Specifications

CL-7
19XR, XRV PIC II OPTIONS TABLE CONFIGURATION SHEET — MACHINES WITH SERIAL NUMBERS
1410QXXXXX AND LATER OR VERSION 9 OR LATER SOFTWARE
NOTE: No variables are available for CCN read or write operation.
DESCRIPTION RANGE UNITS DEFAULT VALUE
Auto Restart Option 0/1 DSABLE/ENABLE DSABLE
Remote Contacts Option 0/1 DSABLE/ENABLE DSABLE
Soft Stop Amps Threshold 40 to 100 % 100
Surge / Hot Gas Bypass
Surge Limit/HGBP Option 0/1 0
Select: Surge=0, HGBP=1
Minimum Load Point
Surge/HGBP Delta Tsmin
0.0 to 150.0
0.0 to 83.3
ˆF
ˆC
45
25.0
Surge/HGBP IGVmin 0.0 to 110.0 % 5.0
Full Load Point
Surge/HGBP Delta Tsmax
0.0 to 150.0
0.0 to 83.3
ˆF
ˆC
70
38.9
Surge/HGBP IGVmax 0.0 to 110.0 % 5.0
Surge Line Shape Factor –1.000 to 0.000 –0.040
Surge Line Speed Factor 0.00 to 3.00 1.85
Surge Line High Offset
0.1 to 3.0
0.1 to 1.7
ˆF
ˆC
1.0
0.6
Surge/HGBP Deadband
0.5 to 3
0.3 to 1.7
ˆF
ˆC
1
0.6
Low Load HGBP
HGBP On Delta T
0.5 to 10.0
0.3 to 5.6
ˆF
ˆC
2.0
1.1
HGBP Off Delta T
1.0 to 10.0
0.3 to 5.6
ˆF
ˆC
4.0
2.2
Surge Protection
Surge Delta% Amps 5 to 20 % 10
Surge Time Period 7 to 10 MIN 8
Ice Build Control
Ice Build Option 0/1 DSABLE/ENABLE DSABLE
Ice Build Termination 0 to 2 0
0=Temp, 1=Contacts, 2=Both
Ice Build Recycle 0/1 DSABLE/ENABLE DSABLE
Refrigerant Leak Option 0/1 DSABLE/ENABLE DSABLE
Refrigerant Leak Alarm mA 4 to 20 mA 20
Head Pressure Reference
Delta P at 0% (4mA)
20 to 85
138 to 586
PSI
kPa
25
172
Delta P at 100% (20mA)
20 to 85
138 to 586
PSI
kPa
35
345
Minimum Output 0 to 100 % 0