Specifications

34
Table 3 — ICVC Display Data (cont)
EXAMPLE 18 — ISM_CONF DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Enter password (4444 Factory Default).
6. Scroll down to highlight .
7. Press .
NOTE: Option 3 for VFD is available on software Version 9 or higher. All other software versions use Option 2 for VFD.
DESCRIPTION STATUS UNITS POINT DEFAULT
Starter Type 0-3 starter 1
(0 = Full, 1 = Red, 2 = SS/VFD)
Motor Rated Line Voltage 200-13200 VOLTS rlv 460
Volt Transformer Ratio:1 1-115 vt_rat 1
Overvoltage Threshold 105-115 % overvolt 115
Undervoltage Threshold 85-95 % undrvolt 85
Over/Under Volt Time 1-10 SEC ovuntime 5
Voltage % Imbalance 1-10 % v_unbal 10
Voltage Imbalance Time 1-10 SEC vu_time 5
Motor Rated Load Amps 10-5000 AMPS rla 200
Motor Locked Rotor Trip 100-60000 AMPS mot_lra 1000
Locked Rotor Start Delay 1-10 cycles lrs_del 5
Starter LRA Rating 100-60000 AMPS str_lra 2000
Motor Current CT Ratio:1 10-1000 ct_ratio 100
Current % Imbalance 5-40 % c_unbal 15
Current Imbalance Time 1-10 SEC cu_time 5
Grnd Fault CT’s? 0/1 NO/YES gf_cts YES
Ground Fault CT Ratio:1 150 gfct_rat 150
Ground Fault Current 1-25 AMPS gf_amps 15
Ground Fault Start Delay 1-20 cycles gf_sdel 10
Ground Fault Persistence 1-10 cycles gf_pdel 5
Single Cycle Dropout 0/1 DSABLE/ENABLE 1cyc_en DSABLE
Frequency = 60 Hz? (No = 50) 0/1 NO/YES linefreq YES
Line Frequency Faulting 0/1 DSABLE/ENABLE freq_en DSABLE
MENU
SERVICE
ISM (STARTER) CONFIG DATA
SELECT
ISM_CONF
SELECT