Installation guide

Table 5--Superheat Charging
OUTDOOR EVAPORATOR ENTERING ABR TEMPERATURE (°FWB)
TEMP
[°F} 50 52 54 56 58 60 62 64 66 68 70 72 74 76
55 9 12 14 17 20 23 26 2g 32 35 37 40 42 45
60 7 10 12 15 18 21 24 27 30 33 35 38 40 43
65 -- 6 10 13 16 19 21 24 27 30 33 36 38 41
70 -- -- 7 10 13 16 19 21 24 27 30 33 36 39
75 -- -- -- 6 9 12 15 18 21 24 28 31 34 37
80 .... 5 8 12 15 18 21 25 28 31 35
88 ...... 8 11 15 19 22 26 30 33
90 ...... 5 9 13 16 20 24 27 31
95 ....... 6 10 14 18 22 25 29
100 ........ 8 12 15 20 23 27
105 ........ 5 9 13 17 22 26
110 ......... 6 11 15 20 25
118 .......... 8 14 18 23
Table 6--Required Suction-Line Temperature (°F WB)
SUPERHEAT SUCTION PRESSURE AT SERVICE PORT (PSIG}
TEMP
{OF} 107.8 112.2 116.8 121.2 126.0 130.8 138.8 140.8 145.8
0 35 37 39 41 43 45 47 49 5I
2 37 39 41 43 45 47 4g 51 53
4 39 41 43 45 47 49 51 53 55
¢ 41 43 45 47 4g 51 53 55 57
8 43 45 47 49 51 53 55 57 59
10 45 47 49 51 53 55 57 59 61
t2 47 49 51 53 55 57 5g 61 63
14 49 51 53 55 57 59 61 63 65
t6 51 53 55 57 5g 61 63 65 67
18 53 55 57 59 61 63 65 67 69
20 55 57 59 61 63 65 67 69 71
22 57 59 61 63 65 67 69 71 73
24 59 61 63 65 67 69 71 73 75
26 61 63 65 67 6g 71 73 75 77
28 63 65 67 69 71 73 75 77 79
30 65 67 69 71 73 75 77 79 81
32 67 69 71 73 75 77 7g 81 83
34 69 71 73 75 77 79 81 83 85
36 71 73 75 77 79 8I 83 85 87
38 73 75 77 79 81 83 85 87 89
40 75 77 79 81 83 85 87 89 91