Installation guide

START-UP
Preliminary
Checks
1.
Make
sure
all
wiring
connections
are
correct
and
they
are
tight.
.
Field
electrical
power
source
must
agree
with
unit
name
plate rating.
bo
3.
Check
that
all
barriers,
covers, and
panels
are
in
place.
En-
sure
that
the
filters
and
return-air
grilles
on
the
indoor
unit
have
been
installed
and
that
the
discharge
louvers
are
posi-
tioned
correctly.
4.
All
service
valves
must
be
closed.
5.
On
units
with
crankcase
heaters,
ensure
belly-band
heaters
are
tight
around
the
compressor.
6.
Check
that
the
condensate
drain
plug
is
in
place
and
prop-
erly
sealed.
Evacuate
and
Dehydrate
the
System
UNIT
DAMAGE
HAZARD
Failure
to
follow
this
caution
may
result
in
equipment
damage
or
improper
operation.
Never
use
the
system
compressor
as
a
vacuum
pump.
Refrigerant
tubes
and
indoor
coil
should
be
evacuated
using
the
recommended
deep
vacuum
method
of
500
microns.
the
alternate
triple
evacuation
method
may
be
used
if
the
procedure
outlined
below
is
followed.
Always
break
a
vacuum
with
dry
nitrogen.
Using
Vacuum
Pump
1.
Completely
tighten
flare
nuts
A,
B,
C,
D,
connect
manifold
gage
charge
hose
to
a
charge
port
of
the
low
side
service
valve.
(See
Fig.
40.)
.
Connect
charge
hose
to
vacuum
pump.
Ww
be
.
Fully
open
the
low
side
of
manifold
gage.
(See
Fig.
41)
.
Start
vacuum
pump
a
.
Evacuate
using
either
deep
vacuum
or
triple
evacuation
method.
6.
After
evacuation
is
complete,
fully
close
the
low
side
of
manifold
gage
and
stop
operation
of
vacuum
pump.
~l
.
The
factory
charge
contained
in
the
outdoor
unit
is
good
for
up
to
25
ft.
(8
m)
of
line
length.
For
refrigerant
lines
longer
than
25
ft
(8
m),
add
0.3
oz.
per
foot
of
extra
piping
up
to
the
maximum
allowable
length.
8.
Disconnect
charge
hose
from
charge
connection
of
the
low
side
service
valve.
oO
.
Fully
open
service
vaives
B
and
A.
10.
Securely
tighten
caps
of
service valves.
Refrigerant
Indoor
Unit
Low
Side
Outdoor
Unit
Service
Valve
07360
Fig.
40
-
Service
Valve
Manifoid
Gage
500
microns~*
-e-1
Rap
High
side
vaive
Charge
hose
ll
°
Low
side
vaive
-
Charge
hose
-
Vacuum
pump
Low
side
valve
A07361
Fig.
41
-
Manifold
Deep Vacuum
Method
The
deep
vacuum
method
requires
a
vacuum
pump
capable
of
pulling
a
vacuum
of
500
microns
and
a
vacuum
gage
capable
of
accurately
measuring
this
vacuum
depth.
The
deep
vacuum
method
is
the
most
positive
way
of
assuring
a
system
is
free
of
air
and
liquid
water.
(See
Fig.
42)
50004
4500
4
g
S500
Z
SYSTEM
6
3000-
oc
6
2500
= 2000-44
=
a
VACUUM
TIGHT
‘ooo
TOO
WET
TIGHT
500
———__—_———
pry
SYSTEM
MINUTES
A95424
Fig.
42
-
Deep
Vacuum
Graph
Triple
Evacuation
Method
The
triple
evacuation
method
should
only
be
used
when
vacuum
pump
is
only
capable
of
pumping
down
to
28
in.
of
mercury
vacuum
and
system
does
not
contain
any
liquid
water.
Refer
to
Fig.
43
and
proceed
as
follows:
1.
Pump
system
down
to
28
in.
of
mercury
and
allow
pump
to
continue
operating
for
an
additional
15
minutes.