Specifications
37
Table 3 — ICVC Display Data (cont)
EXAMPLE 21 — SETUP1 DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight .
6. Press
*When set to DISABLE, alarm functions as an alert.
NOTE: No variables are available for CCN read or write operation; forcing shall not be supported on service screens.
DESCRIPTION STATUS UNITS POINT DEFAULT
Comp Motor Temp Override 150-200 DEG F MT_OVER 200
Cond Press Override 90-165 PSI CP_OVER 125
Comp Discharge Alert 125-200 DEG F CD_ALERT 200
Comp Thrust Brg Alert 10-20 ^F TB_ALERT 10
Comp Thrust Brg Trip 160-185 DEG F TB_TRIP 185
Thrust Brg Reset Factor 1.0-3.0 TB_POWER 1.4
Chilled Medium 0/1 WATER/BRINE MEDIUM WATER
Chilled Water Deadband 0.5-2.0 ^F CWDB 1.0
Evap Refrig Trippoint 0.0-40.0 DEG F ERT_TRIP 33
Refrig Override Delta T 2.0-5.0 ^F REF_OVER 3
Evap Approach Alert 0.5-15 ^F EVAP_AL 5
Cond Approach Alert 0.5-15 ^F COND_AL 6
Condenser Freeze Point -20 - 35 DEG F CDFREEZE 34
Flow Delta P Display 0/1 DSABLE/ENABLE FLOWDISP DSABLE
Evap Flow Delta P Cutout 0.5 - 50.0 ^PSI EVAP_CUT 5.0
Cond Flow Delta P Cutout 0.5 - 50.0 ^PSI COND_CUT 5.0
Cond Hi Flow Alarm Opt* 0/1 DSABLE/ENABLE COND_ALM DSABLE
Cond Hi Flow Del P Limit 0.5-50.0 PSI COND_VAL 50.0
Water Flow Verify Time 0.5-5 MIN WFLOW_T 5
Oil Press Verify Time 15-300 SEC OILPR_T 40
Recycle Control
Restart Delta T 2.0-10.0 ^F rcycr_dt 5
Shutdown Delta T 0.5-4.0 ^F rcycs_dt 1
Spare Alert/Alarm Enable
Disable=0, Lo=1/3,Hi=2/4
Spare Temp #1 Enable 0-4 sp1_en 0
Spare Temp #1 Limit -40-245 DEG F sp1_lim 245
Spare Temp #2 Enable 0-4 sp2_en 0
Spare Temp #2 Limit -40-245 DEG F sp2_lim 245
MENU
SERVICE
EQUIPMENT SERVICE
SELECT
SETUP1
SELECT
312