Table 4 m Electrical Data, Indoor Units m 30VDC
UNIT VOLTAGE MCA* MOCP* FULLLOAD FANMOTOR COMPRESSOR COMPRESSORLOCKED
AMPS AMPS AMPS ROTORAMPS
40BNC 009 30VDC N/A N/A 1.8 1.1 N/A N/A
40BNQ 012 30VDC N/A N/A 1.8 1.5 N/A N/A
LEGEND
MCA --Minimum CircuitAmps
MOCP -- Maximum Overcurrent Protection
*If indoor unit is powered from outdoor terminal block, the MOCP for
the outdoor unit is for both sections
NOTE: Specifications and performance data are subject to change without notice.
3095897
Table 5 -- Electrical Data, Outdoor Units -- 115, 1-60
UNIT VOLTAGE MCA* MOCP* FULLLOAD FANMOTOR COMPRESSOR COMPRESSORLOCKED
AMPS AMPS AMPS ROTORAMPS
38BCC 018 115VAC 19.8 25 18 1.00 7.2 42
38BCQ 024 115VAC 24.6 30 22.2 1.00 9.3 58
LEGEND
MCA --Minimum CircuitAmps
MOCP -- Maximum Overcurrent Protection
*If indoor unit is powered from outdoor terminal block, the MOCP
for the outdoor unit is for both sections
NOTE: Specifications and performance data are subject to change without notice.
3095897