Paulson-Cheek Mechanical 6145 Northbelt Parkway Suite F Norcross, GA 30071 770. 729. 0076 770. 729. 1076 Fax Saint Michael The Archangel Catholic Church Woodstock, GA HVAC Record Submittal November 24, 2014 General Contractor: The Winter Construction Company, Inc. Mechanical Engineer: Leppard Johnson & Associates, PC Mechanical Contractor: Paulson-Cheek Mechanical, Inc.
10 Wall Louvers 11 Grilles, Registers & Diffusers with Plenums and CableOperated Dampers 12 Take-Off Fittings 13 Flexible Ductwork 14 Controls
HVAC Submittal Cover Sheet SECTION: 1 PRODUCT: Split System Units Paulson-Cheek Mechanical, Inc. 6145 Norhtbelt Parkway, Suite F Norcross, GA 30071 PROJECT: Saint Michael The Archangel Catholic Church LOCATION: Woodstock, GA PHONE: 770-729-0076 FAX: 770-729-1076 Paulson-Cheek Mechanical, Inc. ARCHITECT'S/ENGINEER'S STAMP Paulson-Cheek Mechanical, Inc.
Carrier Complete Systems 6675 Jones Mill Court Norcross, Georgia 30092 (P) 770-239-2122 (F) 770-239-2100 S UM M AR Y Attention: Fax Number: Account: Danny Brooks Customer: Address: Paulson-Cheek Mechanical 100012 Date: Quote Number: Engineer: Job Name: Job Location: 05/30/2014 DM140288 Leppard, Johnson & Associate (Ben A.
♦ ♦ ♦ ♦ ♦ ♦ ♦ AHU-2 1 39MJ1617C8R755BBB7 CU 3-5 3 38AUDB12A0A6-0A0A0 3 6 6 6 CALVHLGD011A00 EF680033 EF680037 KM680008 2 38AUDB25A0A6-0A0A0 2 4 4 4 6 6 6 CALVHLGD009A00 KM680004 EF680035 EF680037 EF680033 EF680037 KM680008 1 24ABB324A003 1 1 1 1 1 1 KAACH1401AAA KAALP0401PUR KSALA0301410 KAAWS0101AAA FX4DNF025T05 KFCEH0801N08 1 24ABB348A006 1 1 1 1 1 1 KAACH1901AAA KAALP0401PUR KSALA0301410 KAAWS0101AAA FX4DNF049T00 KFCEH1601315 2 24ABB318A003 2 KAACH1401AAA CU-1,2 AHU CU 10 FCU/C
AHU CU 78 AHU CU9 AHU CU 12 RTU-1 2 KAALP0401PUR Low Pressure Switch 2 2 2 2 KSALA0301410 KAAWS0101AAA FX4DNF019L00 KFCEH0801N08 1 24ABB336A006 1 1 1 1 1 1 KAACH1501AAA KAALP0401PUR KSALA0301410 KAAWS0101AAA FX4DNF037L00 KFCEH1601315 1 24ABB318A003 1 1 1 1 1 1 12 KAACH1401AAA KSALA0301410 KAALP0401PUR KAAWS0101AAA FX4DNF019L00 KFCEH0501N05 33CS2PP2S-03 1 50ES-A36---6 1 1 1 1 1 CPMANDPR007A00 CPFILTRK007A00 CPLOUVER018A00 CPRFCURB011A00 CPHEATER062A00 Low-Ambient Pressure Switch Winter S
Job Name St Michael Archangel Church Mark for AHU-1 Date May 30, 2014 Unit Parameters Aero Indoor Air Handler Unit Size: Size 17 Insulation: R-13 Double Wall Sealed Panel Exterior Finish: Galvanized Exterior Panels Interior Finish: Galvanized Interior Panels Level I Thermal Break 6 inch tall Base Rail Mixing Box Shipping Split After Damper: Right Side Premium Opposed Damper: Top Premium Opposed Angle Filter Shipping Split After Shipping Skid 2In. Angle Filter Qty (12) 12in. x 24in.
Job Name St Michael Archangel Church Mark for AHU-1 Date May 30, 2014 No Coating R-410A Draw-Thru Supply Fan Rear Inlet Fan Sled Forward Curve B FCA18_18A 907 fanRPM Class I Top Horiz. Front Discharge Right Side Fan Motor Location Spring Fan Isolation Motor 5 HP Premium Efficiency ODP 208-230/460 3Ph 60Hz 1800 RPM Manufacturer - Generic Frame Size - 184T Motor Shaft Diameter (in.) - 1.125 Voltage Selected - 460/3/60 Full Load Amps - 6.5 MCA - 8.1 MOCP - 10 Efficiency - 89.5% Belt Drive 1.
DX Coil Performance Summary Project: Untitled Tag: AHU-1 DX Coil Cross-Plot 4 / 14 / HF 38AUD025(D) (Circuit B, Upper Connections) Conde ns ing Unit DX Coil S uction Line Los s S a tura te d S uction Te mpe ra ture (F) 55 50 Ba la nce P oint 45 40 35 30 100 120 140 160 180 Tota l Cooling Ca pa city (mbh) 200 220 DX Coil Cross-Plot 4 / 14 / HF 38AUD025(D) (Circuit A, Lower Connections) Conde ns ing Unit DX Coil S uction Line Los s S a tura te d S uction Te mpe ra ture (F) 55 50 Ba la nce P o
Supply Fan Performance Summary Project: Untitled Tag: AHU-1 Fan Model Unit Size Fan Type Fan Wheel Diameter Fan Class Fan Application Orientation Actual Airflow, CFM Site Altitude, ft Upstream Ext. Static, in wg Downstream Ext. Static, in wg Cooling Coil Static, in wg Heating Coil Static, in wg Other Losses, in wg Total Accessory Static, in wg Total Static Pressure, in wg Calculated Fan RPM / Motor RPM Class I Max. RPM Static Efficiency (%) Fan BHP v6.
Air Filter Submittal Project: Untitled Unit Tag: AHU-1 Carrier Part Number ....................................................... Kit Description ................................................................ Unit Airflow, CFM ........................................................... Filter Velocity, FPM ........................................................ Filter Sizes and Quantities .............................................
Job Name St Michael Archangel Church Mark for AHU-2 Date May 30, 2014 Unit Parameters Aero Indoor Air Handler Unit Size: Size 17 Insulation: R-13 Double Wall Sealed Panel Exterior Finish: Galvanized Exterior Panels Interior Finish: Galvanized Interior Panels Level I Thermal Break 6 inch tall Base Rail Mixing Box Shipping Split After Damper: Left Side Premium Opposed Damper: Top Premium Opposed Angle Filter Shipping Split After Shipping Skid 2In. Angle Filter Qty (12) 12in. x 24in.
Job Name St Michael Archangel Church Mark for AHU-2 Date May 30, 2014 No Coating R-410A Draw-Thru Supply Fan Rear Inlet Fan Sled Forward Curve B FCA18_18A 907 fanRPM Class I Top Horiz. Front Discharge Left Side Fan Motor Location Spring Fan Isolation Motor 5 HP Premium Efficiency ODP 208-230/460 3Ph 60Hz 1800 RPM Manufacturer - Generic Frame Size - 184T Motor Shaft Diameter (in.) - 1.125 Voltage Selected - 460/3/60 Full Load Amps - 6.5 MCA - 8.1 MOCP - 10 Efficiency - 89.5% Belt Drive 1.
DX Coil Performance Summary Project: Untitled Tag: AHU-2 DX Coil Cross-Plot 4 / 14 / HF 38AUD025(D) (Circuit B, Upper Connections) Conde ns ing Unit DX Coil S uction Line Los s S a tura te d S uction Te mpe ra ture (F) 55 50 Ba la nce P oint 45 40 35 30 100 120 140 160 180 Tota l Cooling Ca pa city (mbh) 200 220 DX Coil Cross-Plot 4 / 14 / HF 38AUD025(D) (Circuit A, Lower Connections) Conde ns ing Unit DX Coil S uction Line Los s S a tura te d S uction Te mpe ra ture (F) 55 50 Ba la nce P o
Supply Fan Performance Summary Project: Untitled Tag: AHU-2 Fan Model Unit Size Fan Type Fan Wheel Diameter Fan Class Fan Application Orientation Actual Airflow, CFM Site Altitude, ft Upstream Ext. Static, in wg Downstream Ext. Static, in wg Cooling Coil Static, in wg Heating Coil Static, in wg Other Losses, in wg Total Accessory Static, in wg Total Static Pressure, in wg Calculated Fan RPM / Motor RPM Class I Max. RPM Static Efficiency (%) Fan BHP v6.
Air Filter Submittal Project: Untitled Unit Tag: AHU-2 Carrier Part Number ....................................................... Kit Description ................................................................ Unit Airflow, CFM ........................................................... Filter Velocity, FPM ........................................................ Filter Sizes and Quantities .............................................
Unit Report For CU-1,2 Project: ~Untitled65 Prepared By: 05/30/2014 03:47PM Outdoor Unit Parameters Unit Quantity: Unit Model: Unit Size: Voltage: Condenser Coil: 1 38AUD 20 Tons 460-3-60 V-Ph-Hz Al/Cu System Parameter System Quantity: Refrigerant Type: Compressor Quantity: Compressor Type: Std. Capacity Steps: Std. Min. Outdoor Temp(Cooling): No. of Outdoor fans: 2 PURON 2 Scroll 50, 100 -20.
Performance Summary For CU-1,2 Project: ~Untitled65 Prepared By: 05/30/2014 03:47PM System: System Quantity: Altitude: EER @ ARI Conditions: IPLV: Suction Line Loss: Condensing unit is rated in accordance with ARI 365. 38AUD025 2 0.0 ft 13.0 NA 1.
Performance Summary For CU-1,2 Project: ~Untitled65 Prepared By: 05/30/2014 03:47PM Acoustic Note: 1. 38AUZ and 38AUD sound power data is tested in accordance with ARI270-95 Sound Rating of Unitary Equipment. 2. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook 1987 HVAC Systems & Applications, Chapter 52. 3. The acoustic center of the unit is located at the geometric center of the unit. 4.
Acoustic Summary For CU-1,2 Project: ~Untitled65 Prepared By: Outdoor Unit Parameters: Tag Name: Unit Model: Unit Size: System Type: Refrigerant Type: Compressor Quantity: Compressor Type: 05/30/2014 03:47PM CU-1,2 38AUD 20 Tons Dx Cooling Only PURON 2 Scroll Advanced Accoustics Parameters 1.0 ft 1. Unit height above ground: 20.0 ft 2. Horizontal distance from unit to receiver: 5.7 ft 3. Receiver height above ground: 0.0 ft 4. Height of obstruction: 5.
Certified Drawing for CU-1,2 Project: ~Untitled65 Prepared By: Commercial Split Systems Builder 1.
Guide Specification for CU-1,2 Project: ~Untitled65 Prepared By: 05/30/2014 03:47PM GUIDE SPECIFICATIONS Commercial Air-Cooled Condensing Units HVAC Guide Specifications Size Range: 6 to 20 Tons, Nominal Carrier Model Numbers: 38AUZ, Single Circuit (07 - 25 Models) 38AUD, Dual Circuit (12 - 25 Models) Part 1 — General 1.01 SYSTEM DESCRIPTION Outdoor-mounted, air-cooled condensing unit suitable for on-the-ground or rooftop installation.
Guide Specification for CU-1,2 Project: ~Untitled65 Prepared By: 05/30/2014 03:47PM a. Standard evaporator and condenser coils shall have aluminum lanced plate fins mechanically bonded to seamless internally grooved copper tubes with all joints brazed. b. Evaporator coils shall be leak tested to 150 psig, pressure tested to 450 psig, and qualified to UL 1995 burst test at 1775 psig. c.
Guide Specification for CU-1,2 Project: ~Untitled65 Prepared By: 05/30/2014 03:47PM G. Controls and Safeties: 1. Minimum control functions shall include: a. Control wire terminal blocks. b. Compressor lockout on auto-reset safety until reset from thermostat. c. Each unit shall utilize the Comfort Alertt Diagnostic Board that provides: (1.) System Pressure Trip fault code indication (2.) Short Cycling fault code indication (3.) Locked Rotor fault code indication (4.) Open Circuit fault code indication (5.
Guide Specification for CU-1,2 Project: ~Untitled65 Prepared By: 05/30/2014 03:47PM Copyright 2011 Carrier Corp. Edition Date: 03/11 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Catalog No: GS-38AU-04PD Replaces: GS-38AU-03PD Commercial Split Systems Builder 1.
Job Name St Michael Archangel Church Mark for AHU-3,4 Date May 30, 2014 Unit Parameters Aero Indoor Air Handler Unit Size: Size 08 Insulation: R-13 Double Wall Sealed Panel Exterior Finish: Galvanized Exterior Panels Interior Finish: Galvanized Interior Panels Level I Thermal Break 6 inch tall Base Rail Mixing Box Shipping Split After Damper: Top Premium Opposed Damper: Right Side Premium Parallel Angle Filter Shipping Split After 2In. Angle Filter Construction Filters Qty (4) 16in. x 25in.
Job Name St Michael Archangel Church Mark for AHU-3,4 Date May 30, 2014 R-410A Draw-Thru Supply Fan Rear Inlet Fan Sled Forward Curve B FCA12_12A 1346 fanRPM Class I Top Horiz. Front Discharge Right Side Fan Motor Location Spring Fan Isolation Motor 3 HP Premium Efficiency ODP 208-230/460 3Ph 60Hz 1800 RPM Manufacturer - Generic Frame Size - 182T Motor Shaft Diameter (in.) - 1.125 Voltage Selected - 460/3/60 Full Load Amps - 3.9 MCA - 4.9 MOCP - 6 Efficiency - 89.5% Belt Drive 1.
DX Coil Performance Summary Project: Untitled Tag: AHU-3,4 DX Coil Cross-Plot 4 / 11 / HF 38AUD012(D) (Circuit B, Upstream Connections) Conde ns ing Unit DX Coil S uction Line Los s S a tura te d S uction Te mpe ra ture (F) 55 50 Ba la nce P oint 45 40 35 30 30 35 40 45 50 55 60 65 70 Tota l Cooling Ca pa city (mbh) 75 80 85 90 DX Coil Cross-Plot 4 / 11 / HF 38AUD012(D) (Circuit A, Downstream Connections) Conde ns ing Unit DX Coil S uction Line Los s S a tura te d S uction Te mpe ra t
Supply Fan Performance Summary Project: Untitled Tag: AHU-3,4 Fan Model Unit Size Fan Type Fan Wheel Diameter Fan Class Fan Application Orientation Actual Airflow, CFM Site Altitude, ft Upstream Ext. Static, in wg Downstream Ext. Static, in wg Cooling Coil Static, in wg Heating Coil Static, in wg Other Losses, in wg Total Accessory Static, in wg Total Static Pressure, in wg Calculated Fan RPM / Motor RPM Class I Max. RPM Static Efficiency (%) Fan BHP v6.
Air Filter Submittal Project: Untitled Unit Tag: AHU-3,4 Carrier Part Number ....................................................... Kit Description ................................................................ Unit Airflow, CFM ........................................................... Filter Velocity, FPM ........................................................ Filter Sizes and Quantities .............................................
Job Name St Michael Archangel Church Mark for AHU-5 Date May 30, 2014 Unit Parameters Aero Indoor Air Handler Unit Size: Size 08 Insulation: R-13 Double Wall Sealed Panel Exterior Finish: Galvanized Exterior Panels Interior Finish: Galvanized Interior Panels Level I Thermal Break 6 inch tall Base Rail Mixing Box Shipping Split After Damper: Top Premium Opposed Damper: Left Side Premium Parallel Angle Filter Shipping Split After 2In. Angle Filter Construction Filters Qty (4) 16in. x 25in.
Job Name St Michael Archangel Church Mark for AHU-5 Date May 30, 2014 R-410A Draw-Thru Supply Fan Rear Inlet Fan Sled Forward Curve B FCA12_12A 1337 fanRPM Class I Top Horiz. Front Discharge Left Side Fan Motor Location Spring Fan Isolation Motor 3 HP Premium Efficiency ODP 208-230/460 3Ph 60Hz 1800 RPM Manufacturer - Generic Frame Size - 182T Motor Shaft Diameter (in.) - 1.125 Voltage Selected - 460/3/60 Full Load Amps - 3.9 MCA - 4.9 MOCP - 6 Efficiency - 89.5% Belt Drive 1.
DX Coil Performance Summary Project: Untitled Tag: AHU-5 DX Coil Cross-Plot 4 / 14 / HF 38AUD012(D) (Circuit B, Upstream Connections) Conde ns ing Unit DX Coil S uction Line Los s S a tura te d S uction Te mpe ra ture (F) 55 50 Ba la nce P oint 45 40 35 30 30 40 50 60 70 Tota l Cooling Ca pa city (mbh) 80 90 100 DX Coil Cross-Plot 4 / 14 / HF 38AUD012(D) (Circuit A, Downstream Connections) Conde ns ing Unit DX Coil S uction Line Los s S a tura te d S uction Te mpe ra ture (F) 55 50 Ba
Supply Fan Performance Summary Project: Untitled Tag: AHU-5 Fan Model Unit Size Fan Type Fan Wheel Diameter Fan Class Fan Application Orientation Actual Airflow, CFM Site Altitude, ft Upstream Ext. Static, in wg Downstream Ext. Static, in wg Cooling Coil Static, in wg Heating Coil Static, in wg Other Losses, in wg Total Accessory Static, in wg Total Static Pressure, in wg Calculated Fan RPM / Motor RPM Class I Max. RPM Static Efficiency (%) Fan BHP v6.
Air Filter Submittal Project: Untitled Unit Tag: AHU-5 Carrier Part Number ....................................................... Kit Description ................................................................ Unit Airflow, CFM ........................................................... Filter Velocity, FPM ........................................................ Filter Sizes and Quantities .............................................
Unit Report For CU 3-5 Project: ~Untitled65 Prepared By: 05/30/2014 03:47PM Outdoor Unit Parameters Unit Quantity: Unit Model: Unit Size: Voltage: Condenser Coil: 1 38AUD 10 Tons 460-3-60 V-Ph-Hz Al/Cu System Parameter System Quantity: Refrigerant Type: Compressor Quantity: Compressor Type: Std. Capacity Steps: Std. Min. Outdoor Temp(Cooling): No. of Outdoor fans: 3 PURON 2 Scroll 50, 100 -20.
Performance Summary For CU 3-5 Project: ~Untitled65 Prepared By: 05/30/2014 03:47PM System: System Quantity: Altitude: EER @ ARI Conditions: IPLV: Suction Line Loss: System meets ASHRAE 90.1 min EER requirement. 38AUD012 3 0.0 ft 13.0 NA 1.
Performance Summary For CU 3-5 Project: ~Untitled65 Prepared By: 05/30/2014 03:47PM Acoustic Note: 1. 38AUZ and 38AUD sound power data is tested in accordance with ARI270-95 Sound Rating of Unitary Equipment. 2. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook 1987 HVAC Systems & Applications, Chapter 52. 3. The acoustic center of the unit is located at the geometric center of the unit. 4.
Acoustic Summary For CU 3-5 Project: ~Untitled65 Prepared By: Outdoor Unit Parameters: Tag Name: Unit Model: Unit Size: System Type: Refrigerant Type: Compressor Quantity: Compressor Type: 05/30/2014 03:47PM CU 3-5 38AUD 10 Tons Dx Cooling Only PURON 2 Scroll Advanced Accoustics Parameters 1.0 ft 1. Unit height above ground: 20.0 ft 2. Horizontal distance from unit to receiver: 5.7 ft 3. Receiver height above ground: 0.0 ft 4. Height of obstruction: 5.
Certified Drawing for CU 3-5 Project: ~Untitled65 Prepared By: 05/30/2014 03:47PM Commercial Split Systems Builder 1.
Guide Specification for CU 3-5 Project: ~Untitled65 Prepared By: 05/30/2014 03:47PM GUIDE SPECIFICATIONS Commercial Air-Cooled Condensing Units HVAC Guide Specifications Size Range: 6 to 20 Tons, Nominal Carrier Model Numbers: 38AUZ, Single Circuit (07 - 25 Models) 38AUD, Dual Circuit (12 - 25 Models) Part 1 — General 1.01 SYSTEM DESCRIPTION Outdoor-mounted, air-cooled condensing unit suitable for on-the-ground or rooftop installation.
Guide Specification for CU 3-5 Project: ~Untitled65 Prepared By: 05/30/2014 03:47PM a. Standard evaporator and condenser coils shall have aluminum lanced plate fins mechanically bonded to seamless internally grooved copper tubes with all joints brazed. b. Evaporator coils shall be leak tested to 150 psig, pressure tested to 450 psig, and qualified to UL 1995 burst test at 1775 psig. c.
Guide Specification for CU 3-5 Project: ~Untitled65 Prepared By: 05/30/2014 03:47PM G. Controls and Safeties: 1. Minimum control functions shall include: a. Control wire terminal blocks. b. Compressor lockout on auto-reset safety until reset from thermostat. c. Each unit shall utilize the Comfort Alertt Diagnostic Board that provides: (1.) System Pressure Trip fault code indication (2.) Short Cycling fault code indication (3.) Locked Rotor fault code indication (4.) Open Circuit fault code indication (5.
Guide Specification for CU 3-5 Project: ~Untitled65 Prepared By: 05/30/2014 03:47PM Copyright 2011 Carrier Corp. Edition Date: 03/11 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Catalog No: GS-38AU-04PD Replaces: GS-38AU-03PD Commercial Split Systems Builder 1.
Unit Report For FCU/CU-6 Project: ~Untitled68 Prepared By: 08/19/2014 Outdoor Unit Parameters 24ABB Unit Model: 4 Tons High Efficiency Unit Size: 460-3-60 V-Ph-Hz Voltage: Indoor Unit Parameters FX4D Unit Model: 48,000 Btuh Unit Size: Cabinet Insulation:Single-piece cabinet with 1-in.
Performance Summary For FCU/CU-6 Project: ~Untitled68 Prepared By: 08/19/2014 System Performance System: System Quantity: Altitude: Linear Pipe Length: SEER @ ARI Conditions: EER @ ARI Conditions: 24ABB/FX4D 1 0.0 ft 0.0 ft 14.0 12.0 Actual Airflow: Standard Airflow: Total Net Clg Capacity: Net Sensible Clg Capacity: Total System Power: 1600.0 1600.0 46.79 34.89 3.
Acoustic Summary For FCU/CU-6 Project: ~Untitled68 Prepared By: 08/19/2014 Outdoor Unit Parameters: Unit Model: Unit Size: Variations: Octave Band Center Frequency, Hz Sound Power,dB A-Weighted Sound Power, dBA Indoor Unit Parameters: Unit Model: Unit Size: Cabinet Insulation: Octave Band Center Frequency, Hz Sound Power,dB A-Weighted Sound Power, dBA Residential Carrier Products Bldr 1.19p 24ABB 4 Tons High Efficiency Dense Grille 63 0.0 125 58.5 250 67.5 500 73.5 1k 75.0 2k 70.5 4k 67.
O 0,1 1,2 2 2 24ABB342 24ABB348 18,24,30 36 48,60 - X X 1,2 24ABB336 X X X O O X O O O O O O X X X O X O O X X X X O X FIELDCONTROL SUPPLYCONN. 7/8"HOLE 32 5/16" 35 3/4" 25 1/2" 28 15/16" 31 3/16" 31 3/16" 31 3/16" 3 1/2" 35" X 35" 26" X 26" VAPORLINECONN. D C X = YES O = NO 3 7/8" 32 5/16" 25 3/4" 31 3/16" 7/8" 7/8" 7/8" 7/8" 7/8" 3/4" 3/4" SQ.
Certified Drawing for FCU/CU-6 Project: ~Untitled68 Prepared By: 08/19/2014 DIMENSIONS NOTES: 1. CONDENSATE PAN DRAIN CAPS NOT SHOWN FOR CLARITY. (cont.) SLOPECOIL 2. ALL DIMENSIONS ARE IN "INCHES" UNLESS NOTED. AIRFLOW 2 3/16" TYP. (2 PLACES)* 7/16" TYP. (2 PLACES)* AIRFLOW 3 1/4" F G 1" TYP. (2 PLACES)* PRIMARY DRAIN 1 1/4" SECONDARY DRAIN SECONDARY DRAIN PRIMARY DRAIN 2 7/8" 7/16" TYP. (4 PLACES)* 1 1/4" DOWNFLOW (FIELDCONVERTED) 2 3/16" TYP.
Certified Drawing for FCU/CU-6 Project: ~Untitled68 Prepared By: 08/19/2014 DIMENSIONS UNIT A FX4DNF019 B C D 49 5/8" 17 5/8" 15 3/4" 15 5/8" FX4DNF025 23 5/8" - 17" X - SHIPPING WT (LBS) NON TIN-COATED 122 SHIPPING WT (LBS) TIN-COATED 122 F 15 3/8" COIL CONFIGURATION 23 1/8" E G H J SLOPE "A" 49 5/8" 17 5/8" 15 3/4" 15 5/8" 15 3/8" 23 1/8" 23 5/8" - 17" X - 122 122 FX4DNF031 53 7/16" 21 1/8" 19 1/4" 19 1/8" 19 3/16" 26 15/16" 27 1/2" - 19" X - 146 146
Guide Specification for FCU/CU-6 Project: ~Untitled68 Prepared By: 08/19/2014 GUIDE SPECIFICATIONS GENERAL 24ABB System Description Outdoor-mounted, air-cooled, split-system air conditioner unit suitable for ground or rooftop installation. Unit consists of a hermetic compressor, an air-cooled coil, propeller-type condenser fan, and a control box. Unit will discharge supply air upward as shown on contract drawings.
Guide Specification for FCU/CU-6 Project: ~Untitled68 Prepared By: 08/19/2014 Guide Specifications – Fan Coils – Fixed Speed Guide Specifications for ________________________________. (See the most recent edition of publication ___________________for data for the specific model to be specified). Furnish and Install _________________ direct expansion fan coil(s) equipped with cooling control kit and _____(with) _____(without) electric heater in the location and manner shown on the plan.
Unit Report For AHU CU 7 8 Project: ~Untitled65 Prepared By: Outdoor Unit Parameters Unit Model: Unit Size: Voltage: 05/30/2014 24ABB 1.5 Tons 208/230-1-60 V-Ph-Hz Outdoor Unit Dimensions and Weight Unit Length: Unit Width: Unit Height: Unit Shipping Weight: 25 36 34 130 in in in lb Indoor Unit Parameters FX4D Unit Model: 18,000 Btuh Unit Size: Cabinet Insulation:Single-piece cabinet with 1-in.
Performance Summary For AHU CU 7 8 Project: ~Untitled65 Prepared By: 05/30/2014 System Performance System: System Quantity: Altitude: Linear Pipe Length: SEER @ ARI Conditions: EER @ ARI Conditions: 24ABB/FX4D 2 0.0 ft 0.0 ft 14.5 12.0 Actual Airflow: Standard Airflow: Total Net Clg Capacity: Net Sensible Clg Capacity: Total System Power: 600.0 600.0 17.16 13.85 1.
Acoustic Summary For AHU CU 7 8 Project: ~Untitled65 Prepared By: 05/30/2014 Outdoor Unit Parameters: Unit Model: Unit Size: Variations: Octave Band Center Frequency, Hz Sound Power,dB A-Weighted Sound Power, dBA Indoor Unit Parameters: Unit Model: Unit Size: Cabinet Insulation: Octave Band Center Frequency, Hz Sound Power,dB A-Weighted Sound Power, dBA Residential Carrier Products Bldr 1.19p 24ABB 1.5 Tons Dense Grille 63 0.0 125 53.5 250 59.5 500 63.5 1k 67.0 2k 63.5 4k 59.0 8k 52.5 dBA 72.
O 0,1 1,2 2 2 24ABB342 24ABB348 18,24,30 36 48,60 - X X 1,2 24ABB336 X X X O O X O O O O O O X X X O X O O X X X X O X FIELDCONTROL SUPPLYCONN. 7/8"HOLE 32 5/16" 35 3/4" 25 1/2" 28 15/16" 31 3/16" 31 3/16" 31 3/16" 3 1/2" 35" X 35" 26" X 26" VAPORLINECONN. D C X = YES O = NO 3 7/8" 32 5/16" 25 3/4" 31 3/16" 7/8" 7/8" 7/8" 7/8" 7/8" 3/4" 3/4" SQ.
Certified Drawing for AHU CU 7 8 Project: ~Untitled65 Prepared By: 05/30/2014 DIMENSIONS NOTES: 1. CONDENSATE PAN DRAIN CAPS NOT SHOWN FOR CLARITY. (cont.) SLOPECOIL 2. ALL DIMENSIONS ARE IN "INCHES" UNLESS NOTED. AIRFLOW 2 3/16" TYP. (2 PLACES)* 7/16" TYP. (2 PLACES)* AIRFLOW 3 1/4" F G 1" TYP. (2 PLACES)* PRIMARY DRAIN 1 1/4" SECONDARY DRAIN SECONDARY DRAIN PRIMARY DRAIN 2 7/8" 7/16" TYP. (4 PLACES)* 1 1/4" DOWNFLOW (FIELDCONVERTED) 2 3/16" TYP.
Certified Drawing for AHU CU 7 8 Project: ~Untitled65 Prepared By: 05/30/2014 DIMENSIONS UNIT A FX4DNF019 B C D 49 5/8" 17 5/8" 15 3/4" 15 5/8" FX4DNF025 23 5/8" - 17" X - SHIPPING WT (LBS) NON TIN-COATED 122 SHIPPING WT (LBS) TIN-COATED 122 F 15 3/8" COIL CONFIGURATION 23 1/8" E G H J SLOPE "A" 49 5/8" 17 5/8" 15 3/4" 15 5/8" 15 3/8" 23 1/8" 23 5/8" - 17" X - 122 122 FX4DNF031 53 7/16" 21 1/8" 19 1/4" 19 1/8" 19 3/16" 26 15/16" 27 1/2" - 19" X - 146 1
Unit Report For AHU CU-9 Project: ~Untitled68 Prepared By: Outdoor Unit Parameters Unit Model: Unit Size: Voltage: 08/19/2014 24ABB 3 Tons 208/230-1-60 V-Ph-Hz Outdoor Unit Dimensions and Weight Unit Length: Unit Width: Unit Height: Unit Shipping Weight: 27 40 36 170 in in in lb Indoor Unit Parameters FX4D Unit Model: 36,000 Btuh Unit Size: Cabinet Insulation:Single-piece cabinet with 1-in.
Performance Summary For AHU CU-9 Project: ~Untitled68 Prepared By: 08/19/2014 System Performance System: System Quantity: Altitude: Linear Pipe Length: SEER @ ARI Conditions: EER @ ARI Conditions: 24ABB/FX4D 1 0.0 ft 0.0 ft 14.5 12.0 Actual Airflow: Standard Airflow: Total Net Clg Capacity: Net Sensible Clg Capacity: Total System Power: 1200.0 1200.0 33.95 27.10 2.
Acoustic Summary For AHU CU-9 Project: ~Untitled68 Prepared By: 08/19/2014 Outdoor Unit Parameters: Unit Model: Unit Size: Variations: Octave Band Center Frequency, Hz Sound Power,dB A-Weighted Sound Power, dBA Indoor Unit Parameters: Unit Model: Unit Size: Cabinet Insulation: Octave Band Center Frequency, Hz Sound Power,dB A-Weighted Sound Power, dBA Residential Carrier Products Bldr 1.19p 24ABB 3 Tons Dense Grille 63 0.0 125 59.5 250 63.0 500 68.5 1k 70.0 2k 65.5 4k 61.5 8k 53.5 dBA 75.
O 0,1 1,2 2 2 24ABB342 24ABB348 18,24,30 36 48,60 - X X 1,2 24ABB336 X X X O O X O O O O O O X X X O X O O X X X X O X FIELDCONTROL SUPPLYCONN. 7/8"HOLE 32 5/16" 35 3/4" 25 1/2" 28 15/16" 31 3/16" 31 3/16" 31 3/16" 3 1/2" 35" X 35" 26" X 26" VAPORLINECONN. D C X = YES O = NO 3 7/8" 32 5/16" 25 3/4" 31 3/16" 7/8" 7/8" 7/8" 7/8" 7/8" 3/4" 3/4" SQ.
Certified Drawing for AHU CU-9 Project: ~Untitled68 Prepared By: 08/19/2014 DIMENSIONS NOTES: 1. CONDENSATE PAN DRAIN CAPS NOT SHOWN FOR CLARITY. (cont.) SLOPECOIL 2. ALL DIMENSIONS ARE IN "INCHES" UNLESS NOTED. AIRFLOW 2 3/16" TYP. (2 PLACES)* 7/16" TYP. (2 PLACES)* AIRFLOW 3 1/4" F G 1" TYP. (2 PLACES)* PRIMARY DRAIN 1 1/4" SECONDARY DRAIN SECONDARY DRAIN PRIMARY DRAIN 2 7/8" 7/16" TYP. (4 PLACES)* 1 1/4" DOWNFLOW (FIELDCONVERTED) 2 3/16" TYP.
Certified Drawing for AHU CU-9 Project: ~Untitled68 Prepared By: 08/19/2014 DIMENSIONS UNIT A FX4DNF019 B C D 49 5/8" 17 5/8" 15 3/4" 15 5/8" FX4DNF025 23 5/8" - 17" X - SHIPPING WT (LBS) NON TIN-COATED 122 SHIPPING WT (LBS) TIN-COATED 122 F 15 3/8" COIL CONFIGURATION 23 1/8" E G H J SLOPE "A" 49 5/8" 17 5/8" 15 3/4" 15 5/8" 15 3/8" 23 1/8" 23 5/8" - 17" X - 122 122 FX4DNF031 53 7/16" 21 1/8" 19 1/4" 19 1/8" 19 3/16" 26 15/16" 27 1/2" - 19" X - 146 146
Guide Specification for AHU CU-9 Project: ~Untitled68 Prepared By: 08/19/2014 GUIDE SPECIFICATIONS GENERAL 24ABB System Description Outdoor-mounted, air-cooled, split-system air conditioner unit suitable for ground or rooftop installation. Unit consists of a hermetic compressor, an air-cooled coil, propeller-type condenser fan, and a control box. Unit will discharge supply air upward as shown on contract drawings.
Guide Specification for AHU CU-9 Project: ~Untitled68 Prepared By: 08/19/2014 Guide Specifications – Fan Coils – Fixed Speed Guide Specifications for ________________________________. (See the most recent edition of publication ___________________for data for the specific model to be specified). Furnish and Install _________________ direct expansion fan coil(s) equipped with cooling control kit and _____(with) _____(without) electric heater in the location and manner shown on the plan.
Unit Report For AHU CU 10 Project: ~Untitled65 Prepared By: Outdoor Unit Parameters Unit Model: Unit Size: Voltage: 05/30/2014 24ABB 2 Tons 208/230-1-60 V-Ph-Hz Outdoor Unit Dimensions and Weight Unit Length: Unit Width: Unit Height: Unit Shipping Weight: 25 36 34 134 in in in lb Indoor Unit Parameters FX4D Unit Model: 24,000 Btuh Unit Size: Cabinet Insulation:Single-piece cabinet with 1-in.
Performance Summary For AHU CU 10 Project: ~Untitled65 Prepared By: 05/30/2014 System Performance System: System Quantity: Altitude: Linear Pipe Length: SEER @ ARI Conditions: EER @ ARI Conditions: 24ABB/FX4D 1 0.0 ft 0.0 ft 14.5 12.0 Actual Airflow: Standard Airflow: Total Net Clg Capacity: Net Sensible Clg Capacity: Total System Power: 800.0 800.0 22.92 17.38 1.
Acoustic Summary For AHU CU 10 Project: ~Untitled65 Prepared By: 05/30/2014 Outdoor Unit Parameters: Unit Model: Unit Size: Variations: Octave Band Center Frequency, Hz Sound Power,dB A-Weighted Sound Power, dBA Indoor Unit Parameters: Unit Model: Unit Size: Cabinet Insulation: Octave Band Center Frequency, Hz Sound Power,dB A-Weighted Sound Power, dBA Residential Carrier Products Bldr 1.19p 24ABB 2 Tons Dense Grille 63 0.0 125 55.0 250 61.5 500 67.0 1k 71.5 2k 69.0 4k 61.0 8k 55.0 dBA 76.
O 0,1 1,2 2 2 24ABB342 24ABB348 18,24,30 36 48,60 - X X 1,2 24ABB336 X X X O O X O O O O O O X X X O X O O X X X X O X FIELDCONTROL SUPPLYCONN. 7/8"HOLE 32 5/16" 35 3/4" 25 1/2" 28 15/16" 31 3/16" 31 3/16" 31 3/16" 3 1/2" 35" X 35" 26" X 26" VAPORLINECONN. D C X = YES O = NO 3 7/8" 32 5/16" 25 3/4" 31 3/16" 7/8" 7/8" 7/8" 7/8" 7/8" 3/4" 3/4" SQ.
Certified Drawing for AHU CU 10 Project: ~Untitled65 Prepared By: 05/30/2014 DIMENSIONS NOTES: 1. CONDENSATE PAN DRAIN CAPS NOT SHOWN FOR CLARITY. (cont.) SLOPECOIL 2. ALL DIMENSIONS ARE IN "INCHES" UNLESS NOTED. AIRFLOW 2 3/16" TYP. (2 PLACES)* 7/16" TYP. (2 PLACES)* AIRFLOW 3 1/4" F G 1" TYP. (2 PLACES)* PRIMARY DRAIN 1 1/4" SECONDARY DRAIN SECONDARY DRAIN PRIMARY DRAIN 2 7/8" 7/16" TYP. (4 PLACES)* 1 1/4" DOWNFLOW (FIELDCONVERTED) 2 3/16" TYP.
Certified Drawing for AHU CU 10 Project: ~Untitled65 Prepared By: 05/30/2014 DIMENSIONS UNIT A FX4DNF019 B C D 49 5/8" 17 5/8" 15 3/4" 15 5/8" FX4DNF025 23 5/8" - 17" X - SHIPPING WT (LBS) NON TIN-COATED 122 SHIPPING WT (LBS) TIN-COATED 122 F 15 3/8" COIL CONFIGURATION 23 1/8" E G H J SLOPE "A" 49 5/8" 17 5/8" 15 3/4" 15 5/8" 15 3/8" 23 1/8" 23 5/8" - 17" X - 122 122 FX4DNF031 53 7/16" 21 1/8" 19 1/4" 19 1/8" 19 3/16" 26 15/16" 27 1/2" - 19" X - 146 14
Unit Report For AHU CU 12 Project: ~Untitled65 Prepared By: Outdoor Unit Parameters Unit Model: Unit Size: Voltage: 05/30/2014 24ABB 1.5 Tons 208/230-1-60 V-Ph-Hz Outdoor Unit Dimensions and Weight Unit Length: Unit Width: Unit Height: Unit Shipping Weight: 25 36 34 130 in in in lb Indoor Unit Parameters FX4D Unit Model: 18,000 Btuh Unit Size: Cabinet Insulation:Single-piece cabinet with 1-in.
Performance Summary For AHU CU 12 Project: ~Untitled65 Prepared By: 05/30/2014 System Performance System: System Quantity: Altitude: Linear Pipe Length: SEER @ ARI Conditions: EER @ ARI Conditions: 24ABB/FX4D 1 0.0 ft 0.0 ft 14.5 12.0 Actual Airflow: Standard Airflow: Total Net Clg Capacity: Net Sensible Clg Capacity: Total System Power: 525.0 525.0 16.81 12.51 1.
Acoustic Summary For AHU CU 12 Project: ~Untitled65 Prepared By: 05/30/2014 Outdoor Unit Parameters: Unit Model: Unit Size: Variations: Octave Band Center Frequency, Hz Sound Power,dB A-Weighted Sound Power, dBA Indoor Unit Parameters: Unit Model: Unit Size: Cabinet Insulation: Octave Band Center Frequency, Hz Sound Power,dB A-Weighted Sound Power, dBA Residential Carrier Products Bldr 1.19p 24ABB 1.5 Tons Dense Grille 63 0.0 125 53.5 250 59.5 500 63.5 1k 67.0 2k 63.5 4k 59.0 8k 52.5 dBA 72.
O 0,1 1,2 2 2 24ABB342 24ABB348 18,24,30 36 48,60 - X X 1,2 24ABB336 X X X O O X O O O O O O X X X O X O O X X X X O X FIELDCONTROL SUPPLYCONN. 7/8"HOLE 32 5/16" 35 3/4" 25 1/2" 28 15/16" 31 3/16" 31 3/16" 31 3/16" 3 1/2" 35" X 35" 26" X 26" VAPORLINECONN. D C X = YES O = NO 3 7/8" 32 5/16" 25 3/4" 31 3/16" 7/8" 7/8" 7/8" 7/8" 7/8" 3/4" 3/4" SQ.
Certified Drawing for AHU CU 12 Project: ~Untitled65 Prepared By: 05/30/2014 DIMENSIONS NOTES: 1. CONDENSATE PAN DRAIN CAPS NOT SHOWN FOR CLARITY. (cont.) SLOPECOIL 2. ALL DIMENSIONS ARE IN "INCHES" UNLESS NOTED. AIRFLOW 2 3/16" TYP. (2 PLACES)* 7/16" TYP. (2 PLACES)* AIRFLOW 3 1/4" F G 1" TYP. (2 PLACES)* PRIMARY DRAIN 1 1/4" SECONDARY DRAIN SECONDARY DRAIN PRIMARY DRAIN 2 7/8" 7/16" TYP. (4 PLACES)* 1 1/4" DOWNFLOW (FIELDCONVERTED) 2 3/16" TYP.
Certified Drawing for AHU CU 12 Project: ~Untitled65 Prepared By: 05/30/2014 DIMENSIONS UNIT A FX4DNF019 B C D 49 5/8" 17 5/8" 15 3/4" 15 5/8" FX4DNF025 23 5/8" - 17" X - SHIPPING WT (LBS) NON TIN-COATED 122 SHIPPING WT (LBS) TIN-COATED 122 F 15 3/8" COIL CONFIGURATION 23 1/8" E G H J SLOPE "A" 49 5/8" 17 5/8" 15 3/4" 15 5/8" 15 3/8" 23 1/8" 23 5/8" - 17" X - 122 122 FX4DNF031 53 7/16" 21 1/8" 19 1/4" 19 1/8" 19 3/16" 26 15/16" 27 1/2" - 19" X - 146 14
Guide Specification for AHU CU 12 Project: ~Untitled65 Prepared By: 05/30/2014 GUIDE SPECIFICATIONS GENERAL 24ABB System Description Outdoor-mounted, air-cooled, split-system air conditioner unit suitable for ground or rooftop installation. Unit consists of a hermetic compressor, an air-cooled coil, propeller-type condenser fan, and a control box. Unit will discharge supply air upward as shown on contract drawings.
Guide Specification for AHU CU 12 Project: ~Untitled65 Prepared By: 05/30/2014 Guide Specifications – Fan Coils – Fixed Speed Guide Specifications for ________________________________. (See the most recent edition of publication ___________________for data for the specific model to be specified). Furnish and Install _________________ direct expansion fan coil(s) equipped with cooling control kit and _____(with) _____(without) electric heater in the location and manner shown on the plan.
HVAC Submittal Cover Sheet SECTION: 2 PRODUCT: Roof Top Unit Paulson-Cheek Mechanical, Inc. 6145 Norhtbelt Parkway, Suite F Norcross, GA 30071 PROJECT: Saint Michael The Archangel Catholic Church LOCATION: Woodstock, GA PHONE: 770-729-0076 FAX: 770-729-1076 Paulson-Cheek Mechanical, Inc. ARCHITECT'S/ENGINEER'S STAMP Paulson-Cheek Mechanical, Inc.
Unit Report For RTU-1 Project: ~Untitled65 Prepared By: 05/30/2014 10:46AM Unit Parameters 50ES-A36---6 Unit Model: 36 (3 Tons) Unit Size: 460-3-60 Volts-Phase-Hertz: Electric Heating Type: Vertical Supply / Vertical Return Duct Cfg: Dimensions (ft. in.) & Weight (lb.) *** 4' 0.1875'' Unit Length: 2' 8.625'' Unit Width: 3' 10'' Unit Height: *** Weights and Dimensions are approximate. Weight does not include roof curbs, unit packaging, field installed accessories or factory installed options.
Certified Drawing for RTU-1 Project: ~Untitled65 Prepared By: 05/30/2014 10:46AM Packaged Rooftop Builder 1.
Performance Summary For RTU-1 Project: ~Untitled65 Prepared By: 05/30/2014 10:46AM Part Number:50ES-A36---6 ARI SEER: Base Unit Dimensions Unit Length: Unit Width: Unit Height: Total Operating Weight: Unit Unit Voltage-Phase-Hertz: Air Discharge: Fan Drive Type: Actual Airflow: Site Altitude: 13.00 48.2 32.6 46.
Performance Summary For RTU-1 Project: ~Untitled65 Prepared By: 05/30/2014 10:46AM Acoustics Sound Rating: Sound Power Levels, db re 10E-12 Watts 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz Discharge NA NA NA NA NA NA NA NA 75.0 db Inlet NA NA NA NA NA NA NA NA Outdoor NA 64.0 63.5 68.0 70.5 64.5 61.0 61.0 Advanced Acoustics Advanced Accoustics Parameters 30.0 ft 1. Unit height above ground: 50.0 ft 2. Horizontal distance from unit to receiver: 5.7 ft 3.
Performance Summary For RTU-1 Project: ~Untitled65 Prepared By: 05/30/2014 10:46AM that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated.
Guide Specification for RTU-1 Project: ~Untitled65 Prepared By: 05/30/2014 10:46AM HVAC Guide Specifications Packaged Electric Cooling Unit Constant Volume Application Size Range: 2 to 5 Tons, Nominal Cooling Carrier Model Number: 50ES-A Part 1 — General SYSTEM DESCRIPTION Outdoor rooftop mounted or ground mounted, electric cooling unit utilizing a hermetic scroll compressor for cooling duty. Unit shall discharge supply air vertically or horizontally as shown on contract drawings.
Guide Specification for RTU-1 Project: ~Untitled65 Prepared By: 05/30/2014 10:46AM 1. Unit cabinet shall be constructed of phosphated, zinc--coated, pre--painted steel capable of with-standing 500 hours in salt spray. 2. Normal service shall be through a 3 removable cabinet panels. 3. The unit shall be constructed on a rust proof unit base that has an externally trapped, integrated sloped drain. 4. Evaporator fan compartment top surface shall be insulated with a minimum 1/2--in. (12.
Guide Specification for RTU-1 Project: ~Untitled65 Prepared By: 05/30/2014 10:46AM L. Special Features: 1. Coil Options: Base unit with tin plated indoor coil hairpins available as a factory installed option. 2. Compressor Start Kit (single phase units only): Shall provide additional starting torque for single-phase compressors. 3. Thermostat: To provide for one-stage heating and cooling in addition manual or automatic changeover and indoor fan control. 4.
HVAC Submittal Cover Sheet SECTION: 3 PRODUCT: Ductless Split System Paulson-Cheek Mechanical, Inc. 6145 Norhtbelt Parkway, Suite F Norcross, GA 30071 PROJECT: Saint Michael The Archangel Catholic Church LOCATION: Woodstock, GA PHONE: 770-729-0076 FAX: 770-729-1076 Paulson-Cheek Mechanical, Inc. ARCHITECT'S/ENGINEER'S STAMP Paulson-Cheek Mechanical, Inc.
Submittal Data: PKA-A12HA & PUY-A12NHA3 12,000 Btu/h Wall-mounted Air-Conditioning SYSTEM Job Name: ST Michael the Archangel Location: Purchaser: Paulson Cheek Engineer: Submitted to: Unit Designation: For DFC/ DFCU-1 Reference Date: Leppard Johnson Approval Construction Schedule No.
Dimensions: PKA-A12HA
Dimensions: PUY-A12NHA3 Clearance space around the outdoor unit C SD - PKA-A12HA / PUY-A12NHA3 - 200907 © MITSUBISHI ELECTRIC / HVAC 2009 3400 Lawrenceville Suwanee Rd Suwanee, GA 30024 Tele: 678-376-2900 • Fax: 800-889-9904 Toll Free: 800-433-4822 (#3) www.mehvac.com Specifications are subject to change without notice.
HVAC Submittal Cover Sheet SECTION: 4 PRODUCT: Ceiling, Kitchen and Make-Up Exhaust Fans Paulson-Cheek Mechanical, Inc. 6145 Norhtbelt Parkway, Suite F Norcross, GA 30071 PROJECT: Saint Michael The Archangel Catholic Church LOCATION: Woodstock, GA PHONE: 770-729-0076 FAX: 770-729-1076 Paulson-Cheek Mechanical, Inc. ARCHITECT'S/ENGINEER'S STAMP Paulson-Cheek Mechanical, Inc.
A/E confirm manufacturer and models for KEF and MAU.
HVAC Submittal Cover Sheet SECTION: 5 PRODUCT: Wall Caps for Exhaust fans Paulson-Cheek Mechanical, Inc. 6145 Norhtbelt Parkway, Suite F Norcross, GA 30071 PROJECT: Saint Michael The Archangel Catholic Church LOCATION: Woodstock, GA PHONE: 770-729-0076 FAX: 770-729-1076 Paulson-Cheek Mechanical, Inc. ARCHITECT'S/ENGINEER'S STAMP Paulson-Cheek Mechanical, Inc.
HVAC Submittal Cover Sheet SECTION: 6 PRODUCT: Motor Operated Dampers Paulson-Cheek Mechanical, Inc. 6145 Norhtbelt Parkway, Suite F Norcross, GA 30071 PROJECT: Saint Michael The Archangel Catholic Church LOCATION: Woodstock, GA PHONE: 770-729-0076 FAX: 770-729-1076 Paulson-Cheek Mechanical, Inc. ARCHITECT'S/ENGINEER'S STAMP Paulson-Cheek Mechanical, Inc.
A/E Verify
HVAC Submittal Cover Sheet SECTION: 7 PRODUCT: Manual Volume Dampers Paulson-Cheek Mechanical, Inc. 6145 Norhtbelt Parkway, Suite F Norcross, GA 30071 PROJECT: Saint Michael The Archangel Catholic Church LOCATION: Woodstock, GA PHONE: 770-729-0076 FAX: 770-729-1076 Paulson-Cheek Mechanical, Inc. ARCHITECT'S/ENGINEER'S STAMP Paulson-Cheek Mechanical, Inc.
A/E Verify
HVAC Submittal Cover Sheet SECTION: 8 PRODUCT: Fire Dampers Paulson-Cheek Mechanical, Inc. 6145 Norhtbelt Parkway, Suite F Norcross, GA 30071 PROJECT: Saint Michael The Archangel Catholic Church LOCATION: Woodstock, GA PHONE: 770-729-0076 FAX: 770-729-1076 Paulson-Cheek Mechanical, Inc. ARCHITECT'S/ENGINEER'S STAMP Paulson-Cheek Mechanical, Inc.
HVAC Submittal Cover Sheet SECTION: 9 PRODUCT: Line Dampers Paulson-Cheek Mechanical, Inc. 6145 Norhtbelt Parkway, Suite F Norcross, GA 30071 PROJECT: Saint Michael The Archangel Catholic Church LOCATION: Woodstock, GA PHONE: 770-729-0076 FAX: 770-729-1076 Paulson-Cheek Mechanical, Inc. ARCHITECT'S/ENGINEER'S STAMP Paulson-Cheek Mechanical, Inc.
HVAC Submittal Cover Sheet SECTION: 10 PRODUCT: Wall Louvers Paulson-Cheek Mechanical, Inc. 6145 Norhtbelt Parkway, Suite F Norcross, GA 30071 PROJECT: Saint Michael The Archangel Catholic Church LOCATION: Woodstock, GA PHONE: 770-729-0076 FAX: 770-729-1076 Paulson-Cheek Mechanical, Inc. ARCHITECT'S/ENGINEER'S STAMP Paulson-Cheek Mechanical, Inc.
FAX TO: (404) 605-0690 Brian Rucks ( ) - Carl Trevathan The Winter Construction Company 191 Peachtree St., Suite 2100 Atlanta, Georgia 30303 Phone: 404-588-3300 Fax: 404-223-1146 Request for Information St. Michael the Archangel Catholic Church RFI #: 58 Winter Project No: 14-044 Location: 490 Arnold Mill Road Brian Rucks (Sizemore Group) To: cc: Reason for Request: Insufficient Information Engineering Conflict Alternative Proposal Other Sub / Vendor: PAULSON-CHEEK MECH, INC.
For and on Behalf of Sizemore Group Dated: 10/28/2014 Signed: Title: Brian Rucks Project Architect Trades Affected: Resultant Delay: Schedule Impact: Cost Impact: Attachments: Louver Size Drawings.pdf Distribution: Response Distribution: TWCC's Project RFI # is: 58 St.
HVAC Submittal Cover Sheet SECTION: 11 Grilles, Registers & Diffusers w/ Plenums & Cable-Op Dampers Paulson-Cheek Mechanical, Inc. 6145 Norhtbelt Parkway, Suite F Norcross, GA 30071 PROJECT: Saint Michael The Archangel Catholic Church LOCATION: Woodstock, GA PHONE: 770-729-0076 FAX: 770-729-1076 Paulson-Cheek Mechanical, Inc. ARCHITECT'S/ENGINEER'S STAMP Paulson-Cheek Mechanical, Inc.
A/E Verify
HVAC Submittal Cover Sheet SECTION: 12 PRODUCT: Take-Off Fittings Paulson-Cheek Mechanical, Inc. 6145 Norhtbelt Parkway, Suite F Norcross, GA 30071 PROJECT: Saint Michael The Archangel Catholic Church LOCATION: Woodstock, GA PHONE: 770-729-0076 FAX: 770-729-1076 Paulson-Cheek Mechanical, Inc. ARCHITECT'S/ENGINEER'S STAMP Paulson-Cheek Mechanical, Inc.
HVAC Submittal Cover Sheet SECTION: 13 PRODUCT: Flexible Ductwork Paulson-Cheek Mechanical, Inc. 6145 Norhtbelt Parkway, Suite F Norcross, GA 30071 PROJECT: Saint Michael The Archangel Catholic Church LOCATION: Woodstock, GA PHONE: 770-729-0076 FAX: 770-729-1076 Paulson-Cheek Mechanical, Inc. ARCHITECT'S/ENGINEER'S STAMP Paulson-Cheek Mechanical, Inc.
HVAC Submittal Cover Sheet SECTION: 14 PRODUCT: Controls Paulson-Cheek Mechanical, Inc. 6145 Norhtbelt Parkway, Suite F Norcross, GA 30071 PROJECT: Saint Michael The Archangel Catholic Church LOCATION: Woodstock, GA PHONE: 770-729-0076 FAX: 770-729-1076 Paulson-Cheek Mechanical, Inc. ARCHITECT'S/ENGINEER'S STAMP Paulson-Cheek Mechanical, Inc.
Control Drawings Prepared for: St. Michael the Archangel Church 490 Arnold Mill Rd. Woodstock, GA 30188 DATE: 08/18/2014 JOB NUMBER: A DIVISION OF United Green Building Solutions 3687 McElroy Rd. Atlanta, GA 30340 Stipulation for Reuse This Drawing was created for use on a specific site contemporaneously with its issue date. It is not suitable for use on a different project site or at a later time.
TEC Series Wireless Thermostat Controller System for Staged Equipment Code No. LIT-12011400 Product Bulletin Issued June 4, 2009 Supersedes March 25, 2009 TEC2001-3, TEC2002-3, TEC2003-3, TEC2004-3 The TEC Series Wireless Thermostat Controller System provides wireless networked control of Heating, Ventilating, and Air Conditioning (HVAC) equipment on a Building Automation System (BAS) that enables remote monitoring and programming.
Applications IMPORTANT: Use the TEC Series Wireless Thermostat Controller System only to provide an input to equipment under normal operating conditions. Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system.
While using industry-standard frequencies, the devices use a proprietary protocol that secures the RF data transmissions and inhibits the deciphering of any intercepted RF data.
Ethernet Network TEC20-3C Coordinator (BACnet IP) NAE or Other Supervisory Controller TEC Wireless Thermostat Controller TEC Wireless Thermostat Controller TEC Wireless Thermostat Controller BACnet MS/TP FC Bus TEC Wireless Thermostat Controller FEC Device Address 4 TEC Wireless Thermostat Controller TEC Wireless Thermostat Controller IOM Device Address 5 TEC Wireless Thermostat Controller TEC Wireless Thermostat Controller TEC Wireless Thermostat Controller TEC20-6C Coordinator (BACnet MS/TP
Supervisory Controllers The TEC Series Wireless Thermostat Controller System uses Web-enabled, Ethernet-based, supervisory controllers that connect BAS networks to IP networks and the Web. These supervisory controllers provide scheduling, alarm and event management, trending, energy management, data exchange, dial-out capability, and password protection. With a computer running Microsoft® Internet Explorer® Web browser version 6.
See the following list for features common to TEC Wireless Thermostat Controllers for staged equipment control: • Remote Indoor Sensing Accommodates remote indoor sensors. Up to three indoor sensors can be averaged. • Adjustable Heating/Cooling Deadband Adjusts the minimum heating/cooling deadband from 2.0F°/1.0C° to 5.0F°/2.5C°. • • Easy-to-Use Interface Keys Allow for easy commissioning of the thermostat, and eliminate the need for DIP switches.
See Table 4 for information on the LEDs used on specific models. Status LED (beneath cover) Table 4: LED Status Indicators Backlit Plain-Text LCD System Activity LEDs YES NO FIG:TEC200x-3_frnt Intuitive Operation Keys Room Temp 70.0ºF Figure 5: Front Cover User Interface Keys The user interface consists of five keys on the front cover as illustrated in Figure 5.
Main User Menu The Main User Menu allows the user to access and change the basic operating parameters: The Main User Menu uses Auto Help. Auto Help is displayed automatically in the Main User Menu when there is a pause in programming activity. • Temperature Setpoints • System Mode • Fan Mode Installer Configuration Menu The Installer Configuration Menu allows the installer to set up the TEC Wireless Thermostat Controller for an application-specific operation.
Ordering Information Repair Information Use the information in Table 6 to order a TEC200x-3 Wireless Thermostat Controller for Staged Equipment Control. Use the information in Table 7 to order a TEC20 Coordinator. Use the information in Table 8 to order accessories. If the TEC Wireless Thermostat Controller System for Staged Equipment fails to operate within its specifications, replace the unit. For a replacement, contact the nearest Johnson Controls representative.
Technical Specifications TEC20 Wireless Coordinator Product Code Numbers TEC20-3C-2: BACnet IP Version TEC20-6C-2: BACnet MS/TP Version Power Requirements 15 VDC, 6 W Maximum Platform IBM® PowerPC® 405EP 250 MHz Processor 64 MB SDRAM and 64 MB Serial Flash Battery Backup - Shutdown Begins within 10 Seconds Real-Time Clock - 3 Month Backup Maximum with Battery Operating System NiagraAX Communications Ethernet: Two 10/100 Mbps Ports (RJ-45 Connection) RS-232: 9-Pin D-Shell Connection RS-485: 3-Pin No
TEC200x-3 Wireless Thermostat Controllers (Part 2 of 2) Auxiliary/Outdoor Air Temperature Indication Range -40.0°C/-40.0°F to 50.0°C/122.0°F Minimum Deadband 1C°/2F° between Heating and Cooling Ambient Conditions Operating: 0 to 50°C (32 to 122°F); 95% RH Maximum, Noncondensing Storage: -30 to 50°C (-22 to 122°F); 95% RH Maximum, Noncondensing Compliance United States: UL Listed, File E27734, CCN XAPX, Under UL 873, Temperature Indicating and Regulating Equipment FCC Compliant to Part 15.
Building Efficiency 507 E. Michigan Street, Milwaukee, WI 53202 Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc. All other marks herein are the marks of their respective owners. © 2009 Johnson Controls, Inc. 12 TEC Series Wireless Thermostat Controller System for Staged Equipment Product Bulletin Published in U.S.A. www.johnsoncontrols.