Installation guide

Userefrigerationgradetubing.Servicevalvesareclosedfrom
factoryandreadyforbrazing.Afterwrappingservicevalvewitha
wetcloth,brazesweatconnectionsusingindustryaccepted
methodsandmaterials.Consultlocalcoderequirements.
Refrigeranttubingandindoorcoilarenowreadyforleaktesting.
Thischeckshouldincludeallfieldandfactoryjoints.
Table1 - Refrigerant Connections and Recommended Liquid
and Va mr Tube Diameters (In.)
UNIT SIZE (SERIES)
18, 24
30, 36
42, 48
60 (all series)
Notes:
LIQUID
Connection
& Tube
Diameter
3/8
3/8
3/8
3/8
RATED VAPOR
up to 80 ft. (24.38m)*
Connection Tube
Diameter Diameter
5/8 5/8
3/4 3/4
7/8 7/8
7/8 1-1/8
1. Tube diameters are for total equivalent lengths up to 80 ft. (24.38 m)
2. Do not apply capillary tube or fixed orifice indoor coils to these units.
* For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m)
horizontal or 20 ft, (6.10 m) vertical differential (250 ft, (76.2 m)Total
Equivalent Length), refer to the Longtine Guideline- Air Conditioners
and Heat Pumps using R-22
Install Liquid-Line Filter Drier Indoor
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
1. Installation of filter drier in liquid line is required.
2. Filter drier must be wrapped in a heat-sinking material
such as a wet cloth while brazing.
Refer to Fig. 3 and install filter drier as follows:
1. Braze 5-in. liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to above 5-in. (127 mm) liquid tube.
Flow arrow must point towards indoor coil.
4. Connect and braze liquid refrigerant tube to the filter drier.
A05178
Fig. 3 - Liquid Line Filter Drier
Evacuate Refrigerant Tubing and Indoor Coil
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using the
recommended deep vacuum method of 500 microns. The alternate
triple evacuation method may be used (see triple evacuation
procedure in service manual). Always break a vacuum with dry
nitrogen.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of
pulling a vacuum of 500 microns and a vacuum gage capable of
accurately measuring this vacuum depth. The deep vacuum method
is the most positive way of assuring a system is free of air and
liquid water. A tight dry system will hold a vacuum of 1000
microns after approximately 7 minutes. See Fig. 4.
IN
SYSTEM
VACUUM TIGHT
TOO WET
TIGHT
DRY SYSTEM
0 1 2 3 4 5 6 7
MINUTES
A95424
Fig. 4 - Deep Vacuum Graph
Final Tubing Check
IMPORTANT: Check to be certain factory tubing on both indoor
and outdoor unit has not shifted during shipment. Ensure tubes are
not rubbing against each other or any sheet metal or wires. Pay
close attention to feeder tubes, making sure wire ties on feeder
tubes are secure and tight.