Specifications
Perform a Control Test — Check the safety controls
status by performing an automated control test. Access the
CONTROL TEST table and select a test to be performed
function (Table 6).
The Automated Control Test checks all outputs and inputs
for function. The compressor must be in the OFF mode to
operate the controls test. The compressor can be put in OFF
mode by pressing the STOP push-button on the CVC. Each
test asks the operator to confirm the operation is occurring
and whether or not to continue. If an error occurs, the op-
erator can try to address the problem as the test is being done
or note the problem and proceed to the next test.
NOTE: Enter guide vane calibration to calibrate guide
input on CCM (Plug J4 upper terminal 9 and 10).
NOTE: If during the control test the guide vanes do not open,
verify the low pressure alarm is not active. (An active low
pressure alarm causes the guide vanes to close.)
NOTE: The oil pump test will not energize the oil pump if
cooler pressure is below –5 psig (–35 kPa).
When the control test is finished or the EXIT
softkey is
pressed, the test stops, and the CONTROL TEST menu dis-
plays. If a specific automated test procedure is not com-
pleted, access the particular control test to test the function
when ready. The CONTROL TEST menu is described in the
table below.
CCM Pressure Thermistors Check of all thermistors.
CCM Pressure Transducers Check of all transducers.
Pumps Checks operation of pump out-
puts; pumps are activated. Also
tests associated inputs such as
flow or pressure.
Discrete Ouputs Activation of all on/off outputs
individually.
Guide Vane Check of the guide vane
operation.
Pumpdown/Lockout Pumpdown prevents the low re-
frigerant alarm during evacuation
so refrigerant can be removed
form the unit. Also locks the
compressor off and starts the
water pumps.
Terminate Lockout To charge refrigerant and enable
the chiller to run after pumpdown
lockout.
Guide Vane Calibration Calibrates guide vane input on
CCM.
NOTE: During any of the tests, an out-of-range reading will have an
asterisk (*) next to the reading and a message will be displayed.
COOLER CONDENSER PRESSURE TRANSDUCER AND
WATERSIDE FLOW DEVICE CALIBRATION — Cali-
bration can be checked by comparing the pressure readings
from the transducer to an accurate refrigeration gage read-
ing. These readings can be viewed or calibrated from the
HEAT_EX screen on the CVC. The transducer can be checked
and calibrated at 2 pressure points. These calibration points
are 0 psig (0 kPa) and between 25 and 250 psig (173 and
1724 kPa). To calibrate these transducers:
1. Shut down the compressor, cooler, and condenser pumps.
NOTE: There should be no flow through the heat
exchangers.
2. Disconnect the transducer in question from its Schrader
fitting for cooler or condenser transducer calibration. For
oil pressure or flow device calibration keep transducer in
place.
NOTE: If the cooler or condenser vessels are at 0 psig
(0 kPa) or are open to atmospheric pressure, the trans-
ducers can be calibrated for zero without removing the
transducer from the vessel.
3. Access the HEAT_EX screen and view the particular
transducer reading (the EVAPORATOR PRESSURE or
CONDENSER PRESSURE parameter on the HEAT_EX
screen). To calibrate oil pressure or waterside flow de-
vice, view the particular reading (CHILLED WATER DELTA
P and CONDENSER WATER DELTA P on the HEAT_EX
screen, and OIL PUMP DELTA P on the COMPRESS
screen). It should read 0 psi (0 kPa). If the reading is not
0 psi (0 kPa), but within ± 5 psi (35 kPa), the value may
be set to zero by pressing the SELECT
softkey while
the appropriate transducer parameter is highlighted on the
CVC screen. Then press the ENTER
softkey. The value
will now go to zero. No high end calibration is necessary
for OIL PUMP DELTA P or flow devices.
If the transducer value is not within the calibration range,
the transducer returns to the original reading. If the pres-
sure is within the allowed range (noted above), check the
voltage ratio of the transducer. To obtain the voltage ra-
tio, divide the voltage (dc) input from the transducer by
the supply voltage signal (displayed in CONTROL TEST
menu in the CCM PRESSURE TRANSDUCERS screen)
or measure across the positive (+ red) and negative
(− black) leads of the transducer. For example, the con-
denser transducer voltage input is measured at CCM ter-
minals J2-4 and J2-5. The voltage ratio must be between
0.80 and 0.11 for the software to allow calibration. Pres-
surize the transducer until the ratio is within range. Then
attempt calibration again.
4. A high pressure point can also be calibrated between 25
and 250 psig (172.4 and 1723.7 kPa) by attaching a regu-
lated 250 psig (1724 kPa) pressure (usually from
a nitrogen cylinder). The high pressure point can be cali-
brated by accessing the appropriate transducer parameter
on the HEAT_EX screen, highlighting the parameter, press-
ing the SELECT
softkey, and then using the
INCREASE
or DECREASE softkeys to adjust the
value to the exact pressure on the refrigerant gage. Press
the ENTER
softkey to finish the calibration. Pressures
at high altitude locations must be compensated for, so the
chiller temperature/pressure relationship is correct.
The PIC II does not allow calibration if the transducer is
too far out of calibration. In this case, a new transducer must
be installed and re-calibrated.
Check Optional Pumpout System Controls and
Compressor —
Controls include an on/off switch, a 3-amp
fuse, the compressor overloads, an internal thermostat, a com-
pressor contactor, and a refrigerant high pressure cutout.
The high pressure cutout is factory set to open at 161 psig
(1110 kPa) and reset at 130 psig (896 kPa). Ensure the water-
cooled condenser has been connected. Loosen the
compressor holddown bolts to allow free spring travel. Open
the compressor suction and discharge the service valves. En-
sure oil is visible in the compressor sight glass. Add oil if
necessary.
See the Pumpout and Refrigerant Transfer Procedures and
Optional Pumpout System Maintenance sections, pages 63
and 70, for details on the transfer of refrigerant, oil speci-
fications, etc.
High Altitude Locations — Because the chiller is ini-
tially calibrated at sea level, it is necessary to recalibrate
the pressure transducers if the chiller has been moved to a
high altitude location. See the calibration procedure in the
Troubleshooting Guide section.
57










