Specifications

CL-3
19XR, XRV PIC II SETPOINT TABLE CONFIGURATION SHEET
ICVC Software Version Number:
ICVC Controller Identification: BUS: ADDRESS:
DESCRIPTION RANGE UNITS DEFAULT VALUE
Base Demand Limit 40 to 100 % 100
LCW Setpoint
10 to 120
-9.4 to 48.9
DEG F
DEG C
50.0
10.0
ECW Setpoint
15 to 120
-12.2 to 48.9
DEG F
DEG C
60.0
15.6
Ice Build Setpoint
15 to 60
-9.4 to 15.6
DEG F
DEG C
40.0
4.4
Tower Fan High Setpoint
55 to 105
13 to 41
DEG F
DEG C
75
24