Product data
INSTANTANEOUSANDINTEGRATEDHEATINGRATINGS(cont)
SYSTEM37H*—CEILING-SUSPENDEDSYSTEM(38QR-C060WITH40QAE060)
TEMP (F)
AIR
ENTERING
INDOOR UNIT
AIR
ENTERING
INDOOR UNIT
(CFM)
AIR TEMPERATURE ENTERING OUTDOOR COIL (F)
010172030404760
55
1040
Cap 21.70 19.90 28.00 25.60 32.50 29.60 34.70 31.30 42.00 36.80 50.70 50.70 57.70 57.70 69.80 69.80
kW 3.34 3.70 3.96 4.07 4.45 4.88 5.20 5.72
1220
Cap 22.30 20.50 28.70 26.30 33.20 30.30 35.50 32.00 43.00 37.70 51.90 51.90 58.80 58.80 70.30 70.30
kW 3.38 3.72 3.96 4.07 4.41 4.80 5.08 5.51
1600
Cap 23.20 21.30 29.70 27.20 34.30 31.30 36.70 33.10 44.50 39.00 53.00 53.00 58.40 58.40 69.90 69.90
kW 3.46 3.77 3.99 4.08 4.40 4.68 4.85 5.20
60
1040
Cap 20.80 19.10 27.20 24.90 31.70 28.90 33.90 30.60 41.10 36.10 49.70 49.70 56.80 56.80 69.80 69.80
kW 3.36 3.75 4.02 4.13 4.53 4.98 5.34 5.95
1220
Cap 21.40 19.70 27.90 25.50 32.50 29.60 34.70 31.30 42.10 36.90 51.00 51.00 57.90 57.90 69.70 69.70
kW 3.41 3.77 4.02 4.14 4.50 4.92 5.22 5.69
1600
Cap 22.40 20.60 29.00 26.50 33.60 30.60 35.90 32.40 43.60 38.20 52.10 52.10 58.50 58.50 69.30 69.30
kW 3.50 3.83 4.07 4.16 4.50 4.81 5.04 5.38
65
1040
Cap 19.80 18.20 26.30 24.00 30.80 28.10 33.00 29.80 40.20 35.30 48.70 48.70 55.70 55.70 68.60 68.60
kW 3.38 3.78 4.06 4.18 4.60 5.07 5.45 6.08
1220
Cap 20.40 18.80 27.00 24.70 31.60 28.80 33.80 30.50 41.20 36.10 50.00 50.00 56.90 56.90 69.00 69.00
kW 3.42 3.81 4.08 4.19 4.59 5.02 5.35 5.85
1600
Cap 21.40 19.70 28.10 25.70 32.80 29.90 35.10 31.60 42.70 37.40 51.40 51.40 58.00 58.00 68.80 68.80
kW 3.52 3.88 4.13 4.23 4.59 4.94 5.19 5.55
70
1040
Cap 18.80 17.30 25.40 23.20 30.00 27.30 32.10 29.00 39.40 34.50 47.80 47.80 54.50 54.50 67.50 67.50
kW 3.39 3.91 4.10 4.23 4.68 5.17 5.55 6.22
1220
Cap 19.40 17.90 26.10 23.90 30.80 28.10 33.00 29.80 40.30 35.40 49.00 49.00 56.00 56.00 68.20 68.20
kW 3.44 3.85 4.13 4.25 4.67 5.12 5.48 6.02
1600
Cap 20.50 18.80 27.20 24.90 32.00 29.20† 34.30 30.90 41.80 36.60 50.80 50.80 57.50 57.50† 68.30 68.30
kW 3.54 3.92 4.19 4.30 4.68 5.08 5.35 5.73
75
1040
Cap 17.70 16.30 24.30 22.20 28.90 26.40 31.10 28.10 38.40 33.70 46.70 46.70 53.30 53.30 66.20 66.20
kW 3.40 3.83 4.13 4.27 4.73 5.24 5.64 6.35
1220
Cap 18.40 16.90 25.10 23.00 29.80 27.20 32.00 28.90 39.40 34.50 48.00 48.00 54.90 54.90 67.40 67.40
kW 3.45 3.87 4.16 4.29 4.73 5.21 5.59 6.18
1600
Cap 19.40 17.80 26.30 24.10 31.20 28.40 33.40 30.10 40.90 35.80 49.80 49.80 56.70 56.70 68.60 68.60
kW 3.56 3.96 4.24 4.36 4.76 5.19 5.49 5.96
80
1040
Cap 16.60 15.30 23.20 21.20 27.80 25.30 30.00 27.10 37.40 32.80 45.70 45.70 52.10 52.10 65.10 65.10
kW 3.41 3.85 4.16 4.30 4.78 5.31 5.72 6.49
1220
Cap 17.20 15.80 24.00 21.90 28.70 26.20 31.00 27.90 38.50 33.70 46.90 46.90 53.60 53.60 66.60 66.60
kW 3.46 3.89 4.19 4.33 4.79 5.30 5.68 6.34
1600
Cap 18.20 16.80 25.20 23.10 30.20 27.50 32.40 29.20 40.00 35.00 48.80 48.80 55.60 55.60 66.90 66.90
kW 3.57 3.98 4.27 4.40 4.83 5.28 5.60 6.06
Indicates rating condition.
Indicates integrated rating.
LEGEND
Cap — Heating Capacity (1000 Btuh) (includes indoor-fan motor heat)
kW — Total Power Input (includes compressor motor power input, outdoor-
fan motor power input, and indoor-fan motor power input)
*Click here to view SystemsIndexTable.
†Integrated Rating.
NOTE: Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the
outdoor coil and the heat required to defrost it.