Specifications

27
Table 2 CVC Display Data (cont)
EXAMPLE 11 OVERRIDE DISPLAY SCREEN
To access this display from the
CVC default
screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight
.
6. Press
.
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance
screens.
EXAMPLE 12 LL_MAINT DISPLAY SCREEN
To access this display from the
CVC default
screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight
6. Press .
NOTES:
1. DISABLE, LEAD, LAG, STANDBY, INVALID
2. DISABLE, LEAD, LAG, STANDBY, RECOVERY, CONFIG
3. Reset, Off, Local, CCN
4. Timeout, Ready, Recycle, Prestart, Startup, Ramping, Running, Demand, Override, Shutdown, Trippout, Pumpdown, Lockout
5. Stop, Start, Retain
6. All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance screens.
DESCRIPTION STATUS UNITS POINT
Comp Motor Winding Temp
40-245 DEG F MTRW
Comp Motor Temp Override
150-200 DEG F mt_over
Condenser Pressure
0-420 PSI CRP
Cond Press Override
90-180 PSI cp_over
Evaporator Refrig Temp
40-245 DEG F ERT
Evap Ref Override Temp
2-45 DEG F rt_over
Comp Discharge Temp
40-245 DEG F CMPD
Comp Discharge Alert
125-200 DEG F cd_alert
Comp Thrust Brg Temp
40-245 DEG F MTRB
Comp Thrust Brg Alert
165-185 DEG F tb_alert
Actual Superheat
20-99 ^F SUPRHEAT
Superheat Required
6-99 ^F SUPR_REQ
Condenser Refrig Temp
40-245 DEG F CRT
DESCRIPTION STATUS UNITS POINT
Lead Lag Control
LEADLAG: Configuration
NOTE 1 leadlag
Current Mode
NOTE 2 llmode
Load Balance Option
0/1 DSABLE/ENABLE loadbal
LAG START Time
2-60 MIN lagstart
LAG STOP Time
2-60 MIN lagstop
Prestart Fault Time
2-30 MIN preflt
Pulldown: Delta T / Min
x.xx ^F pull_dt
Satisfied ?
0/1 NO/YES pull_sat
LEAD CHILLER in Control
0/1 NO/YES leadctrl
LAG CHILLER: Mode
NOTE 3 lagmode
Run Status
NOTE 4 lagstat
Start/Stop
NOTE 5 lag_s_s
Recovery Start Request
0/1 NO/YES lag_rec
STANDBY CHILLER: Mode
NOTE 3 stdmode
Run Status
NOTE 4 stdstat
Start/Stop
NOTE 5 Std_s_s
Recovery Start Request
0/1 NO/YES std_rec
Spare Temperature 1
40-245 DEG F SPARE_1
Spare Temperature 2
40-245 DEG F SPARE_2
MENU
SERVICE
CONTROL ALGORITHM STATUS
SELECT
OVERRIDE
SELECT
MENU
SERVICE
CONTROL ALGORITHM STATUS
SELECT
LL_MAINT.
SELECT