19XR, XRV PIC II RAMP_DEM TABLE CONFIGURATION SHEET
19XR, XRV PIC II TEMP_CTL TABLE CONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
Pulldown Ramp Type:
Select: Temp=0, Load=1
0/1 1
Demand Limit + kW Ramp
Demand Limit Source
Select: Amps=0, kW=1
0/1 0
Motor Load Ramp% Min 5 to 20 10
Demand Limit Prop Band 3 to 15 % 10
Demand Limit At 20 mA 40 to 100 % 40
20 mA Demand Limit Opt 0/1 DSABLE/ENABLE DSABLE
Motor Rated Kilowatts 50 to 9999 kW 145
Demand Watts Interval 5 to 60 MIN 15
DESCRIPTION RANGE UNITS DEFAULT VALUE
Control Point
ECW Control Option 0/1 DSABLE/ENABLE DSABLE
Temp Pulldown Deg/Min
2 to 10
0.6 to 5.6
ˆF
ˆC
3
1.7
Temperature Reset
RESET TYPE 1
Degrees Reset At 20 mA
–30 to 30
–17 to 17
ˆF
ˆC
10
6
RESET TYPE 2
Remote Temp -> No Reset
–40 to 245
–40 to 118
DEG F
DEG C
85
29
Remote Temp -> Full Reset
–40 to 245
–40 to 118
DEG F
DEG C
65
18
Degrees Reset
–30 to 30
–17 to 17
ˆF
ˆC
10
6
RESET TYPE 3
CHW Delta T -> No Reset
0 to 15
0 to 8
ˆF
ˆC
10
6
CHW Delta T -> Full Reset
0 to 15
0 to 8
ˆF
ˆC
0
0
Degrees Reset
–30 to 30
–17 to 17
ˆF
ˆC
5
3
Select/Enable Reset Type 0 to 3 0