Table 3 — ICVC Display Data (cont)
EXAMPLE 4 — STARTUP DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
NOTE: All variables with CAPITAL LETTER point names are avail-
able for CCN read operation. Those shown with (**) shall support
write operations for the ICVC only.
EXAMPLE 5 — COMPRESS DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
NOTES:
1. All variables with CAPITAL LETTER point names are available
for CCN read operation. Those shown with (**) shall support
write operations for the ICVC only.
2. 0=Not Active, 1=Active, 2=Active and more than one degree
over the surge line.
DESCRIPTION STATUS UNITS POINT
Actual Guide Vane Pos 0-100 % GV_ACT
**Chilled Water Pump 0-1 OFF/ON CHWP
Chilled Water Flow 0-1 NO/YES CHW_FLOW
**Condenser Water Pump 0-1 OFF/ON CDP
Condenser Water Flow 0-1 NO/YES CDW_FLOW
Oil Pump Relay 0-1 OFF/ON OILR
**Oil Pump Delta P –6.7-200 ^PSI OILPD
Compressor Start Relay 0-1 OFF/ON CMPR
Compressor Start Contact 0-1 OPEN/CLOSED 1CR_A
Starter Trans Relay 0-1 OFF/ON CMPTRANS
Compressor Run Contact 0-1 OPEN/CLOSED 2M_AUX
**Tower Fan Relay Low 0-1 OFF/ON TFR_LOW
**Tower Fan Relay High 0-1 OFF/ON TFR_HIGH
Starter Fault 0-1 ALARM/NORMAL STR_FLT
Spare Safety Input 0-1 ALARM/NORMAL SAFETY
Shunt Trip Relay 0-1 OFF/ON TRIPR
ISM Fault Status 0-255 ISMFLT
MENU
STATUS
STARTUP
SELECT
DESCRIPTION STATUS UNITS POINT
Actual Guide Vane Pos 0-100 % GV_POS
Guide Vane Delta –2.0-2.0 % GV_DELTA
**Target Guide Vane Pos 0-100 % GV_TRG
Oil Sump Temp –40-245 DEG F OILT
**Oil Pump Delta P –6.7-200 ^PSI OILPD
Comp Discharge Temp –40-245 DEG F CMPD
Comp Thrust Lvg Oil Temp –40-245 DEG F MTRB_OIL
Comp Thrust Brg Reset –40-245 DEG F TB_RESET
Comp Thrust Brg Temp –40-245 DEG F MTRB
Comp Motor Winding Temp –40-245 DEG F MTRW
Spare Temperature 1 –40-245 DEG F SPARE_T1
Spare Temperature 2 –40-245 DEG F SPARE_T2
Oil Heater Relay 0/1 OFF/ON OILHEAT
Diffuser Actuator 0-100 % DIFF_ACT
**Target VFD Speed 0-110 % VFD_OUT
**Actual VFD Speed 0-110 % VFD_ACT
Surge Protection Counts 0-5 SPC
HGBP Active Region 0-2 See Note 2 HGBP_ACT
MENU
STATUS
COMPRESS
SELECT