Installation manual

38GLP---G / 38GLP---G9
Cooling only split system outdoor units
GB - 1
ENGLISH
For operation and maintenance instructions of this unit as well as installation
instructions of the indoor unit, refer to the relevant manuals
Contents
Page
Dimensions and weight ................................................................................................................. 2
Connections .................................................................................................................................. 2
Minimum clearances ..................................................................................................................... 3
System charge............................................................................................................................... 3
General information....................................................................................................................... 4
Warnings: avoid............................................................................................................................. 5
Refrigerant connections ................................................................................................................ 6/8
Operating limits ............................................................................................................................. 8
Electrical connections ................................................................................................................... 9/10
Electrical data ................................................................................................................................10
Pump down and check the refrigerant charge .............................................................................. 11
Unit maintenance .......................................................................................................................... 12
Troubleshooting and guide for the owner ..................................................................................... 12
Accessories ................................................................................................................................... 12
Installation instructions supplement ............................................................................................. 13/14
ATTENTION INSTALLERS AND SERVICE TECHNICIANS!
AIR CONDITIONER WITH R-410A–QUICK REFERENCE GUIDE
R-410A refrigerant operates at 50%-70% higher pressures than R-22. Be sure that servicing
equipment and replacement components are designed to operate with R-410A.
R-410A refrigerant cylinders are pink.
R-410A refrigerant cylinders have a dip tube which allows liquid to flow out of cylinder in an upright
position.
R-410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the
manifold hose in order to vaporize the liquid refrigerant before it enters in the unit.
The R-410A, as for other HFC, is only compatible with oils chosen by the compressor manufacturer.
For this reason, for the type of oil to be used, always refer to the plate on the compressor and the unit.
A vacuum pump is not enough to remove moisture from oil.
POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
Never open system to atmosphere while it is under vacuum.
In case the system should be opened for maintenance, stop the vacuum function with dry nitrogen and
replace the drier filters, if any.
Do not vent R-410A into the atmosphere.
Use only Carrier matching indoor units (Table I).
Table I
Cooling Power
Hi-Wall Cassette Console Satellite
only models supply
38GLP018G 42PHQ018N 42PHQ018P 40KMC018 42VMC018 40SMC018N 40DMC018
38GLP024G
230V ~ 50Hz
42PHQ024N 42PHQ024P 40KMC024 42VMC024 40SMC024N 40DMC024
38GLP018G9 42PHQ018N 42PHQ018P 40KMC018 42VMC018 40SMC018N 40DMC018
38GLP024G9 42PHQ024N 42PHQ024P 40KMC024 42VMC024 40SMC024N 40DMC024
38GLP028G9 400V 3N ~ 50Hz 40KMC028 42VMC028 40SMC028N 40DMC028
38GLP036G9 40KMC036 42VMC036 40SMC036N
40DMC036
38GLP048G9 40KMC048 42VMC048 40SMC048N
38GLP060G9 40KMC060 40SMC060N 40DMC060