Specifications

30
Table 3 — ICVC Display Data (cont)
EXAMPLE 10 — SETPOINT DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Press .
NOTE: All variables are available for CCN read operation; forcing shall not be supported on setpoint screens.
EXAMPLE 11 — CAPACITY DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight .
6. Press .
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance
screen.
EXAMPLE 12 — OVERRIDE DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight .
6. Press .
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance
screens.
DESCRIPTION STATUS UNITS POINT DEFAULT
Base Demand Limit 40-100 % DLM 100
Control Point
LCW Setpoint 10-120 DEG F lcw_sp 50.0
ECW Setpoint 15-120 DEG F ecw_sp 60.0
Ice Build Setpoint 15-60 DEG F ice_sp 40.0
Tower Fan High Setpoint 55-105 DEG F TFH_SP 75
DESCRIPTION STATUS UNITS POINT
Entering Chilled Water –40-245 DEG F ECW
Leaving Chilled Water –40-245 DEG F LCW
Capacity Control
Control Point 10-120 DEG F ctrlpt
Control Point Error –99-99 ^F cperr
ECW Delta T –99-99 ^F ecwdt
ECW Reset –99-99 ^F ecwres
LCW Reset –99-99 ^F lcwres
Total Error + Resets –99-99 ^F error
Guide Vane Delta –2.0-2.0 % gvd
Target Guide Vane Pos 0-100 % GV_TRG
Actual Guide Vane Pos 0-100 % GV_POS
Target VFD Speed 0-100 % VFD_OUT
Actual VFD Speed 0-110 % VFD_ACT
VFD Gain 0.1-1.5 vfd_gain
VFD Load Factor 0.0-1.0 VFD_FACT
Demand Limit Inhibit 0.2-2.0 % DEM_INH
Amps/kW Ramp 40-100 % RAMP_LMT
DESCRIPTION STATUS UNITS POINT
Comp Motor Winding Temp –40-245 DEG F MTRW
Comp Motor Temp Override 150-200 DEG F MT_OVER
Condenser Pressure 0-420 PSI CRP
Cond Press Override 90-180 PSI CP_OVER
Calc Evap Sat Temp –40-245 DEG F ERT
Evap Sat Override Temp 2-45 DEG F ERT_OVER
Comp Discharge Temp
–40-245 DEG F CMPD
Comp Discharge Alert 125-200 DEG F CD_ALERT
Comp Thrust Lvg Oil Temp –40-245 DEG F MTRB_OIL
Comp Thrust Brg Reset –40-245 DEG F TB_RESET
Comp Thrust Brg Temp 155-175 DEG F MTRB
Comp Thrust Brg Alert 165-185 DEG F TB_ALERT
Comp Thrust Brg Trip 175-185 DEG F TB_TRIP
Actual Superheat –20-99 ^F SUPRHEAT
Superheat Required 6-99 ^F SUPR_REQ
Condenser Refrig Temp –40-245 DEG F CRT
MENU
SETPOINT
SELECT
MENU
SERVICE
CONTROL ALGORITHM STATUS
SELECT
CAPACITY
SELECT
MENU
SERVICE
CONTROL ALGORITHM STATUS
SELECT
OVERRIDE
SELECT