Installation guide

ELECTRICAL
DATA
Table
10
—38HDF/38QRF
Electrical
Data
COMPRESSOR
OUTDOOR
FAN
MOTOR
FUSE/
38HDF/38QRF
V-PH-Hz
VOLTAGE
RANGE*
MIN
CKT CKT
UNIT
SIZE
ven
AMPS
BKR
Min
Max
RLA LRA
FLA
NEC
Hp
kW
Out
AMPS
018
208/230
—1-60
187
253
9.0
48.0 0.80
0.125
0.09
12.4
20
024
208/230
—1-60
187
253
12.8
58.3
0.80
0.125
0.09
16.8
25
38QRF030
208/230
—1-60
187
253
14.4
73.0
1.50
0.25 0.19
18.4
30
38HDFO30
208/230
—1-60
187
253
14.4
73.0 0.80
0.125
0.09
18.4
30
208/230
—1-60
187
253
16.7
79.0
1.50
0.25 0.19
22.3
35
035
208/230-3-60
187
253
10.4
73.0
1.50
0.25 0.19
14.5
20
460—-3-—60
414 506
5.8
38.0 0.80 0.25 0.19
8.7
15
208/230
—1-60
187
253
17.9
112.0
1.45
0.25 0.19 23.8
40
036
208/230-3-60
187
253
13.2
88.0
1.45
0.25 0.19
18.0
30
460—-3-—60
414 506
6.0
44.0 0.80 0.25 0.19
8.3
15
Table
11
40K
MC
Fan
coil
Electrical
Data
Voltage
Range
FAN
Power
Louver
40KMC
Condensate
FUSE/
ee
V-PH-Hz
Motor
Unit
Size
:
Pump
FLA MIN
CKT CKT
Min.
Max
FLA
Watts
FLA
AMPS
BKR
AMPS
018
208/230—1—60
187
253
0.55
120
0.08
0.01
0.8
15
024
208/230
—1-60
187
253
0.50
110
0.06
0.01
0.7
15
030
208/230
—1-60
187
253
0.95
210
0.06
0.01
1.3
15
036
208/230
—1-60
187
253
0.95
210
0.06
0.01
1.3
15
Table
12
—-
40KMQ
Fan
Coil
Electrical
Data
Voltage
FAN
Electric
Power
Range
L
Heaters
ouver
40KMQ
Condensate
FUSE/
Unit
Size
V-PH-Hz
Motor
|
Pump
FLA
Motor
MIN
CKT
Min.
|
Max
|
FLA
|
Power
FLA
kw
FLA
CKT
BKR
(Watts)
AMPS
|
anaps
018
208/230
—1-60
187
253
0.50
110
0.06
0.01
3
12.5
16.3 20
024
208/230
—1-60
187
253
0.50
110
0.06
0.01
3
12.5
16.3 20
030
208/230
—1-60
187
253
0.95
210
0.06
0.01
3
12.5 16.9
20
036
208/230
—1-60
187
253
0.95
210
0.06
0.01
3
12.5 16.9
20
*Permissible
limits
of
the
voltage
range
at
which
unit
will
operate
satisfactorily.
LEGEND
NOTES:
FLA
-
MCA
-
NEC
-
RLA
-
Full
Load
Amps
Minimum
Circuit
Amps
per
NEC
Section
430-24
National
Electrical
Code
Rated
Load
Amps
(Compressor)
1.
In
compliance
with
NEC
requirements
for
multi-motor
and
combination
load
equipment
(refer
to
NEC
Articles
430
and
440),
the
over—current
protective
device
for
the
unit
shall
be
fuse
or
equipped
with
a
breaker.
2.
Motor
RLA
values
are
established
in
accordance
with
UL
(Underwriters
Laboratories)
Standard
465.
11
Cc
@