DETAI LED COOLING CAPACI TI ES (CONT.)
EVAPORATOR AIR
CONDENSER ENTERING AIR TEMPERATURES deg ˚F(˚C)
75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7)
CFM EWB
Capacity MBtuh
Tot al S y s -
tem KW
Capacity MBtuh
Tot al
System
KW
Capacity MBtuh
Tot al
System
KW
Capacity MBtuh
Tot al
System
KW
Capacity MBtuh
Tot al
System
KW
Capacity MBtuh
Tot al
System
KW
Tot al Sens Tot a l Sens To t a l Sens To ta l Sens To t a l Sens To ta l Sens
25HCS360C30 Outdoor Section With FC4DN(F,B)060 Indoor Section
1750
72 69.08 35.57 4.41 66.46 34.55 4.82 63.76 33.51 5.28 60.98 32.46 5.79 58.07 31.36 6.35 55.03 30.23 6.95
67 63.00 44.16 4.34 60.58 43.11 4.75 58.07 42.04 5.21 55.49 40.95 5.72 52.81 39.83 6.27 50.00 38.66 6.87
63 58.60 42.72 4.29 56.33 41.68 4.71 0.00 0.00 0.00 51.56 39.50 5.67 49.03 38.37 6.21 46.39 37.19 6.81
62 57.53 52.69 4.28 55.33 51.59 4.70 53.07 50.45 5.15 50.75 49.24 5.66 48.37 47.91 6.21 46.07 46.07 6.80
57 55.75 55.75 4.27 53.98 53.98 4.68 52.14 52.14 5.14 50.22 50.22 5.65 48.20 48.20 6.20 46.08 46.08 6.80
2000
72 70.29 37.22 4.50 67.57 36.18 4.92 64.76 35.13 5.38 61.88 34.07 5.89 58.86 32.96 6.44 55.72 31.81 7.05
67 64.12 46.90 4.44 61.60 45.84 4.85 59.00 44.75 5.31 56.33 43.65 5.82 53.55 42.49 6.37 50.65 41.30 6.97
63 59.68 45.29 4.39 57.32 44.23 4.80 54.88 43.13 5.26 52.36 42.01 5.76 49.74 40.85 6.31 47.02 39.64 6.90
62 58.77 56.33 4.38 56.52 55.12 4.79 54.24 53.79 5.25 52.03 52.03 5.76 49.89 49.89 6.31 47.64 47.64 6.92
57 57.93 57.93 4.37 56.04 56.04 4.79 54.08 54.08 5.25 52.04 52.04 5.76 49.89 49.89 6.31 47.64 47.64 6.92
2250
72 71.19 38.78 4.60 68.38 37.73 5.01 65.49 36.67 5.47 62.53 35.60 5.98 59.43 34.48 6.54 56.21 33.32 7.14
67 64.95 49.52 4.53 62.36 48.43 4.94 59.68 47.33 5.40 56.94 46.20 5.91 54.09 45.03 6.46 51.12 43.81 7.06
63 60.49 47.73 4.48 58.05 46.64 4.89 55.54 45.53 5.35 52.95 44.38 5.85 50.27 43.20 6.40 47.49 41.96 7.00
62 59.88 59.44 4.48 57.72 57.72 4.89 55.66 55.66 5.35 53.51 53.51 5.86 51.27 51.27 6.42 48.91 48.91 7.02
57 59.72 59.72 4.48 57.73 57.73 4.89 55.66 55.66 5.35 53.52 53.52 5.86 51.28 51.28 6.42 48.91 48.91 7.02
Cooling Indoor Model Capacity Power Furnace Model
*FC4DN(F,B)060 1.00 1.00
FK4DNB006 0.99 0.97
CSRH*6012A** 0.97 0.97 58CV(A,X)135---22
CAR**6024A** 0.98 0.98 58CV(A,X)155---22
CNRH*6024A** 0.97 0.97 58CV(A,X)155---22
CNRV*6024A** 0.97 0.97 58CV(A,X)155--- 22
CSRH*6012A** 0.98 0.97 58CV(A,X)155---22
NOTE: When the required data fa l ls between the published data, interpolati on may be performed. Extrapola ti on is not an acceptable practice.
* Detailed cooling capacities are based on i ndoor and outdoor unit at the same elevation per ARI standard 210/240--- 94. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
{ Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
} Sensible capacities sh own are based on 80_F(27_C) entering air at the indoor coil. For sensible capacities at other than 80_F(27_C), deduct 835 Btuh
(245 kW) per 1000 CF M (480 L/S) of i ndoor coil air for each degree below 80_F(27_C), o r add 835 Btuh (245 kW) per 1000 CFM (480 L/S) o f indoor coil air per degree above 80_F(27_C).
** System kw is total of indoor and outdoor unit kilowatts.
{{ At TVA rating indoor condition (75_F edb/63_F ewb). All other indoor air temperatures are at 80_F edb.
EWB Entering Wet Bulb
25HCS3C