Table 3 — ICVC Display Data (cont)
EXAMPLE 16 — WSMCHRLE DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight .
6. Press .
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance
screens.
EXAMPLE 17 — NET_OPT DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight .
6. Press .
NOTE: No variables are available for CCN read or write operation.
DESCRIPTION STATUS UNITS POINT
WSM Active? 0/1 NO/YES WSMSTAT
Chilled Water Temp 0.0-99.9 DEG F CHWTEMP
Equipment Status 0/1 OFF/ON CHWRST
Commanded State XXXXXXXX TEXT CHWRENA
CHW setpt Reset Value 0.0-25.0 DEG F CHWRVAL
Current CHW Set Point 0.0-99.9 DEG F CHWSTPT
DESCRIPTION STATUS UNITS POINT DEFAULT
Loadshed Function
Group Number 0-99 ldsgrp 0
Demand Limit Decrease 0-60 % ldsdlta 20
Maximum Loadshed Time 0-120 MIN maxshed 60
CCN Occupancy Config:
Schedule Number 3-99 occ_num 3
Broadcast Option 0-1 DSABLE/ENABLE occbrcst DSABLE
Alarm Configuration
Re-Alarm Time 0-1440 MIN retime 30
Alarm Routing xxxxxxxx routing 10000000
MENU
SERVICE
CONTROL ALGORITHM STATUS
SELECT
WSMCHRLE
SELECT
MENU
SERVICE
EQUIPMENT CONFIGURATION
SELECT
NET_OPT
SELECT