ARI* Capacities Multi Split Applications Page 1 of 2; Go to Page 2
Nominal Fan Qty Circuit Indoor Outdoor Std. Net Cooling Net Heating Total SEER EER
Capacity Coils Section Section CFM BTUH BTUH kW
Cassette 2 A 40QKB024 38HDS024 1,050 23,000 n/a 2.20 12.0 10.5
Under Ceiling 2 A 40QAB024 + 38HDS024 1,000 24,000 n/a 2.22 12.0 10.8
High Wall 2 A 40QNB018 38HDS024 960 23,000 n/a 2.03 12.0 11.3
Cassette 1 A 40QKB024 38HDS024 1,025 23,000 n/a 2.24 12.0 10.3
2 Tons Under Ceiling 1 A 40QAB024 +
Cassette 1 A 40QKB024 38HDS024 1,005 23,000 n/a 2.14 12.0 10.7
High Wall 1 A 40QNB018
Under Ceiling 1 A 40QAB024 + 38HDS024 980 23,000 n/a 2.15 12.0 10.7
High Wall 1 A 40QNB018
40CG-030---301RM 38SC-030---301 800 30,000 n/a 2 x 3.4 10.0 8.8
2.5 Tons Console 2
40CS-030---301RM 38SB-030---301 800 30,000 31,000 2 x 3.4 10.0 8.8
High Wall 2 A 40QNB018 38HDS048 1,920 46,000 n/a 4.06 12.0 11.3
2 B 40QNB018
High Wall 1 A 40QNB024 38HDS048 1,510 45,800 n/a 4.12 12.0 11.1
2 B 40QNB018
High Wall 1 A 40QNB024 38HDS048 1,100 45,600 n/a 4.18 12.0 10.9
1 B 40QNB024
Under Ceiling 2 A 40QAB024 + 38HDS048 2,000 48,000 n/a 4.44 12.0 10.8
2 B 40QAB024 +
Under Ceiling 1 A 40QAB024 38HDS048 1,600 46,800 n/a 4.29 12.0 10.9
2 B 40QAB024 +
Under Ceiling 1 A 40QAB024 38HDS048 1,200 45,600 n/a 4.14 12.0 11.0
1 B 40QAB024
Cassette 2 A 40QKB024 38HDS048 2,100 46,000 n/a 4.40 12.0 10.5
2 B 40QKB024
Cassette 2 A 40QKB024 38HDS048 1,965 47,000 n/a 4.40 12.0 10.7
1 B 40QKB036
4 Tons Cassette 1 A 40QKB036 38HDS048 1,830 48,000 n/a 4.40 12.0 10.9
1 B 40QKB036
High Wall 2 A 40QNB018 38HDS048 1,940 46,000 n/a 4.18 12.0 11.0
High Wall 1 B 40QNB018
Under Ceiling 1 B 40QAB024 +
High Wall 2 A 40QNB018 38HDS048 1,965 46,000 n/a 4.17 12.0 11.0
High Wall 1 B 40QNB018
Cassette 1 B 40QKB024
High Wall 2 A 40QNB018 38HDS048 1,960 47,000 n/a 4.25 12.0 11.0
Under Ceiling 2 B 40QAB024 +
High Wall 2 A 40QNB018 38HDS048 2,010 46,000 n/a 4.23 12.0 10.9
Cassette 2 B 40QKB024
High Wall 2 A 40QNB018 38HDS048 1,985 46,000 n/a 4.27 12.0 10.8
Under Ceiling 1 B 40QAB024 +
Cassette 1 B 40QKB024
Under Ceiling 2 A 40QAB024 + 38HDS048 1,980 47,000 n/a 4.37 12.0 10.8
Under Ceiling 1 B 40QAB024 +
High Wall 1 B 40QNB018
Legend
* Air Conditioning & Refrigeration Institute
+ Unit must be reconfigured for 1 1/2 ton (18,000 Btuh) operation. Refer to
installations included with the fan coil unit for more details.
Notes:
1) ARI rating conditions is 80 deg F db, 67 deg F wb air entering evaporator and
95 deg F db air entering condenser.
2) Total kW is for total system, including compressor and outdoor and indoor fan motors.
3) Ratings are based on 25 ft of interconnecting refrigerent lines.
4) All system ratings are based on fan coil units operating at high fan speed. Consult Physical Data
Rev "A"
tables for airflows at all available fan speeds.
09/17/01