Pump Down and check the refrigerant charge
Check the refrigerant charge
This check becomes necessary after any refrigerant leak due to
incorrect connection, or after replacement of the compressor.
The best method to correctly charge refrigerant is to completely
empty the refrigerant circuit using refrigerant recovery equipment.
Then charge the exact quantity of refrigerant according to the
data shown on the unit nameplate.
This can be done with charging equipment of the Dial a charge
type.
R-410A refrigerant cylinders contain a dip tube which allows
liquid refrigerant to flow from the cylinder in an upright
position.
Charge R-410A units with cylinder in upright position and a
commercial-type metering device in manifold hose in order to
vaporize the liquid refrigerant before it enters in the unit.
Charge refrigerant into suction-line.
Pump-down
Pump-down is an operation intended to collect all the system
refrigerant in the outdoor unit.
This operation must be carried out before disconnecting the
refrigerant tubing in order to avoid refrigerant loss to the
atmosphere, if it becomes necessary to disconnect the
refrigerant connections for unit repair, removal or disposal;
in this case, after removal, unit must be delivered to an
appropriate disposal centre or the original dealer.
Shut off the liquid valve with the Allen wrench.
Turn the system on in cooling with fan operating at high velocity.
(Compressor will immediately start, provided 3 minutes have
elapsed since the last stop).
After 2 minutes of operation, shut the suction valve with the same
wrench.
Turn the system off and switch mains supply off.
Disconnect tubing.
After disconnection, protect valves and tubing ends from dust.
Compressor damage may occur if run at a negative suction
pressure.
Refrigerant circuit
Cooling only unit
Legend:
Outdoor coil
Compressor
Metering device
Strainer
Vapor valve
Liquid valve
Service pressure port
Pressure transducer on head
pressure controller board
Drier filter
High pressure switch
Low pressure switch
Rotary compressor storage battery
*
Additional storage battery
*
Crankcase heater
Discharge muffler
*
Indoor unit coil
Gas
Liquid + Gas
Liquid
(
*
according to the models)