Product data
COOLING CAPACITIES (cont)
SYSTEM 21* – 38HDL048 WITH 40QAB048
LEGEND Rating Condition
Not recommended for long-term operation
*Click here to view Systems Index Table.
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80 F edb temperature of air entering indoor
coil.
Below 80 F edb, subtract (corr factor x cfm) from SHG.
Above 80 F edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
TEMP (F)
AIR ENTERING
CONDENSER
(Edb)
AIR ENTERING EVAPORATOR — CFM/BF
1100/0.05 1160/0.05 1200/0.06
Air Entering Evaporator — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67
72
55
TCG
44.9 48.7 52.1 54.5 45.9 49.3 52.4 54.8 46.4 49.6 52.7 54.9
SHG
44.9 39.8 33.7 27.4 45.9 40.8 34.3 27.6 46.4 41.5 34.7 27.8
TC
43.6 47.4 50.7 53.2 44.5 48.0 51.1 53.5 45.1 48.3 51.3 53.6
kW
3.01 3.07 3.14 3.18 3.02 3.09 3.15 3.19 3.03 3.09 3.15 3.19
CMP
2.33 2.40 2.46 2.51 2.34 2.41 2.47 2.51 2.35 2.42 2.48 2.51
LDB
38.9 43.7 49.4 55.4 40.2 44.6 50.4 56.4 41.0 45.2 51.1 57.1
LWB
38.2 43.4 49.1 55.3 38.9 44.3 50.0 56.2 39.3 44.9 50.6 56.8
65
TCG
43.5 47.4 51.6 54.7 44.4 48.0 52.1 55.1 45.1 48.4 52.4
55.3
SHG
43.5 39.2 33.7 27.5 44.4 40.3 34.4 27.9 45.1 41.0 34.8 28.1
TC
42.2 46.0 50.3 53.4 43.1 46.7 50.8 53.7 43.7 47.1 51.0 54.0
kW
3.35 3.37 3.45 3.51 3.37 3.38 3.46 3.52 3.36 3.39 3.46 3.52
CMP
2.67 2.69 2.77 2.83 2.69 2.70 2.78 2.84 2.69 2.71 2.78 2.84
LDB
40.2 44.2 49.4 55.2 41.4 45.1 50.4 56.2 42.2 45.6 51.0 56.8
LWB
38.9 44.0 49.3 55.2 39.5 44.8 50.2 56.1 39.9 45.3 50.7 56.7
75
TCG
42.2 45.6 50.3 54.2 43.1 46.3 50.9 54.6 43.7 46.7 51.3
54.9
SHG
42.2 38.3 33.1 27.3 43.1 39.5 33.9 27.8 43.7 40.2 34.5 28.0
TC
40.9 44.3 49.0 52.9 41.8 45.0 49.6 53.3 42.4 45.4 49.9 53.5
kW
3.65 3.74 3.79 3.86 3.68 3.74 3.80 3.87 3.69 3.73 3.81 3.88
CMP
2.97 3.06 3.11 3.18 3.00 3.06 3.12 3.19 3.02 3.06 3.13 3.20
LDB
41.4 45.0 49.9 55.4 42.6 45.8 50.7 56.3 43.4 46.3 51.3 56.9
LWB
39.5 44.8 49.8 55.4 40.2 45.6 50.6 56.3 40.6 46.1 51.2 56.8
85
TCG
40.8 43.8 48.6 53.0 41.7 44.4 49.1 53.5 42.3 44.7 49.5
53.8
SHG
40.8 37.5 32.4 26.9 41.7 38.6 33.2 27.4 42.3 39.3 33.8 27.7
TC
39.5 42.5 47.2 51.7 40.4 43.1 47.8 52.2 41.0 43.4 48.2 52.5
kW
3.99 4.09 4.18 4.25 4.02 4.10 4.18 4.26 4.04 4.11 4.19 4.26
CMP
3.31 3.41 3.50 3.57 3.34 3.43 3.50 3.58 3.36 3.44 3.51 3.58
LDB
42.7 45.8 50.6 55.8 43.8 46.6 51.4 56.7 44.6 47.1 51.9 57.2
LWB
40.2 45.6 50.6 55.8 40.8 46.4 51.3 56.7 41.2 46.8 51.8 57.2
95
TCG
39.3 41.7 46.5 51.4 40.2 42.3 47.1 51.9 40.7 42.7
45.5 52.1
SHG
39.3 36.5 31.5 26.2 40.2 37.6 32.3 26.7 40.7 38.3
31.5 27.0
TC
38.0 40.4 45.2 50.0 38.9 41.0 45.8 50.5 39.4 41.3
44.0 50.8
kW
4.36 4.45 4.60 4.67 4.39 4.47 4.61 4.68 4.41 4.48
4.61 4.68
CMP
3.68 3.77 3.92 3.99 3.72 3.79 3.93 4.00 3.73 3.80
3.93 4.00
LDB
44.2 46.8 51.4 56.5 45.2 47.5 52.2 57.2 46.0 48.0
52.6 57.7
LWB
41.0 46.6 51.4 56.5 41.5 47.2 52.1 57.2 41.9 47.7
52.6 57.7
105
TCG
37.7 39.6 44.1 49.3 38.4 40.1 44.7 49.8 38.9 40.5 45.1 50.1
SHG
37.7 35.5 30.5 25.4 38.4 36.6 31.3 25.9 38.9 37.3 31.9 26.3
TC
36.3 38.2 42.8 48.0 37.1 38.8 43.4 48.5 37.6 39.1 43.7 48.8
kW
4.78 4.84 5.01 5.13 4.80 4.86 5.03 5.13 4.82 4.88 5.04 5.14
CMP
4.10 4.16 4.33 4.45 4.12 4.19 4.35 4.46 4.14 4.20 4.37 4.46
LDB
45.7 47.7 52.4 57.2 46.8 48.4 53.1 57.9 47.5 48.8 53.5 58.4
LWB
41.8 47.5 52.3 57.2 42.3 48.2 53.0 57.9 42.6 48.5 53.4 58.4
115
TCG
35.9 37.3 41.7 46.8 36.7 37.8 42.3 47.3 37.2 38.1 42.6 47.7
SHG
35.9 34.4 29.5 24.4 36.7 35.5 30.3 25.0 37.2 36.2 30.9 25.3
TC
34.5 35.9 40.4 45.5 35.3 36.5 41.0 46.0 35.8 36.8 41.3 46.4
kW
5.22 5.27 5.45 5.66 5.25 5.30 5.47 5.66 5.27 5.31 5.48 5.66
CMP
4.54 4.60 4.77 4.98 4.57 4.62 4.79 4.98 4.59 4.63 4.81 4.99
LDB
47.4 48.8 53.3 58.1 48.4 49.4 54.0 58.8 49.0 49.8 54.4 59.2
LWB
42.6 48.5 53.3 58.1 43.1 49.1 53.9 58.8 43.4 49.4 54.3 59.2
125
TCG
34.0 34.8 39.2
44.2 34.7 35.2 39.7 44.7 35.2 35.5 40.0 45.1
SHG
34.0 33.3 28.4
23.4 34.7 34.3 29.2 24.0 35.2 35.0 29.8 24.4
TC
32.7 33.4 37.9
42.8 33.4 33.9 38.3 43.4 33.9 34.2 38.6 43.7
kW
5.70 5.74 5.92 6.16 5.73 5.75 5.94 6.19 5.75 5.77 5.96 6.21
CMP
5.02 5.06 5.24
5.48 5.06 5.08 5.27 5.51 5.07 5.09 5.28 5.53
LDB
49.2 49.9 54.3
59.0 50.1 50.5 54.9 59.6 50.7 50.9 55.3 60.0
LWB
43.5 49.6 54.3 59.0 44.0 50.1 54.8 59.6 44.3 50.4 55.2 60.0
BF —
Bypass Factor
CMP —
Compressor
Edb —
Entering Dry Bulb
Ewb —
Entering Wet Bulb
kW —
Total Power
LDB —
Leaving Dry Bulb
LWB —
Leaving Wet Bulb
SHG —
Gross Sensible Capacity (1000 Btuh)
TC —
Total Net Cooling Capacity (1000 Btuh)
TCG —