Specifications

28
Table 2 CVC Display Data (cont)
EXAMPLE 13 ISM_HIST DISPLAY SCREEN
To access this display from the
CVC default
screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight
.
6. Press .
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance
screens.
EXAMPLE 14 WSMDEFME DISPLAY SCREEN
To access this display from the
CVC default
screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight
.
6. Press .
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance
screens.
DESCRIPTION STATUS UNITS POINT
ISM FAULT HISTORY
Values At Last Fault:
Line Current Phase 1
0-99999 AMPS AMPS_1F
Line Current Phase 2
0-99999 AMPS AMPS_2F
Line Current Phase 3
0-99999 AMPS AMPS_3F
Line Voltage Phase 1
0-99999 VOLTS VOLTS_1F
Line Voltage Phase 2
0-99999 VOLTS VOLTS_2F
Line Voltage Phase 3
0-99999 VOLTS VOLTS_3F
Ground Fault Phase 1
0-999 AMPS GF_1F
Ground Fault Phase 2
0-999 AMPS GF_2F
Ground Fault Phase 3
0-999 AMPS GF_3F
I2T Sum Heat-Phase 1
0-200 % HEAT1SUMF
I2T Sum Heat-Phase 2
0-200 % HEAT2SUMF
I2T Sum Heat-Phase 3
0-200 % HEAT3SUMF
Phase 1 Faulted?
0/1 NO/YES PH1_FLT
Phase 2 Faulted?
0/1 NO/YES PH2_FLT
Phase 3 Faulted?
0/1 NO/YES PH3_FLT
Line Frequency
0-99 Hz FREQ_ F
ISM Fault Status
0-9999 ISM_STAT
DESCRIPTION STATUS UNITS POINT
WSM Active?
0/1 NO/YES WSMSTAT
Chilled Water Temp
0.0-99.9 DEG F CHWTEMP
Equipment Status
0/1 OFF/ON CHLRST
Commanded State
XXXXXXXX TEXT CHLRENA
CHW setpt Reset Value
0.0-25.0 DEG F CHWRVAL
Current CHW Set Point
0.0-99.9 DEG F CHWSTPT
MENU
SERVICE
CONTROL ALGORITHM STATUS
SELECT
ISM_HIST
SELECT
MENU
SERVICE
CONTROL ALGORITHM STATUS
SELECT
WSMDEFME
SELECT