Specifications

GEMINI TM
38AQ007
38ARQ008,012
38AQS016
Split System Heat Pumps
50/60 Hz
Installation, Start-Up and Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ...................... 1
INSTALLATION ................................ 1-17
General .......................................... l
Step 1 -- Complete Pre-lnstallation Checks ...... 1
Step 2 -- Rig and Mount Unit ..................... 1
Step 3 -- Complete Refrigerant Piping
Connections .................................. 10
Step 4 -- Complete Electrical Connections ...... 11
PRE-START-UP ............................... 18, 19
START-UP .................................... 19-21
SEQUENCE OF OPERATION ................. 21,22
SERVICE ..................................... 22-27
TROUBLESHOOTING ......................... 28, 29
START-UP CHECKLIST .................. CL-I, CL-2
SAFETY CONSIDERATIONS
Installing, stalling up, and servicing air-conditioning equip-
ment can be hazardous due to system pressures, electric;d
components, and equipment location (roofs, elevated struc-
tures, etc.).
Only tnuned, qualified installers and service mechanics
should install, start-up, and service this equipment. Untrained
pel_onnel can perforru basic maintenance functions such as
cleaning coils. All other operations should be performed by
trained service pel_onnel.
When working on the equipment, observe precautions in
the literature and on tags, stickers, and labels attached to the
equipment.
Follow all safety codes. Wear safety glasses and work
gloves. Keep quenching cloth and fire extinguisher nem_y
when brazing. Use care in handling, rigging, and setting bulky
equipment.
Before installing or servicing system, ¢flways turn off main
power to system and inst_fll lockout tag on disconnect.
There may be more than one disconnect switch. Electric_d
shock can cause personal injury.
INSTALLATION
General -- The split systeln heat pump units described in
this book should only be used with fire40RMQ indoor pack-
aged air handler sections.
Step 1 -- Complete Pre-lnstallation Checks
UNCRATE UNIT- Remove unit packaging except for the
top skid assembly, which should be left in place until after the
unit is rigged into its final location.
INSPECT SHIPMENT -- File claim with shipping company
if shipment is damaged or incomplete.
CONSIDER SYSTEM REQUIREMENTS
Consult local building codes and National Electrical
Code (NEC, U.S.A.) for special installation requirements.
Allow sufficient space for airflow clearance, wiring,
refi'igerant piping, and servicing unit. See Fig. 1-3 for
unit dimensions. Figure 4 shows typical component loca-
tions for 38AQS016 units.
Locate unit so that outdoor coil airflow is unrestricted on
all sides and above.
Unit may be mounted on a level pad directly on the base
channels or mounted on raised pads at support points.
See Tables IA-ID for unit operating weights.
Step 2 -- Rig and Mount Unit
Be sure unit panels are securely in place prior to rigging.
Be cgueful rigging, handling, and installing unit. Improper
unit location can cause system malfunction and material
damage. Inspect base rails for any shipping damage and
make sum they are fastened securely to unit before rigging.
RIGGING -- These units are designed for overhead rigging.
Refer to rigging label for preferred rigging method. Spreader
bars am not required if top crating is left on unit. All panels
must be in place when rigging. As lin-ther protection for coil
faces, plywood sheets may be placed against sides of unit,
behind cables. Run cables to a centrtd suspension point so that
angle from the horizontal is not less than 45 degrees. Raise and
set unit down careliflly.
If it is necessary to roll the unit into position, mount the unit
on field-supplied rails placed lengthwise under the unit using a
minimum of 3 rollers. Apply force to the rails, not the unit. ff
the unit is to be skidded into position, place it on a large pad
and di'ag it by the pad. Do not apply any force to fire unit.
Raise from above to lift unit from the mils or pad when unit
is in final position.
After unit in position, remove all shipping materials and top
crating.
LOCATE UNIT- For service access and unrestricted air-
flow, provide clearance on each end and side of unit. Position
unit so that there is unrestricted airflow above unit.
NOTE: Before mounting unit, remove holddown brackets and
release skid.
If conditions or local codes require unit to be fastened to
pad, use the mounting holes in the base rails.
MOUNT UNIT -- The unit may be mounted on a solid, level
concrete pad, on accessory mounting legs, or on field-supplied
raised supports at each mounting position. (Note that mounting
hardware is field supplied.)
Bolt unit securely to pad or supports after unit is in position
and is level. Be sure to mount unit level to ensure proper oil
return to compressors. Mounting holes on unit can be used to
secure unit to vibration isolators, if required.