Product data

COOLING CAPACITIES (cont)
SYSTEM 25* 38HDL030 WITH 40QKB036
LEGENDRating Condition
Not recommended for long-term operation
*Click here to view Systems Index Table.
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80 F edb temperature of air entering indoor
coil.
Below 80 F edb, subtract (corr factor x cfm) from SHG.
Above 80 F edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
TEMP (F)
AIR ENTERING
CONDENSER
(Edb)
AIR ENTERING EVAPORATOR — CFM/BF
635/0.08 745/0.10 915/0.12
Air Entering Evaporator — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
55
TCG
26.5 29.0 30.9 33.3 28.2 29.8 31.8 34.1 29.7 30.7 33.2 34.5
SHG
26.5 23.2 19.7 16.5 28.2 24.8 20.9 17.2 29.7 27.2 22.6 17.7
TC
25.9 28.5 30.3 32.8 27.7 29.3 31.2 33.6 29.1 30.1 32.6 33.9
kW
1.81 1.85 1.89 1.95 1.83 1.86 1.93 1.99 1.86 1.89 1.93 2.02
CMP
1.50 1.54 1.58 1.64 1.52 1.55 1.62 1.68 1.55 1.58 1.62 1.71
LDB
37.7 43.0 48.8 54.1 41.6 46.3 51.8 57.0 47.0 49.9 55.1 60.8
LWB
37.6 42.6 48.4 54.0 39.6 45.4 51.1 56.7 42.4 48.4 53.9 59.8
65
TCG
25.6 27.8 29.9 32.5 27.2 28.7 30.9 33.4 28.9 29.7 32.2 33.8
SHG
25.6 22.7 19.3 16.2 27.2 24.4 20.6 17.0 28.9 26.8 22.4 17.6
TC
25.0 27.3 29.4 32.0 26.7 28.1 30.3 32.8 28.3 29.1 31.7 33.3
kW
1.99 2.03 2.09 2.15 2.02 2.05 2.13 2.19 2.06 2.09 2.13 2.22
CMP
1.68 1.72 1.78 1.84 1.71 1.74 1.82 1.88 1.75 1.78 1.82 1.91
LDB
39.1 43.9 49.4 54.6 42.9 46.9 52.2 57.3 47.9 50.3 55.3 60.8
LWB
38.3 43.5 49.0 54.5 40.3 46.1 51.6 57.1 42.9 48.9 54.2 60.0
75
TCG
24.7 26.9 29.5 31.6 26.4 28.0 30.3 32.5 28.4 29.2 31.1 33.1
SHG
24.7 22.2 19.2 15.9 26.4 24.2 20.4 16.7 28.4 26.9 22.1 17.5
TC
24.1 26.3 28.9 31.0 25.8 27.4 29.7 31.9 27.9 28.6 30.6 32.6
kW
2.22 2.25 2.30 2.37 2.25 2.27 2.32 2.40 2.28 2.30 2.35 2.43
CMP
1.91 1.94 1.99 2.06 1.94 1.96 2.01 2.09 1.97 1.99 2.04 2.12
LDB
40.6 44.6 49.5 55.1 44.0 47.1 52.4 57.7 48.4 50.1 55.6 61.0
LWB
39.1 44.3 49.4 55.1 40.9 46.6 51.9 57.5 43.1 49.2 54.7 60.3
85
TCG
23.9 25.7 28.5 31.1 25.5 26.8 29.6 31.8 27.5 28.1 30.6 32.6
SHG
23.9 21.7 18.8 15.7 25.5 23.7 20.3 16.4 27.5 26.5 22.2 17.4
TC
23.3 25.2 28.0 30.6 24.9 26.3 29.0 31.2 27.0 27.5 30.1 32.0
kW
2.43 2.49 2.55 2.60 2.48 2.53 2.57 2.63 2.53 2.54 2.59 2.66
CMP
2.12 2.18 2.24 2.29 2.17 2.22 2.26 2.31 2.22 2.23 2.28 2.35
LDB
41.9 45.5 50.2 55.4 45.3 47.8 52.6 58.0 49.5 50.6 55.6 61.0
LWB
39.8 45.2 50.0 55.4 41.6 47.3 52.3 57.9 43.6 49.7 54.9 60.5
95
TCG
23.0 24.5 27.3 30.3 24.5 25.6 28.4 31.2 26.5 26.8
29.0 32.0
SHG
23.0 21.1 18.3 15.3 24.5 23.1 19.8 16.3 26.5 25.9
21.5 17.4
TC
22.4 24.0 26.8 29.7 24.0 25.0 27.9 30.6 25.9 26.3
28.4 31.5
kW
2.67 2.72 2.83 2.88 2.72 2.76 2.85 2.90 2.79 2.81
2.87 2.93
CMP
2.35 2.41 2.52 2.57 2.41 2.45 2.54 2.59 2.48 2.50
2.56 2.62
LDB
43.4 46.4 51.1 55.9 46.6 48.6 53.3 58.2 50.6 51.3
55.9 61.0
LWB
40.6 46.1 50.9 55.9 42.2 48.1 53.0 58.2 44.2 50.3
55.4 60.8
105
TCG
22.0 23.3 26.0 29.0 23.5 24.2 27.0 30.0 25.3 25.4 28.1 31.0
SHG
22.0 20.5 17.7 14.8 23.5 22.5 19.2 15.8 25.3 25.2 21.3 17.1
TC
21.4 22.7 25.4 28.4 22.9 23.6 26.4 29.5 24.8 24.9 27.5 30.5
kW
2.92 2.97 3.08 3.19 2.98 3.01 3.12 3.20 3.06 3.06 3.17 3.22
CMP
2.61 2.66 2.77 2.87 2.67 2.70 2.81 2.89 2.75 2.75 2.86 2.91
LDB
45.0 47.4 52.0 56.7 48.1 49.5 54.1 58.8 51.9 52.1 56.6 61.3
LWB
41.4 47.0 51.8 56.7 43.0 48.9 53.8 58.8 44.8 51.0 56.1 61.2
115
TCG
20.9 21.9 24.6 27.6 22.4 22.8 25.5 28.5 24.2 24.2 26.5 29.6
SHG
20.9 19.9 17.1 14.3 22.4 21.8 18.5 15.2 24.2 24.2 20.6 16.6
TC
20.4 21.3 24.0 27.0 21.8 22.2 24.9 28.0 23.6 23.6 25.9 29.1
kW
3.19 3.24 3.35 3.49 3.26 3.28 3.39 3.54 3.34 3.34 3.44 3.55
CMP
2.88 2.93 3.04 3.18 2.95 2.97 3.08 3.23 3.03 3.03 3.13 3.24
LDB
46.8 48.4 53.0 57.7 49.6 50.4 55.0 59.6 53.3 53.3 57.3 61.9
LWB
42.3 48.1 52.8 57.6 43.7 49.8 54.7 59.6 45.5 51.6 56.8 61.7
125
TCG
19.7 20.3 23.0 26.0 21.1 21.2 23.8 26.9 22.9 22.9 24.8 27.9
SHG
19.7 19.1 16.4 13.6 21.1 21.0 17.9 14.6 22.9 22.9 20.0 16.0
TC
19.2 19.7 22.5 25.4 20.5 20.7 23.3 26.3 22.3 22.3 24.3 27.4
kW
3.48 3.50 3.64 3.79 3.55 3.55 3.68 3.84 3.64 3.64 3.73 3.89
CMP
3.17 3.19 3.33 3.48 3.24 3.24 3.37 3.53 3.33 3.33 3.42 3.58
LDB
48.7 49.7 54.1 58.7 51.4 51.5 55.9 60.5 54.7 54.7 58.0 62.6
LWB
43.2 49.3 53.9 58.6 44.6 50.8 55.6 60.4 46.2 52.3 57.5 62.4
BF
Bypass Factor
CMP
Compressor
Edb
Entering Dry Bulb
Ewb
Entering Wet Bulb
kW
Total Power
LDB
Leaving Dry Bulb
LWB
Leaving Wet Bulb
SHG
Gross Sensible Capacity (1000 Btuh)
TC
Total Net Cooling Capacity (1000 Btuh)
TCG
Gross Cooling Capacity (1000 Btuh)