38GLP---G/38GLP---G9 INSTALLATION MANUAL
For operation and maintenance instructions of this unit as well as installation instructions of the indoor unit, refer to the relevant manuals Contents Dimensions and weight ................................................................................................................. Connections .................................................................................................................................. Minimum clearances .............................................................
8GLP---G / 38GLP---G9 Dimensions and weight A A A B B E D E B E E F C C Mod. 38GLP 18 - 24 E F D E F C Mod. 38GLP 28 - 36 Mod. 38GLP 48 - 60 18 24 38GLP 28 36 mm 800 800 800 800 800 800 mm 590 590 803 803 1264 1264 mm 300 300 300 300 300 300 mm 508 508 508 508 508 508 mm 146 146 146 146 146 146 mm 330 330 330 330 330 330 kg 45 51 65 65 92 94 Mod.
38GLP---G / 38GLP---G9 Minimum clearances ENGLISH D A C B E E Mod.
38GLP---G / 38GLP---G9 General information IMPORTANT: During the unit installation make first refrigerant connections and then electrical connections. If unit is uninstalled first disconnect electrical cables, then refrigerant connections. WARNING: Disconnect the mains power supply switch before servicing the system or handling any internal parts of the unit. • The manufacturer declines any liability for damage resulting from modifications or errors in the electrical or refrigerant connections.
38GLP---G / 38GLP---G9 Warnings: avoid.... ENGLISH Disconnecting the refrigerant connections after installation: this will cause refrigerant leaks. Connecting the condensate drain pipe to the outdoor unit. Excessive height difference between indoor and outdoor unit (see Table II "Connections"). Excessive distance between indoor and outdoor units. (see Table II "Connections"). Predominant head winds. Unnecessary turns and bends in the connecting pipes.
38GLP---G / 38GLP---G9 Refrigerant connections No moisture. No dust. Charge liquid-no gas. No leak. No mineral oil. Copper tubes during storage. Neat. 1/2” UNF (R-410A) Use tools designed for R-410A higher pressure. Keep inside clean. Dry nitrogen brazing. Min. – 100 kPa (– 755 mmHg) Vacuum. GB - 6 2-stage vacuum pump. Replace oil regularly.
38GLP---G / 38GLP---G9 Refrigerant connections ENGLISH Flaring the ends of the tubing 2 1 The unit can be installed: 햲 on the floor; 햳 on the wall using the bracket kit. Remove protective caps from copper tube ends. Position tube end downward, cut the tube to the requested length and remove the burrs with a reamer. Do not leave system open to atmosphere any longer than minimum required for installation. Oil in the compressor is extremely susceptible to moisture absorption.
38GLP---G / 38GLP---G9 Refrigerant connections ! 햽 햹 햿 햺 햾 햳 햴 햵 햶 햷 햸 Three-way valve Needle valve Valve cap Valve needle Two-way valve Allen (hex. head) wrench 햹 햺 햻 햽 햾 햿 Gas line (large diameter) Liquid line (small diameter) Flare nut Indoor unit Outdoor unit Vacuum pump Air purging 헂 Use only a vacuum pump to purge air from the piping. NEVER use the system compressor as a vacuum pump. NEVER use the unit refrigerant gas to purge the connecting pipes.
38GLP---G / 38GLP---G9 Electrical connections ENGLISH Single-phase version Cooling only unit Cooling only system L N R C Y L N R C Y O W2 S 230V ~ 50Hz L N R C Y 햳 햲 10 햲 120 쐋 쐏 R C Y O W2 S 10 100 햳 Terminal box legend, all models L L1 L2 L3 N R C Y Earth Live power supply. Live power supply. Live power supply. Live power supply. Neutral power supply. Live connection indoor/outdoor unit. Neutral connection indoor/outdoor unit. Compressor interlocking contact.
38GLP---G / 38GLP---G9 Electrical connections • For 230 V ~ 1 pH 50 Hz single-phase unit Before proceeding with the unit connection to the mains supply locate live L and neutral N, then make connections as shown in the wiring diagram. • For 400V 3N ~50 Hz three-phase unit Before proceeding with the unit connection to the mains supply locate live L1,L2,L3 and neutral N, then make connections as shown in the wiring diagram.
38GLP---G / 38GLP---G9 Pump Down and check the refrigerant charge ENGLISH Pump-down Check the refrigerant charge Pump-down is an operation intended to collect all the system refrigerant in the outdoor unit.
d’installazione supplementari 38GLP---G /Istruzioni 38GLP---G9 Unit maintenance, troubleshooting and guide for the owner Indoor unit coil The following maintenance operations must be carried out by qualified personnel. Cleaning the coil When necessary, proceed as follows for more careful cleaning of the coil: • Condenser coil (outdoor or indoor, in case of heat pump operation) obstructed; remove obstructions. • Outdoor fan off; check cause and repair. • Run capacitor faulty; check and replace.
38GLP---G 38GLP---G9 Installation instructions supplement ENGLISH Cooling only Outdoor unit Indoor unit 햴 햶 햳 햵 햲 햴 햲 햳 햴 햵 햶 38GLP...G units are designed to work in North European countries climates. They differ from the standard ones for the following factory fitted accessories: head pressure controller (HPC), loss of refrigerant pressure switch (LRPS), and high pressure switch (HIP).
38GLP---G 38GLP---G9 Installation instructions supplement L N1 N2 HP Head pressure controller: wiring diagram 10FM 1FC N L 1FC - Fan Capacitor 1OFM - Fan motor Troubleshooting See paragraph “Troubleshooting”. Note: At start-up or in case of re-start after a stop of several hours at – 10°C, with low voltage supply (198V), high pressure switch HIP may trip off the unit. In this case, reset the system by switching OFF and ON the power supply.
L010127H19 - 1105 Via R. Sanzio, 9 - 20058 Villasanta (MI) Italy - Tel. 039/3636.1 The manufacturer reserves the right to change any product specifications without notice. November, 2005.