Specifications

134
Table 24A — 19XR Waterbox Cover Weights — English (lb
)
LEGEND
NOTE: Weight for NIH 2-pass cover, 150 psig, is included in the heat
exchanger weights shown in Tables 20A and 20B.
FRAMES 1, 2, and 3 — COOLER
WATERBOX DESCRIPTION
Frame 1 Frame 2 Frame 3
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
NIH, 1 Pass Cover, 150 psig 177 204 282 318 282 318
NIH, 2 Pass Cover, 150 psig 185 218 287 340 287 340
NIH, 3 Pass Cover, 150 psig 180 196 294 310 294 310
NIH Plain End Cover, 150 psig 136 136 243 243 243 243
MWB End Cover, 150 psig 315 315 315 315
MWB Return Cover, 150 psig 243 243 243 243
NIH, 1 Pass Cover, 300 psig 248 301 411 486 411 486
NIH, 2 Pass Cover, 300 psig 255 324 411 518 411 518
NIH, 3 Pass Cover, 300 psig 253 288 433 468 433 468
NIH Plain End Cover, 300 psig 175 175 291 291 291 291
MWB End Cover, 300 psig 619 619 619 619
MWB Return Cover, 300 psig 445 445 445 445
WATERBOX DESCRIPTION
FRAMES 1, 2, and 3 — CONDENSER
Frame 1Frame 2Frame 3
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
NIH, 1 Pass Cover, 150 psig 177 204 282 318 282 318
NIH, 2 Pass Cover, 150 psig 185 218 287 340 287 340
NIH, 3 Pass Cover, 150 psig 180 196 294 310 294 310
NIH Plain End Cover, 150 psig 136 136 225 225 225 225
MWB End Cover, 150 psig 234 234 234 234
MWB Return Cover, 150 psig 225 225 225 225
NIH, 1 Pass Cover, 300 psig 248 301 411 486 411 486
NIH, 2 Pass Cover, 300 psig 255 324 411 518 411 518
NIH, 3 Pass Cover, 300 psig 253 288 433 468 433 468
NIH Plain End Cover, 300 psig 175 175 270 270 270 270
MWB End Cover, 300 psig 474 474 474 474
MWB Return Cover, 300 psig 359 359 359 359
NIH Nozzle-in-Head
MWB Marine Waterbox