Specifications
Table 5E -- Physical Data -- Outdoor Heat Pump Units
UNIT SIZE
NOMINAL CAPACITY (Tons)
OPERATING WEIGHT (Ib)
REFRIGERANT TYPE
Control (Cooling)
Control (Heating)
Charge (Ib)*
CRANKCASE HEATER (Watts)
OUTDOOR FAN
Rpm
Diameter (in,),..No. of Blades
Pitch (Degrees)
Motor Hp
Nominal Air Cfm
OUTDOOR COIL
Face Area (sq ft),..No, of Coils
Fins/in.
CONTROLS
High-Pressure (psig)
Cutout
Cut-in
Liquid Line Low-Pressure (psig)
Cutout
Cut-in
Fusible Plug
Defrost Method
Accumulator
Control Voltagel-
REFRIGERANT LINES
Connection Type
Liquid Line OD (in,)
Vapor Line OD (in.)
Maximum Length (ft)
Maximum Lift (Fan Coil Above) (ft)
Maximum Lift (Fan Coil Below) (ft)
018 024
11/2 2
154 167
R-22
AccuRater® Piston at Fan Coil Unit
AccuRater Piston at Outdoor Unit
See Table 6
19 I 19
Propeller, Direct Drive
850 850
18_.3 18_.3
25 27
l& 1/s
1720 1720
Copper Tube, Aluminum Fin
6.1 ...1.5 I 6.1 ...2
15 I 15
320 _+20
426 _+ 7
7_+3
22_+5
210 F
Time and Temperature Defrost
Yes
24 v
Sweat--Suction; Flare--Liquid
3/8 s/s
s/8 5/s
200 200
65 65
150 150
*These units are shipped with a holding charge only,
1-A 24-v transformer is provided in the fan coil unit; size 018 and 024 units have their own transformers.
Table 5F -- Physical Data -- Heat Pump High Wall Fan Coil Units
018 024
11/2 2
18,000 24,000
38.5 42.9
5.6 6.3
White
R-22
AccuRater® Piston in Fan Coil
AccuRater Piston in Outdoor Unit
See Table 6
Direct Drive Centrifugal
1250/530 1470/570
1150/490 1400/466
1050/430 1300/447
42.3 49
2...3.94 x 17.8 2...3.94 x 17.8
Copper Tube, Aluminum Fin
2.56 2.56
2 3
15.9 18.1
2 3
Cleanable
2,.,111/2 x 173/4
UNIT SIZE
NOMINAL CAPACITY (Tons)
NOMINAL SIZE (Btuh)
OPERATING WEIGHT (Ib)
MOISTURE REMOVAL RATE (Pints/Hr)
FINISH
REFRIGERANT
Control (Cooling)
Control (Heating)
Charge Required (Ib)
INDOOR FAN
Rpm/Cfm High
Rpm/Cfm Medium
Rpm/Cfm Low
Motor Watts
Blowers Quantity..,Size (in.)
INDOOR COIL
Face Area (sq ft)
No. of Rows
Fins/in.
Circuits
FILTERS
Quantity,..Size (in,)
AIBSWEEP
Horizontal
Vertical
CONTROLS
Remote Controller Options
Diagnostics
Defrost Method
Timer Mode
Warm Start Feature
Test Mode
Freeze Protection
Dehumidification
Auto. Changeover
Fan Mode
Auto Restart
Control Voltage
REFRIGERANT LINES
Connection Type
Liquid Line OD (in,)
Vapor Line OD (in.)
CONDENSATE DRAIN CONNECTION (in,)
Manual
Automatic
Integrated Microprocessor
Wireless
Yes
Demand Defrost
Yes
Yes
Yes
Yes
Yes
Yes
High/Medium/Low/Auto.
Yes
24 v (provided)
Flare
3/8
s/8
5/80D, 7/16ID
*Outdoor unit is shipped with a holding charge. The amount of the charge is determined based on 25 ft of line.