User guide

AIR IN
NOTE: Fan position on motor shaft should be as close to motor as possible without touching.
Figure 2—Dimensional Drawing
TABLE I—DIMENSIONS (In Inches)
Size
----------
X
----------
----------
C
----------
D
----------
1
----------
F G
H
K
025
27-3/8 24-9/16 6-3/8 1-7/8 3/8
11-9/16
11-3/4
11/32 3/4
040, 047 & 054
27-3/8 30-9/16 6-3/8 1-7/8 3/8
11-9/16
11 -3/4
11/32
3/4
TABLE II—SPECIFICATIONS
Size 025
040
047
054
Refrigerant Type R-22
R-22 R-22
R-22
Factory Refrigerant Charge Lbs-oz 4-8
6-8 7-2
6-11
Refrigerant Tube^ Liquid 3/8 3/8
3/8
3/8
Connection Size (Compatible) Vapor 3/4 3/4
3/4
3/4
Approx Shipping Weight Lbs 155 200
230
232
♦Refer to appropriate refrigerant tube sizing table to determine correct liquid- and suction-tube diameters.
TABLE III—ELECTRIC CONNECTIONS
Size 025 040
047 054
Nameplate
Volts—Phase (60-Hertz) 230—1—50
400—3—50
400—3—50
400—3—50 400—3—50
Operating Voltage Range
207-253 360-440 360-440 360-440 360-440
Unit Ampacity for Elec
trical Conductor Sizing. 18.5 6.7 9.2 14.1
15.4
Total Unit Amps 15.1 5.6 7.6
11.5 12.5
Min Branch Circuit
Wire Size
AWG No.
12 14 14 14
12
Copper
Conductor^
Max Length
In Ftt
94 321 236 156 228
Largest Wire Size
Terminal Will
Type Conn
Screw Screw
Screw
Screw Lug
, Accommodate
AWG No. 6
6 6 6 6
Max Branch. Circuit
Fuse Sizet
Amps 25
10
15
20 20
NOTE: Use copper wire only between disconnect switch and unit.
♦If other than 75° C copper conductor is used, determine size from unit-ampacity and the National Electric Code. Voltage drop of wire must be less
than 2% of unit rated voltage.
fLength shown is as measured one way along the wire path between the unit and service panel-for minimum 2% voltage drop.
$Sing)e-phase units may use fuses or HACFI-type circuit breakers of same size as noted.