Specifications
97
Table 18 — Optional Pumpout System
Electrical Data
LEGEND
Table 19 — Additional Miscellaneous Weights
Table 20 — Motor Voltage Code
MOTOR
CODE
CONDENSER
UNIT
VOLTS-PH-Hz
MAX
RLA
LRA
1
19EA47-748 575-3-60 3.8 23.0
4
19EA42-748 200/208-3-60 10.9 63.5
5
19EA44-748 230-3-60 9.5 57.5
6
19EA46-748 400/460-3-50/60 4.7 28.8
LRA —
Locked Rotor Amps
RLA —
Rated Load Amps
ITEM Lb Kg
CONTROL CABINET
30 14
UNIT-MOUNTED STARTER
500 227
OPTIONAL ISOLATION VALVES
115 52
UNIT MOUNTED VFD
1000 454
MOTOR VOLTAGE CODE
Code Volts Frequency
60
200 60
61
230 60
62
380 60
63
416 60
64
460 60
65
575 60
66
2400 60
67
3300 60
68
4160 60
69
6900 60
50
230 50
51
346 50
52
400 50
53
3000 50
54
3300 50
55
6300 50