Specifications

3. Press SELECT to select the highlighted value. Then:
For Discrete Points Press YES or NO to se-
lect the desired state.
YES NO ENTER EXIT
For Analog Points Press INCREASE or
DECREASE
to select the desired value.
4. Press ENTER to register the new value.
NOTE: When overriding or changing metric values, it is nec-
essary to hold down the softkey for a few seconds in order
to see a value change, especially on kilopascal values.
To Remove an Override
1. On the point status table press NEXT or
PREVIOUS
to highlight the desired value.
2. Press SELECT to access the highlighted value.
3. Press RELEASE to remove the override and return the
point to the PIC II’s automatic control.
Override Indication An override value is indicated by
‘SUPVSR,’‘SERVC,’or ‘BEST’flashing next to the point
value on the STATUS table.
TIME SCHEDULE OPERATION (Fig. 17)
1. On the Menu screen, press SCHEDULE
.
2. Press NEXT or PREVIOUS to highlight the de-
sired schedule.
OCCPC01S LOCAL Time Schedule
OCCPC02S ICE BUILD Time Schedule
OCCPC03S CCN Time Schedule
3. Press SELECT to view the desired time schedule.
4. Press NEXT or PREVIOUS to highlight the de-
sired period or override to change.
5. Press SELECT to access the highlighted period or
override.
6. a. Press INCREASE or DECREASE to change the
time values. Override values are in one-hour incre-
ments, up to 4 hours.
Fig. 17 Example of Time Schedule
Operation Screen
20