-
L
oc
k
e
d
R
o
t
or
A
mps
MCA
-
Mi
n
i
mum
Ci
rcu
it
A
mps
R
ev
"A"
MOCP - Maximum Overcurrent Protection Amps. (Fuse or Heating, Air Conditioning, and Refrigeration Circuit Breaker
01/09/02