SYSTEM 24* – 38HDL024 WITH 40QKB036
LEGEND Rating Condition
Not recommended for long-term operation
*Click here to view Systems Index Table.
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80 F edb temperature of air entering indoor
coil.
Below 80 F edb, subtract (corr factor x cfm) from SHG.
Above 80 F edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
TEMP (F)
AIR ENTERING
CONDENSER
(Edb)
AIR ENTERING EVAPORATOR — CFM/BF
635/0.08 745/0.10 915/0.12
Air Entering Evaporator — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
55
TCG
24.5 26.2 28.0 29.3 25.9 26.9 28.5 29.7 27.3 27.6 29.0 30.1
SHG
24.5 21.9 18.4 14.8 25.9 23.6 19.3 15.3 27.3 25.7 20.6 15.9
TC
24.0 25.6 27.4 28.8 25.4 26.4 27.9 29.2 26.7 27.1 28.4 29.6
kW
1.35 1.36 1.38 1.40 1.36 1.37 1.39 1.40 1.38 1.38 1.39 1.41
CMP
1.09 1.10 1.12 1.13 1.10 1.11 1.12 1.14 1.11 1.12 1.13 1.15
LDB
41.3 45.5 51.2 57.0 45.1 48.3 54.2 59.8 50.1 51.8 57.4 62.9
LWB
39.5 45.0 50.7 56.7 41.4 47.4 53.2 59.1 43.9 50.1 55.8 61.7
65
TCG
23.7 25.4 27.7 29.5 25.3 26.3 28.4 30.0 27.0 27.3 29.0 30.5
SHG
23.7 21.6 18.5 15.0 25.3 23.5 19.6 15.6 27.0 26.1 21.2 16.3
TC
23.1 24.8 27.1 28.9 24.7 25.7 27.9 29.4 26.4 26.8 28.5 29.9
kW
1.52 1.51 1.53 1.55 1.51 1.52 1.54 1.56 1.52 1.53 1.55 1.57
CMP
1.26 1.25 1.27 1.29 1.25 1.25 1.28 1.29 1.26 1.26 1.28 1.30
LDB
42.6 46.0 51.1 56.8 46.0 48.4 53.8 59.5 50.4 51.4 57.0 62.5
LWB
40.2 45.6 50.9 56.6 41.9 47.8 53.2 59.0 44.1 50.2 55.8 61.5
75
TCG
22.9 24.3 26.9 29.2 24.4 25.2 27.7 29.8 26.2 26.4 28.6 30.3
SHG
22.9 21.1 18.2 14.9 24.4 23.1 19.5 15.6 26.2 25.8 21.4 16.5
TC
22.4 23.7 26.3 28.6 23.8 24.7 27.2 29.2 25.6 25.9 28.0 29.8
kW
1.67 1.69 1.70 1.72 1.69 1.69 1.70 1.73 1.69 1.70 1.71 1.74
CMP
1.41 1.43 1.44 1.46 1.43 1.43 1.44 1.47 1.43 1.43 1.45 1.48
LDB
43.9 46.8 51.6 56.9 47.2 49.0 53.9 59.3 51.3 51.7 56.7 62.2
LWB
40.8 46.5 51.4 56.8 42.5 48.5 53.6 59.1 44.5 50.7 56.0 61.6
85
TCG
22.1 23.2 25.8 28.4 23.5 24.1 26.6 29.1 25.2 25.3 27.6 29.8
SHG
22.1 20.6 17.7 14.6 23.5 22.5 19.1 15.5 25.2 25.3 21.1 16.5
TC
21.5 22.6 25.2 27.8 22.9 23.5 26.1 28.6 24.7 24.7 27.0 29.2
kW
1.84 1.86 1.89 1.91 1.86 1.88 1.90 1.92 1.89 1.89 1.90 1.93
CMP
1.58 1.60 1.63 1.64 1.60 1.61 1.63 1.65 1.63 1.63 1.64 1.66
LDB
45.2 47.6 52.4 57.3 48.5 49.8 54.5 59.5 52.4 52.3 57.0 62.2
LWB
41.5 47.3 52.2 57.3 43.1 49.2 54.2 59.4 45.1 51.2 56.4 61.8
95
TCG
21.1 22.0 24.5 27.2 22.5 22.9 25.4 28.1 24.2 24.2
24.0 28.9
SHG
21.1 20.0 17.1 14.2 22.5 21.9 18.6 15.1 24.2 24.2
18.9 16.4
TC
20.6 21.4 23.9 26.7 21.9 22.3 24.8 27.5 23.6 23.6
23.4 28.3
kW
2.01 2.03 2.09 2.12 2.05 2.06 2.11 2.13 2.09 2.09
2.12 2.14
CMP
1.75 1.77 1.83 1.86 1.78 1.79 1.85 1.86 1.82 1.82
1.85 1.87
LDB
46.8 48.6 53.2 58.0 49.8 50.6 55.2 60.0 53.5 53.5
57.5 62.4
LWB
42.3 48.2 53.0 58.0 43.8 49.9 54.9 60.0 45.6 51.8
57.0 62.1
105
TCG
20.1 20.7 23.1 25.9 21.4 21.5 23.9 26.8 23.0 23.0 24.8 27.6
SHG
20.1 19.4 16.5 13.7 21.4 21.3 18.0 14.6 23.0 23.0 20.1 16.0
TC
19.6 20.1 22.5 25.4 20.8 20.9 23.4 26.2 22.4 22.4 24.2 27.0
kW
2.21 2.22 2.28 2.36 2.24 2.24 2.30 2.36 2.28 2.28 2.33 2.37
CMP
1.95 1.96 2.02 2.09 1.98 1.98 2.04 2.10 2.02 2.02 2.07 2.10
LDB
48.4 49.5 54.2 58.8 51.3 51.5 56.0 60.7 54.9 54.9 58.1 62.8
LWB
43.1 49.1 54.0 58.8 44.5 50.7 55.7 60.6 46.2 52.3 57.6 62.6
115
TCG
19.1 19.3 21.6 24.4 20.2 20.2 22.3 25.1 21.7 21.7 23.1 26.0
SHG
19.1 18.8 15.9 13.1 20.2 20.2 17.4 14.0 21.7 21.7 19.4 15.4
TC
18.5 18.7 21.0 23.8 19.7 19.7 21.7 24.6 21.2 21.2 22.6 25.4
kW
2.42 2.42 2.49 2.57 2.45 2.45 2.51 2.60 2.50 2.50 2.53 2.62
CMP
2.15 2.16 2.23 2.30 2.19 2.19 2.25 2.33 2.23 2.23 2.27 2.36
LDB
50.1 50.6 55.1 59.8 52.9 52.9 56.9 61.5 56.3 56.3 58.9 63.4
LWB
44.0 50.1 54.9 59.8 45.3 51.5 56.5 61.4 46.9 52.9 58.3 63.2
125
TCG
17.9 18.0 20.0 22.7 19.0 19.0 20.6 23.4 20.4 20.4 21.4 24.2
SHG
17.9 18.0 15.3 12.5 19.0 19.0 16.7 13.4 20.4 20.4 18.8 14.7
TC
17.3 17.4 19.4 22.1 18.5 18.5 20.0 22.8 19.8 19.8 20.8 23.6
kW
2.63 2.63 2.70 2.78 2.67 2.67 2.72 2.81 2.72 2.72 2.75 2.84
CMP
2.37 2.37 2.44 2.52 2.41 2.41 2.46 2.55 2.45 2.45 2.49 2.58
LDB
52.0 51.9 56.2 60.8 54.6 54.6 57.8 62.4 57.8 57.8 59.6 64.1
LWB
44.9 51.1 56.0 60.7 46.1 52.2 57.4 62.2 47.6 53.5 59.0 63.9
BF —
Bypass Factor
CMP —
Compressor
Edb —
Entering Dry Bulb
Ewb —
Entering Wet Bulb
kW —
Total Power
LDB —
Leaving Dry Bulb
LWB —
Leaving Wet Bulb
SHG —
Gross Sensible Capacity (1000 Btuh)
TC —
Total Net Cooling Capacity (1000 Btuh)
TCG —
Gross Cooling Capacity (1000 Btuh)