Specifications

56
the graph (default settings are shown) describe a line the algo-
rithm uses to determine the maximum lift of the compressor for
the particular maximum operating speed. When the actual dif-
ferential pressure between the cooler and condenser (delta P)
and the temperature difference between the entering and leav-
ing chilled water (delta T) are above the line on the graph (as
defined by the minimum and full load points), the algorithm
operates in Surge Prevention mode. This is determined when
the ACTIVE DELTA T is less than SURGE/HGBP DEAD-
BAND.
When in Surge Prevention mode, with a command to in-
crease capacity, the VFD speed will increase until maximum
VFD speed is reached. At VFD MAXIMUM SPEED, when Ca-
pacity still needs to increase, the IGV’s open. When in Surge
Prevention mode and with a command to decrease capacity
only the IGVs will close, the VFD speed will not decrease.
Surge Protection (VFD Chiller) — The PIC II mon-
itors surge, which results in a fluctuation on the compressor
motor amperage. Each time the fluctuation in amperage ex-
ceeds an operator-specified limit (SURGE DELTA % AMPS)
plus a load correction factor, both SURGE COUNTS are incre-
mented by one and the VFD will increase in speed provided
that it is not already operating at VFD MAXIMUM SPEED or
that the VFD TARGET SPEED is forced. If the VFD cannot
increase in speed because the VFD is already at maximum
speed of the target speed is forced then the SURGE PROTEC-
TION COUNTS are also incremented by one. If more than 4
SURGE PROTECTION COUNTS occur within an operator-
specified time (SURGE TIME PERIOD) and the ACTUAL
VFD SPEED is greater than 90% then the PIC II declares an
Excessive Compressor Surge Alarm (238) and the chiller is
shut down. If more than four SURGE PROTECTION
COUNTS occur within the SURGE TIME PERIOD and the
ACTUAL VFD SPEED is less than 90% then the chiller is shut
down on a Excessive Compressor Surge / Low Speed Alarm
(236). Both SURGE COUNTS and SURGE PROTECTION
COUNTS are decreased by one if no surges occur within the
SURGE TIME PERIOD.
On chillers with VFDs, if a SURGE COUNT is registered
and the ACTUAL VFD SPEED is less than the VFD MAXI-
MUM SPEED then the TARGET VFD SPEED will be in-
creased by the amount configured in the VFD INCREASE
STEP parameter. The VFD will not decrease in speed if
SURGE COUNTS is greater than zero.
The threshold at which a current fluctuation is interpreted as
a surge can be adjusted from the OPTIONS screen. The por-
tion of the surge threshold attributable to current fluctuations
can be changed by scrolling to the SURGE DELTA % AMPS
parameter and adjusting it with the INCREASE or DE-
CREASE softkeys. The default setting is 10 %. The SURGE
TIME PERIOD can be adjusted from the OPTIONS screen.
Scroll to the SURGE TIME PERIOD parameter and use the
INCREASE or DECREASE softkey to adjust the surge count
time interval. The default setting is 8 minutes.
SURGE PROTECTION COUNTS are displayed in the
COMPRESS screen. Both SURGE PROTECTION COUNTS
and SURGE COUNTS are displayed in the SURGPREV
screen.
VFD Start-Up Speed Control — Immediately accel-
erating to a high VFD speed improves the ability of the com-
pressor to compensate for some start-up environments that ex-
ceed condenser water design conditions. The 19XRV chillers
initially accelerate to high VFD speed and then gradually slow
the compressor, if possible, while adjusting the guide vane po-
sition until a stable operating point with improved chiller effi-
ciency is attained.
Following a start command, the PIC II controls internally
set the VFD TARGET SPEED to the smaller of the VFD
MAXIMUM SPEED or the VFD START SPEED. Provided
that the chiller has sufficient capacity, the VFD will continue to
run at the startup speed during Ramp Loading until the chilled
water temperature falls within the CHILLED WATER DEAD-
BAND surrounding the Setpoint. RAMP LOADING AC-
TIVE in the SURGPREV screen will indicate YES during
Ramp Loading. The GUIDE VANE DELTA will be equal to
zero when the chilled water temperature is in the CHILLED
WATER DEADBAND. The VFD speed will then be ramped
down at one half of the VFD GAIN rate until, surge conditions
are encountered, the VFD MINIMUM SPEED is reached, the
ACTUAL GUIDE VANE POS reaches the GUIDE VANE
TRAVEL LIMIT, or the TARGET VFD SPEED is forced.
VFD RAMPDOWN ACTIVE in the SURGPREV screen will
indicate YES during the rampdown process. The VFD speed
will be regulated by standard capacity control and surge pre-
vention algorithms at the conclusion of the rampdown process.
Head Pressure Reference Output (See
Fig. 27) —
The PIC II control outputs a 4 to 20 mA signal
for the configurable Delta P (CONDENSER PRESSURE mi-
nus EVAPORATOR PRESSURE) reference curve shown in
Fig. 27. An output is available on the ISM module [Terminal
J8-3 (+), J8-4 (–) labeled spare]. The DELTA P AT 100% (chill-
er at maximum load condition default at 50 psi [344 kPa]),
DELTA P AT 0% (chiller at minimum load condition default at
25 psi [172.4 kPa]) and MINIMUM OUTPUT points are con-
figurable in the EQUIPMENT SERVICE-OPTIONS table.
When configuring this output ensure that minimum require-
ments for oil pressure and proper condenser FLASC orifice
performance are maintained.
The output may be useful as a reference signal to control a
tower bypass valve, tower speed control, condenser pump
speed control, etc. Note that it is up to the site design engineer-
ing agent to integrate this analog output with any external sys-
tem device(s) to produce the desired effect. Carrier does not
make any claim that this output is directly usable to control any
specific piece of equipment (that is, without further control ele-
ments or signal conditioning), although it may be.
The head pressure reference output will be on whenever the
condenser pump is operating; it may also be manually operated
in
CONTROLS TEST. When the head pressure differential is less
than the value entered for
DELTA P AT 0%, the output will be
maintained at 4 mA. The output is 2 mA when the chiller is not
running.
Lead/Lag Control — The lead/lag control system auto-
matically starts and stops a lag or second chiller in a 2-chiller
water system. A third chiller can be added to the lead/lag
MINIMUM
REFERENCE
OUTPUT
DELTA P
AT 100%
DELTA P
AT 0%
DELTA P
0 mA 2 mA
4 mA
(0%)
20 mA
(100%)
4 T0 20 mA OUTPUT
Fig. 27 — Head Pressure Reference Output
(Minimum Set Above 4 mA)