Product data

COOLING CAPACITIES (cont)
SYSTEM 26* 38HDL036 WITH 40QKB036
LEGEND Rating Condition
Not recommended for long-term operation
*Click here to view Systems Index Table.
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80 F edb temperature of air entering indoor
coil.
Below 80 F edb, subtract (corr factor x cfm) from SHG.
Above 80 F edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
TEMP (F)
AIR ENTERING
CONDENSER
(Edb)
AIR ENTERING EVAPORATOR — CFM/BF
635/0.02 745/0.03 915/0.04
Air Entering Evaporator — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
55
TCG
32.4 34.8 35.3 35.7 33.9 35.1 35.4 35.3 35.1 35.3 35.8
35.6
SHG
29.5 25.9 21.4 17.2 32.0 26.8 21.7 17.5 34.2 27.5 22.2 17.1
TC
32.0 34.3 34.8 35.3 33.5 34.6 35.0 34.7 34.4 34.6 35.1 35.0
kW
2.29 2.35 2.36 2.38 2.35 2.38 2.40 2.39 2.42 2.43 2.45 2.44
CMP
2.03 2.08 2.10 2.11 2.06 2.09 2.11 2.10 2.09 2.10 2.11 2.11
LDB
34.1 39.7 47.0 53.5 37.7 44.7 51.5 57.2 43.2 50.6 56.4 62.1
LWB
32.9 38.5 45.8 53.0 36.0 42.5 49.5 56.7 40.0 46.7 53.2 59.8
65
TCG
30.8 34.3 36.9 37.6 32.6 35.9 37.4 37.9 35.2 37.1 37.6 38.7
SHG
28.8 25.9 22.5 18.1 31.5 27.9 23.1 18.5 35.2 29.9 23.8 19.0
TC
30.4 33.8 36.5 37.1 32.1 35.4 36.8 37.4 34.5 36.5 36.9 38.1
kW
2.49 2.56 2.63 2.65 2.57 2.63 2.67 2.69 2.64 2.70 2.72 2.76
CMP
2.22 2.30 2.36 2.38 2.28 2.34 2.37 2.39 2.31 2.37 2.38 2.43
LDB
35.3 39.8 45.3 52.2 38.3 43.2 49.6 55.8 42.2 48 54.7 60
LWB
34.3 38.9 44.6 51.8 37.0 41.9 48.3 55.2 40.0 45.7 52.3 58.5
75
TCG
28.0 32.6 36.2 38.8 30.4 34.4 37.6 39.0 33.8 36.5 38.9 40.2
SHG
27.1 25.1 22.2 18.6 30.2 27.3 23.5 19.0 33.8 30.3 25.1 19.8
TC
27.5 32.1 35.7 38.4 29.8 33.8 37.0 38.5 33.2 35.8 38.3 39.6
kW
2.68 2.76 2.85 2.93 2.75 2.84 2.91 2.96 2.86 2.92 3.00 3.05
CMP
2.42 2.50 2.58 2.66 2.46 2.55 2.61 2.67 2.53 2.59 2.66 2.72
LDB
38.0 41.2 45.8 51.4 40.1 44.1 49.2 55.2 43.7 47.6 53.3 59.0
LWB
36.9 40.3 45.1 51.0 38.7 43.0 48.2 54.6 40.7 46.0 51.7 58.0
85
TCG
25.9 29.4 34.5 38.1 28.5 31.8 36.2 39.4 31.7 34.6 38.2 40.6
SHG
25.8 23.4 21.3 18.3 28.5 25.9 22.9 19.2 31.7 29.4 25.1 20.1
TC
25.4 29.0 34.0 37.6 27.9 31.2 35.6 38.9 31.0 33.9 37.4 40.0
kW
2.87 2.97 3.06 3.17 2.95 3.04 3.15 3.24 3.08 3.12 3.23 3.32
CMP
2.61 2.71 2.79 2.90 2.66 2.75 2.86 2.94 2.75 2.79 2.90 2.99
LDB
40.0 43.8 47.1 51.9 42.4 45.8 49.9 55 46.1 48.5 53.3 58.7
LWB
38.8 42.9 46.4 51.5 40.1 44.7 49.0 54.4 41.9 47.0 52.1 57.8
95
TCG
24.0 26.8 31.9 36.3 26.3 29.0 34.2 38.0 29.6 31.6
33.0 39.5
SHG
24.0 22.1 20.1 17.5 26.3 24.5 22.0 18.5 29.6 28.1
22.2 19.7
TC
23.5 26.3 31.4 35.8 25.8 28.4 33.7 37.4 29.0 30.9
32.3 38.8
kW
3.08 3.17 3.27 3.39 3.17 3.24 3.34 3.48 3.28 3.32
3.45 3.56
CMP
2.82 2.90 3.00 3.12 2.88 2.94 3.05 3.18 2.95 2.99
3.12 3.23
LDB
42.9 45.9 49.0 53.2 45.4 47.7 51.1 55.8 48.3 50.0
54.2 59.1
LWB
40.3 44.9 48.3 52.7 41.6 46.5 50.2 55.2 43.0 48.5
53.0 58.2
105
TCG
22.6 24.9 28.9 34.3 24.8 26.0 31.2 35.9 27.7 28.4 33.9 37.7
SHG
22.6 21.2 18.7 16.6 24.8 23.2 20.7 17.7 27.7 26.6 23.4 19.1
TC
22.1 24.4 28.4 33.8 24.3 25.5 30.7 35.3 27.1 27.7 33.3 36.9
kW
3.28 3.35 3.48 3.59 3.36 3.43 3.55 3.68 3.48 3.52 3.64 3.79
CMP
3.02 3.08 3.21 3.32 3.07 3.14 3.25 3.39 3.15 3.19 3.31 3.46
LDB
45.1 47.3 51.2 54.5 47.3 49.6 52.9 57 50.3 51.6 55.2 59.8
LWB
41.5 46.3 50.4 54.0 42.5 48.3 51.9 56.3 44.0 50.1 54.0 59.0
115
TCG
21.2 23.1 26.9 31.4 23.4 24.1 28.0 33.7 25.7 26.3 30.6 35.3
SHG
21.2 20.3 17.9 15.4 23.4 22.3 19.4 16.8 25.7 25.7 22.0 18.2
TC
20.7 22.7 26.4 30.9 22.8 23.5 27.4 33.2 25.0 25.7 29.9 34.7
kW
3.48 3.51 3.66 3.80 3.56 3.60 3.75 3.88 3.70 3.69 3.84 3.99
CMP
3.21 3.25 3.39 3.53 3.26 3.31 3.46 3.58 3.37 3.36 3.50 3.66
LDB
47.3 48.7 52.6 56.5 49.3 50.8 54.8 58.2 52.6 52.6 56.7 60.8
LWB
42.5 47.6 51.8 55.8 43.5 49.5 53.8 57.4 45.2 51.0 55.5 59.9
125
TCG
19.8 20.6 25.0
29.0 21.9 22.1 25.9 30.5 24.0 24.0 27.2 32.9
SHG
19.8 19.2 17.0
14.5 21.9 21.4 18.5 15.5 24.0 24.0 20.6 17.3
TC
19.4 20.1 24.5
28.6 21.3 21.6 25.4 29.9 23.3 23.3 26.5 32.2
kW
3.67 3.70 3.83 3.99 3.75 3.76 3.92 4.08 3.89 3.89 4.03 4.18
CMP
3.40 3.43 3.56
3.72 3.45 3.47 3.63 3.79 3.56 3.56 3.70 3.84
LDB
49.5 50.5 53.9
57.9 51.3 51.9 55.9 59.9 54.5 54.5 58.2 61.8
LWB
43.6 49.4 53.0 57.2 44.5 50.7 54.9 59.1 46.0 52.1 56.9 60.9
BF
Bypass Factor
CMP
Compressor
Edb
Entering Dry Bulb
Ewb
Entering Wet Bulb
kW
Total Power
LDB
Leaving Dry Bulb
LWB
Leaving Wet Bulb
SHG
Gross Sensible Capacity (1000 Btuh)
TC
Total Net Cooling Capacity (1000 Btuh)
TCG
Gross Cooling Capacity (1000 Btuh)