Installation guide
PURON®
(R-410A)
REFRIGERANT
QUICK
REFERENCE
GUIDE
¢
Puron
refrigerant
operates
at
50-70
percent
higher
pressures
than
R-22.
Be
sure
that
servicing
equipment
and
replacement
components
are
designed
to
operate
with
Puron
refrigerant
¢
Puron
refrigerant
cylinders
are
rose
colored.
¢
Recovery
cylinder
service
pressure
rating
must
be
400
psig,
DOT
4BA400
or
DOT
BW400.
¢
Puron
refrigerant
systems
should
be
charged
with
liquid
refrigerant.
Use
a
commercial
type
metering
device
in
the
manifold
hose
when
charging
into
suction
line
with
compressor
operating
*
Manifold
sets
should
be
700
psig
high
side
and 180
psig
low
side
with
550
psig
low-side
retard.
¢
Use
hoses
with
700
psig
service
pressure
rating.
¢
Leak
detectors
should
be
designed
to
detect
HFC
refrigerant.
¢
Puron
refrigerant,
as
with
other
HFCs,
is
only
compatible
with
POE
oils.
*
Vacuum
pumps
will
not
remove
moisture
from
oil.
¢
Do
not
use
liquid-line
filter
driers
with
rated
working
pressures
less
than
600
psig.
¢
Do
not
leave
Puron
suction
line
filter
driers
in
line
longer
than
72
hours.
¢
Do
not
install
a
suction-line
filter
drier
in
liquid
line.
¢
POE
oils
absorb
moisture
rapidly.
Do
not
expose
oil
to
atmosphere.
¢
POE
oils
may
cause
damage
to
certain
plastics
and
roofing
materials.
¢
Wrap
all
filter
driers
and
service
valves
with wet
cloth
when
brazing.
¢
A
factory
approved
liquid-line
filter
drier
is
required
on
every
unit.
¢
Do
NOT
use
an
R-22
TXV.
¢
If
indoor
unit
is
equipped
with
an
R-22
TXV
or
piston
metering
device,
it
must
be
changed
to
a
hard
shutoff
Puron
TXV.
-
fia]
z
4
Li
to]
ey,
=
ma
z
4
Li
i]
¢
Never
open
system
to
atmosphere
while
it
is
under
a
vacuum.
¢
When
system
must
be
opened
for
service,
recover
refrigerant,
evacuate
then
break
vacuum
with
dry
nitrogen
and
replace
filter
driers.
Evacuate
to
500
microns
prior
to
recharging.
¢
Do
not
vent
Puron
refrigerant
into
the
atmosphere.
¢
Do
not
use
capillary
tube
coils.
¢
Observe
all
warnings,
cautions,
and
bold
text.
¢
All
indoor
coils
must
be
installed
with
a
hard
shutoff
Puron
TXV
metering
device.
Always
Ask
For
pACTORY.,
THORLEE
AUTARTS
Copyright
2012
Carrier
Corp.
#
7310
W.
Morris
St.
@
Indianapolis,
IN