Specifications

35
Table 3 — ICVC Display Data (cont)
EXAMPLE 19A — OPTIONS DISPLAY SCREEN (Machines with Serial Numbers Prior to 1410Qxxxxx)
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight .
6. Press .
NOTE: No variables are available for CCN read or write operation.
DESCRIPTION STATUS UNITS POINT DEFAULT
Auto Restart Option 0/1 DSABLE/ENABLE astart DSABLE
Remote Contacts Option 0/1 DSABLE/ENABLE r_contac DSABLE
Soft Stop Amps Threshold 40-100 % softstop 100
Surge / Hot Gas Bypass
Surge Limit/HGBP Option 0/1 srg_hgbp 0
Select: Surge=0, HGBP=1
Min. Load Point (T1,P1)
Surge/HGBP Delta T1 0.5-20 ^F hgb_dt1 1.5
Surge/HGBP Delta P1 30-170 ^PSI hgb_dp1 50
Low Load Point (T2,P2)
Surge/HGBP Delta T2 0.5-20 ^F hgb_dt2 10
Surge/HGBP Delta P2 30-170 ^PSI hgb_dp2 85
Mid Load Point (T3,P3)
Surge/HGBP Delta T3 0.5-20 ^F hgb_dt3 10
Surge/HGBP Delta P3 50-170 ^PSI hgb_dp3 85
Full Load Point (T4,P4)
Surge/HGBP Delta T4 0.5-20 ^F hbg_dt4 10
Surge/HGBP Delta P4 50-170 ^PSI hgb_dp4 85
Surge/HGBP Deadband 0.5-3 ^F hbg_db 1
Low Load HGBP
HGBP On Delta T 0.5-10.0 ^F hgb_ton 2.0
HGBP Off Delta T 1.0-10.0 ^F hgb_toff 4.0
Surge Protection
Surge Delta% Amps 5-20 % surge_a 10
Surge Time Period 7-10 MIN surge_t 8
Ice Build Control
Ice Build Option 0/1 DSABLE/ENABLE ibopt DSABLE
Ice Build Termination 0-2 ibterm 0
0=Temp, 1=Contacts, 2=Both
Ice Build Recycle 0/1 DSABLE/ENABLE ibrecyc DSABLE
Refrigerant Leak Option 0/1 DSABLE/ENABLE LEAK_EN DSABLE
Refrigerant Leak Alarm mA 4-20 mA LEAK_MA 20
Head Pressure Reference
Delta P at 0% (4mA) 20-85 ^PSI HPDPO 25
Delta P at 100% (20mA) 20-85 ^PSI HPDP100 35
Minimum Output 0-100 % HPDPMIN% 0
MENU
SERVICE
EQUIPMENT SERVICE
SELECT
OPTIONS
SELECT