Installation guide
Run Power
Wiring
for
Indoor
Unit
Be
sure
field
wiring
complies
with
local
building
codes
and
NEC,
and
unit
voltage
is
within
limits
shown
in
Table
11
and
Table
12.
Contact
local
power
company
for
correction
of
improper
line
voltage.
ELECTRICAL
SHOCK
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury
or
death.
Before
installing,
modifying,
or
servicing
system,
main
electrical
disconnect
switch
must
be
in
the
OFF
position.
There
may
be
more
than
1
disconnect
switch.
Lock
out
and
tag
switch
with
a
suitable
warning
label.
UNIT
DAMAGE
HAZARD
Failure
to
follow
this
caution
may
result
in
equipment
damage
or
improper
operation.
Unit
failure
as
a
result
of
operation
on
improper
line
voltage
or
excessive
phase
imbalance
constitutes
abuse
and
may
cause
damage
to
electrical
components.
Such
operation
could
void
any
applicable
Carrier
warranty.
NOTE:
Use
copper
wire
only
between
disconnect
switch(es)
and
unit.
NOTE:
Install
branch
circuit
disconnect
of
adequate
size
to
handle
unit
starting
current
per
NEC.
Locate
disconnect
within
sight
of,
and
readily
accessible
from,
unit,
per
section
440-14
of
NEC.
Some
codes
allow
indoor
unit
to
share
disconnect
with
outdoor
unit
if
disconnect
can
be
locked;
check
local
code
before
installing
in
this
manner.
The
40KMC/KMO
units
require
their
own
power
supply.
1.
Locate
the
indoor
power
supply.
2.
Locate
and
install
disconnect
switch
per
NEC
and
local
codes.
3.
Run
power
supply
wiring
to
disconnect
switch.
4.
Run
power
wiring
from
disconnect
switch
to
control
box
area,
Use
copper
wire only
between
the
disconnect
switch
and
unit.
Use
minimum
60°C
wires
for
field
power
con-
nection.
5.
Remove
the
external
control
box
cover.
6.
Place
wiring
through
the
7/8
in.
or
1-1/8
in.
knockouts
on
the
bottom
and
on
the
right
hand
side
of
the
external
control
box
(high
voltage
side).
See
Fig.
24
and
Fig.
25.
15