Specifications

54
the HOT GAS BYPASS/SURGE PREVENTION is off, the
point must pass through the deadband region to the line deter-
mined by the configured values before the HOT GAS BY-
PASS/SURGE PREVENTION will be turned on. As the point
moves from the region where the HOT GAS BYPASS/
SURGE PREVENTION is on, the point must pass through the
deadband region before the HOT GAS BYPASS/SURGE
PREVENTION is turned off. Information on modifying the de-
fault set points of the minimum and full load points may be
found in the Input Service Configurations section, page 55.
The state of the surge/hot gas bypass algorithm on the
HEAT_EX DISPLAY SCREEN (Surge/HGBP Active?).
Corrective action can be taken by making one of 2 choices.
If a hot gas bypass line is present and the hot gas option is se-
lected on the OPTIONS table (SURGE LIMIT/HGBP OPTION
is set to 1), the hot gas bypass valve can be energized.
If the hot gas bypass option is not selected (SURGE LIMIT/
HGBP OPTION is set to 0), prevent the guide vane opening
from increasing. See Table 7, Capacity Overrides. Both of
these corrective actions try to reduce the lift experienced by the
compressor and help prevent a surge condition.
Hot Gas Bypass (Optional) Algorithm — If a
hot gas bypass solenoid valve is present and the HGBP OP-
TION in the OPTIONS table is set to 1 or 2, this operator con-
figurable feature can determine if load conditions are too low
for the compressor and corrective action can be taken.
HGBP OPTION = 0 — The HGBP algorithm is disabled.
HGBP OPTION = 1 (Constant Flow Units with VFD
Option Disabled) — The algorithm determines if corrective
action is necessary by checking the chiller operating point
against an operator configured threshold. The threshold is cal-
culated from a combination of the difference between ENTER-
ING CHILLED WATER and LEAVING CHILLED WATER
and the difference between CONDENSER PRESSURE and
EVAPORATOR PRESSURE.
The operator configured data points in version 8 software
and prior software versions are the MIN LOAD POINT (T1/
P1), the LOW LOAD POINT (T2/P2), the MID LOAD
POINT (T3/P3) and the FULL LOAD POINT (T4/P4). These
points have default settings defined in the OPTIONS screen
and in Table 3. The Default settings use one set of values for
the low, mid, and full load points. These surge characteristics
are factory set based on the original selection, with the values
printed on a label fixed to the bottom of interior face of the con-
trol panel. A line is drawn between these points as shown in
Fig. 25. Sample points for a four point line are shown.
Whenever the ACTIVE DELTA T (actual temperature dif-
ference between the LEAVING CHILLED WATER and EN-
TERING CHILLED WATER) is on the left side of the line plot-
ted in Fig. 25, the algorithm will energize the hot gas bypass
valve to falsely load the compressor. If the ACTIVE DELTA T
falls to the right side of the line plotted in Fig 25 by more than
the HGBP DEADBAND, the hot gas bypass valve is deener-
gized. The HGBP valve is also deenergized if the ACTIVE
DELTA P (actual difference between CONDENSER PRES-
SURE and EVAPORATOR PRESSURE) falls below HGBP
DELTA P1.
If the chiller is used for other than its original design condi-
tions, instructions to configure the MIN LOAD POINT (T1/P1)
and FULL LOAD POINT (T4/P4) are on page 73. Use the T4
value for T2 and T3 also. Use the P4 value for P2 and P3 also.
HGBP OPTION = 1 (Constant Flow Units with VFD
Option Enabled) The HGBP is only energized if a SURGE
PROTECTION COUNT is registered, the ACTIVE DELTA T
falls below the SURGE/HGBP DELTA T or the VFD LOAD
FA C T O R approaches 1.0 and it is not possible to increase VFD
speed. The VFD speed cannot increase when the VFD TAR-
GET SPEED is equal to VFD MAXIMUM SPEED or if the
VFD TARGET SPEED is FORCED to a fixed value.
HGBP OPTION = 1 (Variable Primary Flow Units with
VFD Option Disabled) The algorithm determines if cor-
rective action is necessary by checking the chiller operating
point against an operator configured threshold. The threshold is
calculated from a combination of GUIDE VANE POSITION
and the difference between CONDENSER PRESSURE and
EVAPORATOR PRESSURE. The operator configured data
points are the MINIMUM and MAXIMUM SATURATED
TEMPERATURE DIFFERENCE (Surge/HGP Delta Tsmin
and Surge/HGBP DeltaTsmax), the MAXIMUM AND MINI-
MUM GUIDE VANE POSITIONS (Surge/HGBP IGVmax
and Surge/HGBP IGVmin) printed on a label fixed to the bot-
tom of interior face of the control panel. A line is calculated be-
tween these points.
Whe
never the ACTUAL GUIDE VANE POSITION is on the
left side of the plotted line, the algorithm will energize the hot
gas bypass valve to falsely load the compressor. If the ACTU-
AL GUIDE VANE POSITION falls to the right side of the plot-
ted line by more than the SURGE/HGBP DEADBAND, the hot
gas bypass valve is deenergized.
If the chiller is used for other than its original design condi-
tions, instructions to adjust the Surge / Hot Gas Bypass config-
urations are found on page 80.
HGBP OPTION = 1 (Variable Primary Flow Units with
VFD Option Enabled) The HGBP is only energized if a
SURGE PROTECTION COUNT is registered, the ACTIVE
DELTA T falls below the SURGE/HGBP DELTA T or the VFD
LOAD FACTOR approaches 1.0 and it is not possible to in-
crease VFD speed. The VFD speed cannot increase when the
VFD TARGET SPEED is equal to VFD MAXIMUM SPEED or
if the VFD TARGET SPEED is FORCED to a fixed value.
HGBP OPTION = 2 (Constant Flow and Variable Primary
Flow Units) This option energizes the HOT GAS BYPASS
RELAY solely based on the ACTIVE DELTA T (actual temper-
ature difference between the LEAVING CHILLED WATER and
ENTERING CHILLED WATER). Evaluation of the ACTIVE
DELTA T begins at the completion of ramp loading. The hot
gas bypass valve is energized if the ACTIVE DELTA T is less
than the HGBP ON DELTA T. The hot gas bypass relay will be
turned off when the ACTIVE DELTA T is greater than or equal
HGBP/SURGE PREVENTION ON
HGBP/SURGE PREVENTION OFF
(10.3, 91)
(7.9, 76.4)
(2.6, 64.4)
(0.9, 41.3)
100
90
80
70
60
50
40
30
HGBP
DEADBAND
Sample Points are not defaults
0 2 4 6 8 10 12
T (F)
P (psid)
LEGEND
P = (Condenser Pressure) – (Cooler Pressure)
T = (ECW) – (LCW)
Fig. 25 — 19XR Surge Prevention/Hot Gas Bypass
Option 1 (Constant Flow with VFD Option
Disabled)
ECW Entering Chilled Water
HGBP Hot Gas Bypass
LCW Leaving Chilled Water
a19-1862