Installation guide

CHECK OPERATION
Before starting the system to check operation of low ambient
temperature controller, ensure that the power wiring and location
of controller assembly are correct. To check operation of low
ambient temperature controller:
1. Turn power on to system.
2. Set thermostat below room temperature.
3. Ensure that there is the standard 3-minute time delay for
the microprocessor controlled high wall fan coil systems.
4. Check time delay of installed accessories:
Under-ceiling (40QAC/QAQ) fan coils using the
duct-free 24-v thermostat delay settings: 2 or 4 minute
delay.
The outdoor-fan motor will not operate until the condensing
pressure reaches the control set point of 225 psig for
38BNC/BNQ models or 362 psig for 38QRF-018-036 and
38QRR-018-060 models (-+ 10 psig). When the set point is
reached, the outdoor fan will cycle to maintain the set point
condensing pressure.
If the low ambient temperature controller does not operate
correctly:
Ensure that power is being supplied to the system.
Check condensing pressure: if condensing pressure is
below 200 psig for 38BNC/BNQ models or 321 psig for
38QRF-018-036 and 38QRR-018-060 models, the
outdoor-fan motor should be off and there should be no
voltage across the 2 blue fan power leads coming out of
the controller. If condensing pressure is about 225 psig or
greater for 38BNC/BNQ models or 362 psig for
38QRF-018-036 and 38QRR-018-060 models, the
outdoor-fan motor should be on and will cycle off at
around 200 psig for 38BNC/BNQ or 321 psig for
38QRF-018-036 and 38QRR-018-060 models.