Specifications
26
Table 3 — ICVC Display Data (cont)
EXAMPLE 3 — VPF STAT DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
NOTE: All variables with CAPITAL LETTER point names are avail-
able for CCN read operation. Those shown with (**) shall support
write operations for the ICVC only.
EXAMPLE 4 — VDO STAT DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
NOTE: All variables with CAPITAL LETTER point names are avail-
able for CCN read operation. Those shown with (**) shall support
write operations for the ICVC only.
DESCRIPTION STATUS UNITS POINT
**Target VFD Speed 0-110 % VFD_OUT
Actual Guide Vane Pos 0-100 % GV_ACT
Diffuser Actuator 0-100 % DIFF_ACT
Condenser Refrig Temp –40-245 DEG F CRT
Calc Evap Sat Temp –40-245 DEG F ERT
Active Delta Tsat 0-200 ^F DTS_A
Surge Line Delta Tsat 0-200 ^F DTS_C
Chilled Water Delta T –40-245 ^F CHW_DT
Hot Gas Bypass Relay 0/1 OFF/ON HGBYPASS
Surge Prevention Active? 0/1 NO/YES SHG_ACT
Surge Line High Offset 0.1-3.0 SP_HIGH
Surge/HGBP Delta Tsmin 0.0-150.0 ^F DTsatmin
Surge/HGBP IGVmin 0.0-110.0 % GV_MIN
Surge/HGBP Delta Tsmax 0.0-150.0 ^F DTsatmax
Surge/HGBP IGVmax 0.0-110.0 % GV_MAX
Surge Line Shape Factor –1.000-0.000 shapefac
Surge Line Speed Factor 0.00-3.00 VFD_POW
Surge Delta % Amps 5-40 % surge_a
Surge Time Period 7-10 min surge_t
Surge Delta % Amps Min 0-40 % amps_min
MENU
STATUS
VPF_STAT
SELECT
DESCRIPTION STATUS UNITS POINT
Actual Guide Vane Pos 0-100 % GV_ACT
Diffuser Actuator 0-100 % DIFF_ACT
Calc SRD A Pos (output) 0-100 % SRD_A
Calc Low Lift SRD Pos 1 0-100 % SRD_1
Calc Low Lift SRD Pos 2 0-100 % SRD_2
Lift A (Actual) 0-200 ^F LIFT_A
Lift 1 0-200 ^F LIFT_1
Lift 2 0-200 ^F LIFT_2
Startup Timer 0.0-30.0 min STRT_TMR
SRD Rotating Stall 0/1 NO/YES DIFFAULT
SRD Stall Closure Timer 0.0-30.0 min STALLTMR
Surge Counts 0-5 SC
MENU
STATUS
VDO STAT
SELECT