PHYSICAL DATA -- 38GVC
Outdoor Unit 38GVC 009 012 012 018 024 036
System Voltage 1 1 5 --- 1 --- 60 208/230---1 ---60
Control Voltage Low Voltage Pulse DC
Rated Cooling Capacity (Btuh) 9,000 11,800 12,000 18,000 22,000 33,600
Cooling. Capacity Range
Min --- Max (Btuh)
3,500 --- 11,000 3,300 --- 12,500 3,300 --- 12,500 4,500 --- 21,000 6,400 --- 24,000 7,400 --- 36,000
Operating Weight lb. (kg) 75 (34) 63.8 (30) 112.2 (51) 161 (73)
Refrigerant Type R---410A
Metering Device @ Outdoor Unit Cap. Tube EXV Cap. Tube
Charge lb. (kg) 2.3 (1.05) 2.8 (1.27) 2.2 ( 1.0) 2.8 (1.27) 3.4 (1.55) 5.3 ( 2.4)
Compressor
Type Twin Rotary Inverter Driven
Model KNB092FHBMC QXA---B096ZC190 SNB130FGYMC C---6RZ146H1A TNB306FPGMC
Outdoor Fan
CFM 1060 942 1880 1880 2590
RPM 850 880 690 690 900
Diameter (in) 15.7 14.6 20.5 20.5 21.7
W atts 30 21 60 170
Outdoor Coil
Face Area (sq.) 4.4 3.7 5.9 6.1 7.7
No. Rows 2
Fins per inch 16 18
Refrigerant Lines
Connection Type Flare
Liquid (Mix Phase) in OD 1/4”
Vapor Line in OD 3/8” 1/2” 5/8”
Maximum Length ft. 50 65 50 82 98
Max Lift (Fan Coil Above) ft. 33
Max Drop (Fan Coil Below) f t. 33
External Finish White