Installation guide
INDOOR UNIT BCC/BCQ018, 024
Operation push button for
automatic operation (23 C/73 F),
turning the a/c OFF, canceling
the malfunction indication,
and resetting the filter LED.
PLASTIC CONTROL
COVER
0 AUTO/OFF /
@ FILTER RESE/
\
\
\
\
\
OFFON_---_'OM_ /_"'_ SERVICE LED
IR RECEIVER FILTER
FLARING AND CONNECTING REFRIGERANT LINES
1. Remove the protective cap from the flare fitting.
2. Remove the protective cap from the robing and cut to the
required length. Be sure that the cut is perpendicular and
clean, without burrs.
3. Slip the flare nut on the tubing and flare the tube end using
standard flaring tools.
4. Tighten the nut until resistance is met. Mark the nut and the
fitting. Using a suitable wrench tighten an additional 1/4
turn. Use the t\_llowing specified torque, according to
connection size:
Mixed-Phase line: Suction line:
1/4 in.-(12.3 ft-lb.) 1/2 in.-(36 ft-lb.)
Both refrigerant lines
need to be insulated separatly
NOTE: The selwice valves on the outdoor unit must remain closed
until all 4 connections have been made.
EVACUATE TUBINGAND CHARGE THE SYSTEM When
all the fittings are connected, air must be expelled, then refriger-
ant chaNe must be checked and adjusted. Follow the steps below.
1. Open the selwice port cap on the suction line valve (large
valve of unit No. 1).
2. Connect the vacuum pmnp to the selwice port of unit No. 1
via the pressure gage and evacuate to 500 microns to
eliminate contamination and moisture.
Fig. 12A m Indoor unit LED's and Wiring
3. Disconnect the vacuum pump. Unit should maintain 500
microns for 5 minutes.
4. Remove the service port caps from the mixed-phase valve
and suction line valve
5. Open the mixed-phase valve (small valve) with an Allen
wrench.
6. Open the suction line valve (large valve) with an Allen
wrench.
7. To evacuate and charge unit No. 2 repeat steps 1 thru 6.
8. The outdoor unit is supplied with sufficient R-22
refrigerant for up to 25 ft. lineset length. Add 0.9 oz. of
refrigerant for each additional 3 ft. of tubing length.
9. Make sure that the valves are properly opened. Be careful not
to open them more than required as this may damage the
thread.
10. Replace the service port cap. Using refrigerant oil, lubricate
the cap beam and hand tighten until resistance is met. Use a
suitable wrench to tighten the cap by an additional 1/2 turn.
Power Supply See Tables 4 and 5 for electrical data and
Fig. 13-14 t\_r system wiring diagrams.
Leak Test Leak test all fittings with appropriate test equipment.