Specifications
CL-5
19XR, XRV PIC II ISM_CONF TABLE CONFIGURATION SHEET
* Option 3 for VFD is available on software version 9 or higher. All
other software versions use Option 2 for VFD.
19XR, XRV PIC II OPTIONS TABLE CONFIGURATION SHEET — MACHINES WITH SERIAL NUMBERS PRIOR TO
1410QXXXXX
DESCRIPTION RANGE UNITS DEFAULT VALUE
Starter Type*
(0=Full, 1=Red, 2=SS/VFD, 3=VFD)
0 to 3 1
Motor Rated Line Voltage 200 to 13200 VOLTS 460
Volt Transformer Ratio: 1 1 to 115 1
Overvoltage Threshold 105 to 115 % 115
Undervoltage Threshold 85 to 95 % 85
Over/Under Volt Time 1 to 10 SEC 5
Voltage% Imbalance 1 to 10 % 10
Voltage Imbalance Time 1 to 10 SEC 5
Motor Rated Load Amps 10 to 5000 AMPS 200
Motor Locked Rotor Trip 100 to 60000 AMPS 1000
Locked Rotor Start Delay 1 to 10 cycles 5
Starter LRA Rating 100 to 60000 AMPS 2000
Motor Current CT Ratio: 1 10 to 1000 100
Current% Imbalance 5 to 100 % 15
Current Imbalance Time 1 to 10 SEC 5
Grnd Fault CT’s? 0/1 NO/YES YES
Ground Fault CT Ratio: 1 150 150
Ground Fault Current 1 to 25 AMPS 15
Ground Fault Start Delay 1 to 20 cycles 10
Ground Fault Persistence 1 to 10 cycles 5
Single Cycle Dropout 0/1 DSABLE/ENABLE DSABLE
Frequency-60 Hz? (No=50) 0/1 NO/YES YES
Line Frequency Faulting 0/1 DSABLE/ENABLE DSABLE
DESCRIPTION RANGE UNITS DEFAULT VALUE
Auto Restart Option 0/1 DSABLE/ENABLE DSABLE
Remote Contacts Option 0/1 DSABLE/ENABLE DSABLE
Soft Stop Amps Threshold 40 to 100 % 100
Surge/Hot Gas Bypass
Surge Limit/HGBP Option
Select: Surge=0, HGBP=1
0/1 0
Min. Load Point (T1, P1)
Surge/HGBP Delta T1
0.5 to 20
0.3 to 11.1
ˆF
ˆC
1.5
0.83
Surge/HGBP Delta P1
30 to 170
207 to 1172
PSI
kPa
50
344
Low Load Point (T2, P2)
Surge/HGBP Delta T2
0.5 to 20
0.3 to 11.1
ˆF
ˆC
10
5.5
Surge/HGBP Delta P2
30 to 170
207 to 1172
PSI
kPa
85
586