Installation guide
38HDF /
38QRF
UNIT
SIZE
018
024
030
V-PH-Hz
Table 10 - 38HDF / 38QRF Electrical Data
VOLTAGERANGE* COMPRESSOR OUTDOOR FANMOTOR
Min Max
187 253
187 253
187 253
187 253
187 253
414 506
187 253
187 253
414 506
RLA LRA FLA
NEC Hp
0.125
0.125
0.25
0.25
0.25
0.25
0.25
0.25
0.25
kW Out
MIN CKT
AMPS
208/230-1-60 9.0 48.0 0.80 0.09 12.1
208/230-1-60 12.8 58.3 0.80 0.09 16.8
208/230-1-60 14.1 73.0 1.50 0.19 18.4
208/230-1-60 16.7 79.0 1.50 0.19 22.3
035 208/230-3 -60 10.4 79.0 1.50 0.19 14.5
460 -3 -60 5.8 79.0 0.80 0.19 8.7
208/230-1-60 17.9 112.0 1.45 0.19 23.8
036 208/230 -3 -60 13.2 88.0 1.45 0.19 18.0
460 -3 -60 6.0 44.0 0.80 0.19 8.3
Table 11 - 40QNC, QNQ Fan Coil Electrical Data
VOLTAGE RANGE* FAN POWER
UNIT SIZE V-PH-Hz Motor Power MIN CKT FUSE/CKT
Min Max FLA
(Watts) AMPS BKR AMPS
40QNC01824 208/230-1-60 187 253 0.38 64 0.48 15
40QNC030 208/230-1-60 187 253 0.38 74 0.48 15
40QNC036 208/230-1-60 187 253 0.44 74 0.55 15
40QNQ018 208/230-1-60 187 253 0.38 64 0.48 15
40QNQ024 208/230-1-60 187 253 0.38 64 0.48 15
40QNQ030 208/230-1-60 187 253 0.38 74 0.48 15
40QNQ036 208/230-1-60 187 253 0.44 74 0.55 15
FUSE/
HACR
BKR
AMPS
2O
25
3O
35
2O
15
4O
3O
15
LEGEND:
FLA - Full Load Amps
LRA - Locked Rotor Amps
NEC- National Electrical Code
RLA - Rated Load Amps (compressor)
* Permissible limits of the voltage range at which the unit will operate
satisfactorily
NOTES:
1. Control circuit is 24-V on all units and requires external power
source. Copper wire must be used from service disconnect to unit.
2. All motors/compressors contain internal overload protection.
3. In compliance with NEC (USA Standard) requirements for multimo-
tot and combination load equipment (refer to NEC Articles 430 and
440), the over current protective device for the unit shall be fuse.
4. Motor RLA values are established in accordance with UL (Under-
writers' Laboratories) Standard 465 (USA Standard).
5. 38QRF018-030 units are only available in single-phase voltage.
6. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent-
age of voltage imbalance:
= 100 X max voltaqe deviation from averaqe voltaqe
average
EXAMPLE: Supply voltage is 460-3-60
A 8 C AB = 452v
M_OTO_j_R BC = 464v
AC = 455v
Average Voltage = 452 + 464 + 455
3
= 1371
3
= 457
Determine maximum deviation from average voltage:
(AB) 457-452 = 5v
(BC) 464-457 = 7v
(AC) 457-455 = 2v
Maximum deviation is 7v.
Determine percentage of voltage imbalance
7
% of voltage imbalance = 100 x 5-7-
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum
allowable of 2%.
IMPORTANT: Contact your local electric utility company immediately if the
supply voltage phase imbalance is more than 2%.
cQ0s
11